27
Heat pump heating performance continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
† The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from sup-
plement heaters should be added to those values to obtain total system capacity.
‡ The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these
values to obtain total system kilowatts.
EDB — Entering Dry Bulb
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).
4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).
5. Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and 9 following.)
8. For interconnecting refrigerant tube lengths between 50 and 175 ft and/or 20 ft vertical differential, consult the Residential Split-System Long-Line Application
Guideline available from equipment distributor.
9. If any refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be
buried without further consideration. For buried refrigerant tubing lengths greater than 36 in., consult your local distributor.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°
F
–3
7
17
27
37
47
57
67
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
EDB
CFM Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡ Total Integ† kW‡
38YCG060-32, 34 Outdoor Section With F(A,B)4(A,B)N(F,B)060 Indoor Section
65
1800
2000
2200
30.0
30.4
30.8
27.6
27.9
28.3
4.24
4.31
4.38
34.6
35.0
35.4
31.8
32.2
32.5
4.37
4.43
4.49
39.4
39.9
40.2
36.0
36.3
36.7
4.51
4.55
4.60
44.9
45.4
45.8
39.9
40.3
40.7
4.67
4.70
4.74
50.7
51.2
51.7
46.2
46.6
47.0
4.85
4.88
4.91
58.1
58.7
59.2
58.1
58.7
59.2
5.12
5.13
5.16
66.6
66.4
66.2
66.6
66.4
66.2
5.47
5.42
5.40
71.9
71.1
70.4
71.9
71.1
70.4
5.69
5.61
5.57
70
1800
2000
2200
29.4
29.9
30.3
27.1
27.5
27.9
4.38
4.45
4.52
34.3
34.7
35.1
31.5
31.9
32.2
4.54
4.59
4.65
39.1
39.5
39.9
35.6
36.0
36.4
4.68
4.72
4.78
44.5
44.9
45.4
39.5
39.9
40.3
4.85
4.88
4.93
50.2
50.7
51.2
45.7
46.1
46.5
5.05
5.07
5.10
57.4
58.0
58.5
57.4
58.0
58.5
5.32
5.33
5.36
66.1
66.3
66.1
66.1
66.3
66.1
5.70
5.66
5.63
72.1
70.9
69.9
72.1
70.9
69.9
5.97
5.84
5.78
75
1800
2000
2200
28.9
29.3
29.8
26.5
27.0
27.4
4.53
4.59
4.66
33.9
34.3
34.7
31.2
31.5
31.9
4.71
4.76
4.82
38.7
39.2
39.5
35.3
35.7
36.0
4.87
4.91
4.96
44.1
44.5
44.9
39.2
39.5
39.9
5.05
5.08
5.11
49.7
50.2
50.6
45.2
45.7
46.1
5.25
5.27
5.30
56.8
57.3
57.8
56.8
57.3
57.8
5.54
5.54
5.56
65.5
66.1
66.0
65.5
66.1
66.0
5.94
5.93
5.88
72.2
72.3
70.8
72.2
72.3
70.8
6.26
6.20
6.08
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
CC5A/CD5AA
060
0.97
1.04
CK5A/CK5BT
060
0.97
0.94
CC5A/CD5AW
060
0.97
0.98
CK5A/CK5BX
060
0.97
0.94
CE3AA
060
0.97
0.97
COILS + 58CV(A,X)135-22 VARIABLE-SPEED FURNACE
CK3BA
060
0.97
1.00
CC5A/CD5AA
060
0.96
1.02
CK5A/CK5BA
060
0.97
1.00
CC5A/CD5AW
060
0.95
0.94
CK5A/CK5BT
060
0.97
1.00
CE3AA
060
0.97
0.97
CK5A/CK5BX
060
0.97
0.96
CK3BA
060
0.97
0.94
F(A,B)4(A,B)N(F,B,C)
060
1.00
1.00
CK5A/CK5BA
060
0.97
0.94
FB4(A,B)NB
070
0.98
0.94
CK5A/CK5BT
060
0.97
0.94
FC4(B,C)N(F,B)
060
1.00
1.00
CK5A/CK5BX
060
0.97
0.94
FC4(B,C)NB
070
0.98
0.94
COILS + 58CV(A,X)155-22 VARIABLE-SPEED FURNACE
FG3AAA
060
0.97
0.99
CC5A/CD5AA
060
0.96
1.01
FK4(C,D)NB
006
0.91
0.90
CC5A/CD5AW
060
0.95
0.94
COILS + 58CV(A,X)110-22 VARIABLE-SPEED FURNACE
CE3AA
060
0.97
0.97
CC5A/CD5AA
060
0.96
1.02
CK3BA
060
0.97
0.94
CE3AA
060
0.97
0.97
CK5A/CK5BA
060
0.97
0.94
CK3BA
060
0.97
0.94
CK5A/CK5BT
060
0.97
0.94
CK5A/CK5BA
060
0.97
0.94
CK5A/CK5BX
060
0.97
0.94