Step 14—Final Checks

IMPORTANT:

Before leaving job, be sure to do the following:

1. Securely fasten all panels and covers.

2. Tighten service valve stem caps to 1/12-turn past finger tight.

3. Leave User’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

4. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment.

Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications.

Table 3—Required Liquid-Line Temperature (°F)

LIQUID

PRESSURE AT

SERVICE VALVE

(PSIG)

REQUIRED SUBCOOLING

TEMPERATURE

(°F)

5

10

15

20

134

71

66

61

56

141

74

69

64

59

148

77

72

67

62

156

80

75

70

65

163

83

78

73

68

171

86

81

76

71

179

89

84

79

74

187

92

87

82

77

196

95

90

85

80

205

98

93

88

83

214

101

96

91

86

223

104

99

94

89

233

107

102

97

92

243

110

105

100

95

253

113

108

103

98

264

116

111

106

101

274

119

114

109

104

285

122

117

112

107

297

125

120

115

110

309

128

123

118

113

321

131

126

121

116

331

134

129

124

119

346

137

132

127

122

359

140

135

130

125

Copyright 2002 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231

38ysa4si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

5a 5a

PC 101

Catalog No. 533-80022

Printed in U.S.A.

Form 38YSA-4SI

Pg 12

02-02

Replaces: 38YSA3SI

Содержание 38YSA

Страница 1: ...nal injury or death INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows p...

Страница 2: ...irflow a 6 in clearance on 1 side of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall di...

Страница 3: ...it Step 8 Make Piping Connections Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow con...

Страница 4: ...oltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not...

Страница 5: ...asses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise valve stem...

Страница 6: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Страница 7: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Страница 8: ...VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN COI...

Страница 9: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Страница 10: ...UMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL LEGEND 24 V FACTORY WIRI...

Страница 11: ...observe a complete defrost in warmer weather the thermostat must be closed as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board See Fig 15 Tape to...

Страница 12: ...ature F LIQUID PRESSURE AT SERVICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 5 10 15 20 134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79...

Отзывы: