20
Detailed cooling capacities* continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-94. If additional tubing length and/
or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835
Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S)
of indoor coil air per degree above 80°F (27°C).
** System kW is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB — Entering Wet Bulb
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES
°
F
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
38YCG060-32, 34 Outdoor Section With F(A,B)4(A,B)N(F,B)060 Indoor Section
1800
72
67
63††
62
57
63.8
58.2
54.1
53.2
52.0
31.9
41.1
39.8
49.8
52.0
5.67
5.55
5.46
5.44
5.42
60.9
55.5
51.5
50.7
50.0
30.9
40.0
38.7
48.6
50.0
6.17
6.03
5.94
5.93
5.91
57.9
52.6
48.9
48.3
48.0
29.9
38.8
37.6
47.3
48.0
6.70
6.57
6.47
6.45
6.45
54.8
49.8
46.1
45.8
45.8
28.8
37.7
36.4
45.7
45.8
7.29
7.15
7.04
7.03
7.03
51.6
46.8
43.2
43.4
43.4
27.7
36.6
35.2
43.4
43.4
7.93
7.78
7.66
7.67
7.67
2000
72
67
63††
62
57
64.4
58.8
54.7
54.0
53.5
33.1
43.1
41.7
52.4
53.5
5.79
5.67
5.58
5.56
5.55
61.5
56.0
52.1
51.6
51.4
32.1
42.0
40.6
51.0
51.4
6.29
6.15
6.06
6.04
6.04
58.4
53.2
49.3
49.2
49.2
31.0
40.9
39.4
49.2
49.2
6.82
6.68
6.58
6.58
6.58
55.3
50.2
46.6
46.9
46.9
29.9
39.7
38.3
46.9
46.9
7.41
7.26
7.16
7.17
7.17
51.9
47.1
43.6
44.5
44.5
28.8
38.5
37.0
44.5
44.5
8.05
7.89
7.78
7.81
7.81
2200
72
67
63††
62
57
64.9
59.3
55.1
54.8
54.7
34.2
45.0
43.5
54.5
54.7
5.90
5.78
5.69
5.68
5.68
62.0
56.5
52.4
52.6
52.5
33.2
43.9
42.4
52.6
52.5
6.40
6.26
6.17
6.17
6.17
58.9
53.6
49.7
50.3
50.3
32.1
42.8
41.2
50.3
50.3
6.94
6.79
6.70
6.71
6.71
55.6
50.6
46.9
47.9
47.9
31.0
41.6
40.0
47.9
47.9
7.53
7.38
7.27
7.30
7.30
52.2
47.4
43.9
45.4
45.4
29.9
40.4
38.7
45.4
45.4
8.17
8.01
7.89
7.94
7.94
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CC5A/CD5AA
060
0.96
0.94
CK5A/CK5BX
060
1.00
0.92
CC5A/CD5AW
060
0.99
0.96
COILS + 58CV(A,X)135-22 VARIABLE-SPEED FURNACE
CE3AA
060
1.00
0.96
CC5A/CD5AA
060
0.96
0.92
CK3BA
060
0.96
0.92
CC5A/CD5AW
060
0.98
0.92
CK5A/CK5BA
060
0.96
0.92
CE3AA
060
0.99
0.92
CK5A/CK5BT
060
0.96
0.92
CK3BA
060
0.98
0.93
CK5A/CK5BX
060
0.99
0.95
CK5A/CK5BA
060
0.98
0.93
F(A,B)4(A,B)N(F,B,C)
060
1.00
1.00
CK5A/CK5BT
060
0.98
0.94
FB4(A,B)NB
070
1.01
1.01
CK5A/CK5BX
060
1.00
0.92
FC4(B,C)N(F,B)
060
1.00
0.96
COILS + 58CV(A,X)155-22 VARIABLE-SPEED FURNACE
FC4(B,C)NB
070
1.01
1.01
CC5A/CD5AA
060
0.96
0.91
FG3AAA
060
0.97
0.94
CC5A/CD5AW
060
0.98
0.92
FK4(C,D)NB
006
1.00
0.94
CE3AA
060
0.99
0.91
COILS + 58CV(A,X)110-22 VARIABLE-SPEED FURNACE
CK3BA
060
0.98
0.93
CC5A/CD5AA
060
0.96
0.92
CK5A/CK5BA
060
0.98
0.93
CE3AA
060
0.99
0.92
CK5A/CK5BT
060
0.98
0.93
CK3BA
060
0.98
0.93
CK5A/CK5BX
060
1.00
0.91
CK5A/CK5BA
060
0.98
0.93
—
—
—
CK5A/CK5BT
060
0.98
0.93