7
Electrical data
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable
(NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
** Time-delay fuse.
NOTE:
Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compressors contain
internal overload protection.
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
.
OUTDOOR
UNIT
V/PH
60 Hz
OPERATING VOLTS*
COMPRESSOR
FAN
FLA
MCA
60°C
MIN
WIRE
SIZE†
75°C
MIN
WIRE
SIZE†
60°C
MAX
LENGTH
(Ft)‡
75°C
MAX
LENGTH
(Ft)‡
MAX FUSE**
OR CKT
BKR AMPS
Max
Min
LRA
RLA
018-32
208-230/1
253
197
49.0
9.8
0.5
12.8
14
14
70
70
20
024-32
61.0
11.4
0.5
14.8
14
14
50
45
20
030-33
75.0
13.7
1.4
18.5
14
14
40
40
30
036-33
105.0
18.0
1.4
23.9
12
12
50
50
35
036-34
86.0
17.2
1.4
22.9
12
12
55
52
35
042-34
115.0
24.4
1.4
31.9
8
10
97
59
50
042-36
127.0
22.9
1.4
30.0
10
10
67
63
50
048-32
140.0
24.4
1.4
31.9
8
8
90
90
50
048-34
131.0
22.0
1.4
29.0
8
10
107
66
50
060-32
165.0
30.8
1.4
39.9
8
8
75
70
60
060-34
148.0
30.8
1.4
39.9
8
8
75
70
60
HEAT PUMP SYSTEM
This heat pump can be part of a Comfort Heat Pump System which can
provide higher heating supply air temperatures, as well as up to 30 times
more humidity removal in cooling mode. A Comfort Heat Pump System
requires the use of a Variable-Speed Fan Coil with Thermidistat Control.