Heat pump heating performance (English)
See notes on pg. 14.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°
F
–3
7
17
27
37
47
57
67
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
(F)
EDB
CFM
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
38YCB024-70 Outdoor Section With F(A,B)4ASF024 Indoor Section
65
700
9.25
8.51
1.32
11.6
10.7
1.49
14.1
12.9
1.68
16.7
14.9
1.87
19.7
18.0
2.09
23.0
23.0
2.34
26.8
26.8
2.64
31.0
31.0
2.99
800
9.45
8.69
1.34
11.8
10.9
1.51
14.4
13.1
1.70
17.0
15.1
1.89
20.1
18.3
2.10
23.5
23.5
2.35
27.3
27.3
2.64
31.6
31.6
2.99
900
9.62
8.85
1.37
12.0
11.0
1.54
14.6
13.3
1.72
17.3
15.4
1.91
20.4
18.5
2.12
23.8
23.8
2.36
27.7
27.7
2.65
32.1
32.1
2.99
70
700
8.87
8.16
1.33
11.2
10.3
1.51
13.8
12.5
1.70
16.4
14.5
1.91
19.3
17.6
2.13
22.6
22.6
2.39
26.3
26.3
2.69
30.4
30.4
3.05
800
9.07
8.35
1.35
11.5
10.5
1.53
14.0
12.8
1.72
16.7
14.8
1.92
19.6
17.9
2.14
23.0
23.0
2.40
26.8
26.8
2.70
31.0
31.0
3.05
900
9.25
8.51
1.38
11.6
10.7
1.56
14.2
13.0
1.75
16.9
15.0
1.94
19.9
18.1
2.16
23.3
23.3
2.41
27.2
27.2
2.70
31.5
31.5
3.05
75
700
8.45
7.77
1.34
10.9
9.99
1.52
13.4
12.2
1.73
16.0
14.2
1.94
18.9
17.2
2.17
22.1
22.1
2.44
25.8
25.8
2.75
29.8
29.8
3.11
800
8.66
7.96
1.36
11.1
10.2
1.55
13.6
12.4
1.75
16.3
14.4
1.96
19.2
17.5
2.19
22.5
22.5
2.44
26.3
26.3
2.75
30.4
30.4
3.10
900
8.84
8.14
1.39
11.3
10.4
1.57
13.8
12.6
1.77
16.5
14.6
1.98
19.5
17.7
2.20
22.8
22.8
2.46
26.6
26.6
2.76
30.8
30.8
3.11
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4ASF
024
1.00
1.00
FG3ASA
024
0.99
1.05
030
1.00
0.99
—
—
—
38YCB036-70, 90 Outdoor Section With F(A,B)4AS(F,B)036 Indoor Section
65
1050
14.7
13.6
2.15
18.5
17.0
2.35
22.3
20.4
2.57
26.3
23.4
2.79
31.0
28.2
3.03
36.2
36.2
3.31
42.0
42.0
3.64
48.4
48.4
4.03
1200
15.1
13.9
2.19
18.8
17.3
2.40
22.7
20.7
2.61
26.8
23.8
2.82
31.6
28.7
3.06
36.8
36.8
3.32
42.8
42.8
3.64
49.3
49.3
4.02
1350
15.4
14.2
2.24
19.1
17.6
2.44
23.1
21.1
2.65
27.2
24.2
2.85
32.0
29.1
3.08
37.3
37.3
3.34
43.4
43.4
3.66
50.0
50.0
4.03
70
1050
14.0
12.9
2.16
17.9
16.4
2.38
21.7
19.8
2.61
25.7
22.8
2.84
30.3
27.6
3.10
35.3
35.3
3.38
41.0
41.0
3.72
47.3
47.3
4.11
1200
14.4
13.2
2.21
18.2
16.7
2.43
22.1
20.2
2.65
26.2
23.2
2.87
30.8
28.1
3.12
36.0
36.0
3.40
41.8
41.8
3.72
48.3
48.3
4.11
1350
14.7
13.5
2.27
18.5
17.0
2.48
22.5
20.5
2.69
26.6
23.6
2.91
31.3
28.5
3.15
36.5
36.5
3.42
42.5
42.5
3.74
49.0
49.0
4.12
75
1050
13.3
12.2
2.18
17.2
15.8
2.41
21.1
19.3
2.65
25.1
22.3
2.89
29.6
26.9
3.16
34.5
34.5
3.45
40.1
40.1
3.79
46.3
46.3
4.19
1200
13.7
12.6
2.23
17.6
16.2
2.45
21.5
19.6
2.69
25.6
22.7
2.92
30.1
27.4
3.18
35.2
35.2
3.47
40.9
40.9
3.80
47.2
47.2
4.19
1350
14.0
12.8
2.28
17.9
16.5
2.50
21.9
20.0
2.73
25.9
23.0
2.96
30.6
27.8
3.21
35.7
35.7
3.49
41.5
41.5
3.81
47.9
47.9
4.20
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4ASF
036
1.00
1.00
FG3ASA
036
0.99
1.01
F(A,B)4AS(F,B)