10
Detailed cooling capacities* (English) continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 25 ft of tubing. If other than 25 ft of
tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80
°
F entering air at the indoor coil. For sensible capacities at other than 80
°
F, deduct 835 Btuh per 1000
CFM of indoor coil air for each degree below 80
°
F, or add 835 Btuh per 1000 CFM of indoor coil air per degree above 80
°
F.
** System kw is total of indoor and outdoor unit kilowatts.
EWB — Entering Wet Bulb
COIL
AIR
CONDENSER ENTERING AIR TEMPERATURES
°
F
75
85
95
105
115
125
CFM
(F)
EWB
Capacity
MBtuh†
Sys.
Power
Kw**
Capacity
MBtuh†
Sys.
Power
Kw**
Capacity
MBtuh†
Sys.
Power
Kw**
Capacity
MBtuh†
Sys.
Power
Kw**
Capacity
MBtuh†
Sys.
Power
Kw**
Capacity
MBtuh†
Sys.
Power
Kw**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
38YCB048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
1400
72
54.5
27.0
4.24
52.3
26.2
4.62
49.9
25.3
5.04
47.5
24.4
5.48
44.9
23.5
5.96
42.4
22.7
6.48
67
50.1
34.3
4.12
48.0
33.4
4.49
45.8
32.5
4.88
43.6
31.6
5.31
41.2
30.7
5.78
38.8
29.8
6.27
62
46.0
41.3
4.00
44.1
40.4
4.36
42.1
39.4
4.75
40.1
38.4
5.17
38.0
37.3
5.61
35.7
35.7
6.08
57
44.4
44.4
3.96
42.8
42.8
4.32
41.2
41.2
4.71
39.5
39.5
5.15
37.8
37.8
5.60
35.8
35.8
6.08
1600
72
55.4
28.2
4.34
53.1
27.4
4.72
50.6
26.5
5.13
48.1
25.6
5.58
45.4
24.7
6.06
42.8
23.8
6.58
67
51.0
36.3
4.21
48.8
35.5
4.58
46.5
34.6
4.98
44.1
33.7
5.41
41.7
32.7
5.88
39.3
31.8
6.37
62
46.9
44.1
4.10
45.0
43.1
4.46
43.0
42.0
4.85
41.0
40.7
5.27
39.0
39.0
5.74
37.0
37.0
6.23
57
46.0
46.0
4.07
44.4
44.4
4.44
42.6
42.6
4.84
40.9
40.9
5.27
39.0
39.0
5.74
37.0
37.0
6.23
1800
72
56.1
29.4
4.43
53.7
28.5
4.81
51.2
27.6
5.22
48.6
26.8
5.67
45.9
25.8
6.15
43.1
24.9
6.67
67
51.6
38.4
4.30
49.4
37.5
4.67
47.1
36.6
5.07
44.6
35.6
5.50
42.1
34.7
5.97
39.7
33.7
6.47
62
47.8
46.6
4.19
45.8
45.4
4.55
43.9
43.9
4.95
41.9
41.9
5.39
40.0
40.0
5.86
38.0
38.0
6.37
57
47.4
47.4
4.18
45.7
45.7
4.55
43.8
43.8
4.95
42.0
42.0
5.39
40.0
40.0
5.86
38.0
38.0
6.37
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
048
1.00
1.00
FG3ASA
048
0.98
1.00
060
1.03
1.01
060
1.00
1.01
38YCB060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
1750
72
67.5
33.7
5.11
64.7
32.7
5.61
61.8
31.6
6.18
58.6
30.5
6.81
55.5
29.4
7.51
52.0
28.2
8.27
67
61.9
43.0
4.91
59.3
41.9
5.41
56.5
40.8
5.97
53.7
39.7
6.59
50.8
38.6
7.27
47.6
37.3
8.02
62
56.8
52.0
4.74
54.5
50.9
5.24
52.0
49.6
5.79
49.5
48.3
6.41
47.0
46.8
7.09
44.4
44.4
7.84
57
55.2
55.2
4.69
53.3
53.3
5.20
51.3
51.3
5.76
49.1
49.1
6.39
46.9
46.9
7.09
44.4
44.4
7.84
1900
72
68.1
34.6
5.19
65.2
33.6
5.70
62.1
32.5
6.26
59.0
31.4
6.89
55.8
30.3
7.59
52.3
29.1
8.36
67
62.5
44.6
4.99
59.8
43.5
5.49
57.0
42.4
6.05
54.1
41.3
6.67
51.2
40.1
7.36
47.9
38.9
8.11
62
57.6
54.2
4.83
55.2
53.0
5.32
52.8
51.7
5.88
50.2
50.1
6.50
47.9
47.9
7.19
45.2
45.2
7.96
57
56.4
56.4
4.79
54.5
54.5
5.30
52.3
52.3
5.87
50.1
50.1
6.50
47.8
47.8
7.20
45.3
45.3
7.96
2000
72
68.6
35.2
5.24
65.6
34.2
5.75
62.6
33.1
6.32
59.3
32.0
6.95
56.0
30.9
7.65
52.5
29.7
8.41
67
62.8
45.7
5.04
60.1
44.6
5.54
57.3
43.5
6.10
54.4
42.4
6.72
51.3
41.1
7.41
48.0
39.9
8.16
62
58.0
55.6
4.88
55.6
54.3
5.38
53.1
52.8
5.93
50.8
50.8
6.56
48.4
48.4
7.26
45.7
45.7
8.03
57
57.2
57.2
4.86
55.1
55.1
5.36
53.0
53.0
5.93
50.7
50.7
6.57
48.4
48.4
7.26
45.7
45.7
8.03
2150
72
69.0
36.1
5.32
66.0
35.1
5.83
62.9
34.0
6.39
59.6
32.9
7.03
56.2
31.8
7.73
52.7
30.6
8.49
67
63.3
47.2
5.12
60.5
46.1
5.62
57.7
45.0
6.18
54.7
43.9
6.80
51.6
42.7
7.49
48.3
41.4
8.24
62
58.7
57.5
4.96
56.2
55.9
5.46
53.9
53.9
6.03
51.6
51.6
6.66
49.1
49.1
7.36
46.5
46.5
8.13
57
58.2
58.2
4.95
56.1
56.1
5.46
53.9
53.9
6.03
51.5
51.5
6.66
49.1
49.1
7.36
46.5
46.5
8.13
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
060
1.00
1.00
FG3ASA
060
0.99
1.00
FB4ASB
070
1.02
1.02
—
—
—
Содержание 38YCB
Страница 19: ...19...