8
Detailed cooling capacities* (S.I.) continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 4.55m of tubing. If other than 4.55m of
tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 27
°
C entering air at the indoor coil. For sensible capacities at other than 27
°
C, deduct 245 kw per 480
L/S of indoor coil air for each degree below 27
°
C, or add 245 kw per 480 L/S of indoor coil air per degree above 27
°
C.
** System kw is total of indoor and outdoor unit kilowatt’s.
EWB — Entering Wet Bulb
L/S
— Liters per second
COIL
AIR
CONDENSER ENTERING AIR TEMPERATURES
°
C
28
32
36
40
44
48
52
L/S
(C)
EWB
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Capacity
Kw†
Sys.
Power
Kw**
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total
Sens‡
38YCB048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
650
22
15.4 7.87 4.50 14.9 7.69 4.79 14.4 7.51 5.09 13.9 7.32 5.41 13.3 7.13 5.75 12.8 6.94 6.11 12.3 6.75 6.48
20
14.5 9.38 4.41 14.0 9.19 4.69 13.5 9.00 4.98 13.0 8.81 5.29 12.5 8.62 5.63 12.0 8.42 5.97 11.5 8.23 6.33
18
13.6 10.8 4.32 13.2 10.7 4.59 12.7 10.5 4.88 12.3 10.3 5.18 11.8 10.1 5.51 11.3 9.82 5.84 10.8 9.56 6.19
16
12.9 12.0 4.25 12.5 11.8 4.52 12.1 11.5 4.80 11.7 11.3 5.11 11.3 11.0 5.43 10.9 10.7 5.75 10.4 10.4 6.09
14
12.6 12.6 4.21 12.3 12.3 4.49 12.0 11.9 4.78 11.6 11.6 5.09 11.2 11.2 5.41 10.8 10.8 5.75 10.4 10.4 6.09
750
22
15.6 8.26 4.60 15.1 8.08 4.89 14.6 7.89 5.19 14.1 7.71 5.51 13.5 7.51 5.86 13.0 7.32 6.22 12.4 7.13 6.59
20
14.7 9.96 4.51 14.2 9.78 4.79 13.7 9.59 5.08 13.2 9.39 5.39 12.7 9.19 5.73 12.2 9.00 6.08 11.7 8.80 6.44
18
13.9 11.6 4.42 13.4 11.4 4.69 13.0 11.2 4.98 12.5 10.9 5.29 12.0 10.7 5.62 11.6 10.4 5.97 11.1 10.1 6.32
16
13.3 12.8 4.35 12.9 12.5 4.63 12.5 12.2 4.92 12.0 12.0 5.22 11.6 11.6 5.56 11.2 11.2 5.90 10.8 10.8 6.25
14
13.1 13.1 4.34 12.8 12.7 4.62 12.4 12.4 4.91 12.0 12.0 5.22 11.6 11.6 5.56 11.2 11.2 5.90 10.8 10.8 6.25
850
22
15.8 8.64 4.70 15.3 8.45 4.99 14.8 8.27 5.29 14.2 8.08 5.61 13.7 7.89 5.95 13.1 7.69 6.31 12.5 7.50 6.69
20
14.9 10.5 4.60 14.4 10.3 4.88 13.9 10.2 5.18 13.4 9.96 5.49 12.9 9.75 5.83 12.3 9.55 6.18 11.8 9.35 6.54
18
14.1 12.3 4.51 13.6 12.0 4.79 13.2 11.8 5.08 12.7 11.5 5.40 12.3 11.1 5.74 11.8 10.8 6.09 11.3 10.5 6.45
16
13.6 13.4 4.45 13.2 13.1 4.73 12.8 12.8 5.03 12.4 12.4 5.34 11.9 11.9 5.68 11.5 11.5 6.04 11.1 11.1 6.40
14
13.5 13.5 4.45 13.1 13.1 4.73 12.8 12.8 5.03 12.4 12.4 5.34 11.9 11.9 5.68 11.5 11.5 6.04 11.1 11.1 6.40
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
048
1.00
1.00
FG3ASA
048
0.98
1.00
060
1.03
1.01
060
1.00
1.01
38YCB060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
850
22
19.1
9.97
5.49
18.5
9.74
5.88
17.9
9.52
6.30
17.2
9.28
6.76
16.5
9.05
7.25
15.8
8.80
7.78
15.1
8.55
8.33
20
18.0
12.0
5.35
17.4
11.7
5.73
16.8
11.5
6.15
16.2
11.3
6.60
15.5
11.0
7.09
14.9
10.8
7.60
14.2
10.5
8.15
18
16.9
13.9
5.22
16.4
13.7
5.60
15.8
13.4
6.02
15.2
13.2
6.46
14.7
12.9
6.95
14.1
12.5
7.47
13.5
12.1
8.01
16
16.1
15.4
5.13
15.6
15.1
5.51
15.2
14.8
5.93
14.6
14.4
6.37
14.1
14.0
6.86
13.6
13.6
7.38
13.0
13.0
7.93
14
15.9
15.9
5.10
15.5
15.4
5.49
15.0
15.0
5.91
14.6
14.6
6.36
14.1
14.1
6.86
13.6
13.6
7.38
13.1
13.1
7.93
900
22
19.2
10.2
5.55
18.6
9.94
5.94
17.9
9.71
6.36
17.3
9.48
6.82
16.6
9.25
7.31
15.9
9.00
7.84
15.2
8.76
8.39
20
18.1
12.3
5.41
17.5
12.0
5.79
16.9
11.8
6.21
16.2
11.6
6.66
15.6
11.3
7.15
14.9
11.1
7.66
14.3
10.8
8.21
18
17.0
14.3
5.28
16.5
14.1
5.66
15.9
13.8
6.08
15.4
13.5
6.52
14.8
13.1
7.01
14.2
12.8
7.53
13.6
12.3
8.08
16
16.3
15.8
5.19
15.8
15.5
5.58
15.3
15.1
5.99
14.8
14.7
6.44
14.3
14.3
6.93
13.8
13.8
7.46
13.2
13.2
8.01
14
16.1
16.1
5.17
15.7
15.7
5.56
15.2
15.2
5.98
14.8
14.8
6.44
14.3
14.3
6.94
13.8
13.8
7.46
13.2
13.2
8.01
950
22
19.3
10.4
5.61
18.7
10.1
6.00
18.1
9.92
6.42
17.4
9.68
6.88
16.7
9.45
7.37
16.0
9.20
7.90
15.2
8.95
8.45
20
18.2
12.6
5.46
17.6
12.3
5.85
17.0
12.1
6.26
16.3
11.9
6.71
15.7
11.6
7.20
15.0
11.4
7.72
14.3
11.1
8.26
18
17.1
14.7
5.33
16.6
14.4
5.72
16.0
14.1
6.13
15.5
13.8
6.58
14.9
13.4
7.08
14.3
13.0
7.60
13.7
12.6
8.15
16
16.5
16.1
5.25
16.0
15.8
5.64
15.5
15.4
6.06
15.0
15.0
6.51
14.5
14.5
7.01
13.9
13.9
7.53
13.4
13.4
8.09
14
16.3
16.3
5.24
15.9
15.9
5.63
15.4
15.4
6.05
15.0
15.0
6.51
14.5
14.5
7.01
13.9
13.9
7.53
13.4
13.4
8.09
1000
22
19.4
10.6
5.66
18.8
10.3
6.06
18.1
10.1
6.47
17.4
9.87
6.93
16.7
9.64
7.43
16.0
9.39
7.95
15.3
9.14
8.50
20
18.3
12.9
5.51
17.6
12.6
5.90
17.0
12.4
6.32
16.4
12.2
6.77
15.7
11.9
7.26
15.1
11.7
7.77
14.3
11.4
8.32
18
17.3
15.0
5.39
16.7
14.7
5.78
16.2
14.4
6.19
15.6
14.0
6.65
15.0
13.6
7.14
14.4
13.2
7.66
13.8
12.8
8.21
16
16.6
16.4
5.31
16.1
16.0
5.70
15.6
15.6
6.12
15.1
15.1
6.58
14.6
14.6
7.08
14.1
14.1
7.60
13.5
13.5
8.16
14
16.6
16.5
5.31
16.1
16.1
5.70
15.6
15.6
6.12
15.1
15.1
6.58
14.6
14.6
7.08
14.1
14.1
7.60
13.5
13.5
8.16
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
060
1.00
1.00
FG3ASA
060
0.99
1.00
FB4ASB
070
1.02
1.02
—
—
—
Содержание 38YCB