3
Physical data
* Tube sizes are for lengths up to 50 ft. For lengths over 50 ft and/or 20 ft vertical differential, consult Residential Split-Systems Long-Line Application Guideline.
NOTE:
See unit Installation Instructions for proper installation.
METERING DEVICE
*Piston listed is for any approved coil combination.
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)
UNIT SIZE
018
024
030
036
042
048
060
SERIES
32
32
33
33/34
34/36
32/34
32/34
OPERATING WT (Lb)
127
143
153/157
176/185
195/197
219
237
COMPRESSOR
Type
Reciprocating
Scroll/Reciprocating
Scroll
REFRIGERANT
Control
Charge (Lb) @ 15 ft
R-22
Piston
4.69
4.75
5.63
6.38
7.88
9.25/9.38
10.50/10.25
CONDENSER FAN
Air Discharge
Air Qty (CFM)
Motor HP
Motor RPM (60 Hz)
Propeller Type, Direct Drive
Vertical
1900
1900
2300
3000
3000
3300
3300
1/12
1/12
1/4
1/4
1/4
1/4
1/4
1100
1125
1125
1100
1100
1100
1100
CONDENSER COIL
Face Area (Sq Ft)
Fins per In.
Rows
Circuit
9.10
9.11
12.42
14.8
18.5
22.40
22.40
20
25
20
20
20
20
25
1
1
1
1
1
1
1
2
3
3
3
4
4
5
CONNECTION (In. ID)
Vapor
Liquid
Sweat
5/8
5/8
3/4
3/4
7/8
7/8
7/8
3/8
REFRIGERANT TUBES*
(In. OD)
Vapor (0–50 Ft Tube Length)
Vapor (Max Diameter for
Long-Line Applications)
Liquid (0–50 Ft Tube Length)
Liquid (For Long-Line
Applications)
5/8
5/8
3/4
3/4
7/8
7/8
1-1/8
3/4
3/4
7/8
7/8
1-1/8
1-1/8
1-1/8
3/8
3/8
UNIT
SIZE
SERIES
OUTDOOR
PISTON
INDOOR
PISTON*
018
32
40
52
024
32
49
63
030
33
55
70
036
33
61
76
036
34
57
70
042
34, 36
63
78
048
32/34
73/70
88/86
060
32, 34
76
96
UNIT
SIZE
REQUIRED
SUBCOOLING (°F)
018
14
024
10
030
8
036 (33)
12
036 (34)
14
042
16
048-32/34
10/15
060
10