![Carrier 38YCB Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/carrier/38ycb/38ycb_product-data_2563189012.webp)
12
Heat pump heating performance (S.I.) continued
* The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these
values to obtain total system kilowatts.
† The kw heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The kw heating from supple-
ment heaters should be added to those values to obtain total system capacity.
EDB — Entering Dry Bulb
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°
C
–16
–8
0
4
8
12
16
20
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
Capacity
Kw
Total
Power
(C)
EDB
L/ S
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
Total Integ† Kw*
38YCB048-70, 90, 92 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section
12
650
6.41
5.89
3.05
8.38
7.63
3.25
10.9
9.79
3.48
12.3
11.5
3.61
13.9
13.8
3.75
15.8
15.8
3.92
17.8
17.8
4.12
20.1
20.1
4.34
750
6.48
5.96
3.08
8.49
7.72
3.27
11.0
9.92
3.49
12.4
11.6
3.60
13.9
13.9
3.72
15.9
15.9
3.89
18.1
18.1
4.08
20.4
20.4
4.30
850
6.56
6.03
3.13
8.58
7.81
3.31
11.1
9.99
3.50
12.5
11.7
3.61
14.2
14.2
3.74
16.1
16.1
3.88
18.2
18.2
4.05
20.4
20.4
4.25
15
650
6.35
5.84
3.19
8.33
7.58
3.40
10.8
9.71
3.64
12.2
11.4
3.78
13.8
13.7
3.93
15.6
15.6
4.11
17.7
17.7
4.32
19.9
19.9
4.55
750
6.43
5.91
3.23
8.42
7.67
3.42
10.9
9.82
3.64
12.3
11.5
3.77
13.8
13.8
3.89
15.8
15.8
4.07
17.9
17.9
4.27
20.1
20.1
4.49
850
6.50
5.98
3.27
8.52
7.75
3.45
11.0
9.90
3.66
12.4
11.6
3.77
14.1
14.0
3.91
15.9
15.9
4.06
18.0
18.0
4.24
20.2
20.2
4.45
18
650
6.29
5.79
3.34
8.27
7.52
3.55
10.7
9.62
3.80
12.1
11.3
3.95
13.6
13.6
4.10
15.5
15.5
4.30
17.5
17.5
4.52
19.7
19.7
4.76
750
6.37
5.86
3.37
8.36
7.61
3.57
10.8
9.72
3.80
12.2
11.4
3.93
13.7
13.7
4.07
15.6
15.6
4.25
17.7
17.7
4.46
19.9
19.9
4.69
850
6.44
5.92
3.41
8.45
7.69
3.60
10.9
9.81
3.81
12.3
11.5
3.94
13.9
13.8
4.07
15.8
15.8
4.24
17.8
17.8
4.43
20.0
20.0
4.65
21
650
6.24
5.73
3.48
8.21
7.47
3.70
10.6
9.54
3.96
12.0
11.2
4.11
13.5
13.4
4.28
15.3
15.3
4.48
17.3
17.3
4.72
19.4
19.4
4.96
750
6.31
5.80
3.51
8.30
7.55
3.71
10.7
9.63
3.96
12.1
11.3
4.09
13.6
13.6
4.25
15.5
15.5
4.44
17.5
17.5
4.65
19.6
19.6
4.88
850
6.39
5.87
3.54
8.39
7.63
3.74
10.8
9.72
3.97
12.2
11.4
4.10
13.7
13.7
4.24
15.6
15.6
4.42
17.7
17.7
4.62
19.8
19.8
4.84
24
650
6.20
5.70
3.64
8.18
7.44
3.86
10.5
9.46
4.13
11.9
11.1
4.29
13.4
13.3
4.46
15.1
15.1
4.67
17.1
17.1
4.91
19.2
19.2
5.18
750
6.27
5.76
3.66
8.25
7.51
3.87
10.6
9.55
4.12
12.0
11.2
4.27
13.5
13.4
4.43
15.3
15.3
4.63
17.3
17.3
4.85
19.4
19.4
5.09
850
6.34
5.83
3.70
8.31
7.57
3.89
10.7
9.63
4.13
12.1
11.3
4.27
13.6
13.6
4.42
15.5
15.5
4.61
17.5
17.5
4.82
19.6
19.6
5.05
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
048
1.00
1.00
FG3ASA
048
1.00
1.03
060
0.99
0.96
060
1.00
1.02
38YCB060-90, 92 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section
12
850
9.46
8.70
3.51
11.7
10.6
3.72
14.3
12.8
4.00
15.7
14.7
4.17
17.4
17.3
4.37
19.4
19.4
4.65
21.6
21.6
4.98
24.0
24.0
5.34
900
9.50
8.73
3.53
11.7
10.7
3.73
14.3
12.9
4.00
15.8
14.7
4.17
17.4
17.3
4.36
19.4
19.4
4.64
21.8
21.8
4.97
24.3
24.3
5.33
950
9.54
8.77
3.55
11.7
10.7
3.74
14.4
12.9
4.01
15.9
14.8
4.18
17.5
17.4
4.37
19.5
19.5
4.64
21.7
21.7
4.96
24.0
24.0
5.32
1000
9.59
8.81
3.57
11.8
10.7
3.76
14.4
13.0
4.02
15.9
14.9
4.19
17.6
17.5
4.38
19.6
19.6
4.65
21.7
21.7
4.97
24.0
24.0
5.32
15
850
9.42
8.66
3.73
11.6
10.6
3.96
14.2
12.8
4.25
15.7
14.6
4.43
17.3
17.2
4.64
19.2
19.2
4.93
21.4
21.4
5.26
23.7
23.7
5.63
900
9.46
8.70
3.75
11.7
10.6
3.97
14.3
12.8
4.25
15.7
14.7
4.43
17.3
17.3
4.63
19.3
19.3
4.91
21.5
21.5
5.24
23.9
23.9
5.61
950
9.51
8.74
3.77
11.7
10.6
3.98
14.3
12.9
4.26
15.8
14.7
4.43
17.4
17.3
4.64
19.4
19.4
4.91
21.5
21.5
5.23
23.7
23.7
5.60
1000
9.55
8.78
3.79
11.7
10.7
4.00
14.4
12.9
4.27
15.9
14.8
4.44
17.5
17.4
4.64
19.4
19.4
4.91
21.6
21.6
5.23
23.8
23.8
5.60
18
850
9.38
8.63
3.95
11.6
10.5
4.20
14.1
12.7
4.51
15.6
14.5
4.69
17.2
17.1
4.91
19.1
19.1
5.20
21.2
21.2
5.54
23.4
23.4
5.91
900
9.43
8.67
3.97
11.6
10.6
4.20
14.2
12.8
4.50
15.6
14.6
4.69
17.3
17.2
4.90
19.2
19.2
5.18
21.3
21.3
5.52
23.6
23.6
5.89
950
9.47
8.70
3.99
11.6
10.6
4.21
14.2
12.8
4.51
15.7
14.6
4.69
17.3
17.2
4.90
19.2
19.2
5.18
21.3
21.3
5.51
23.5
23.5
5.88
1000
9.51
8.74
4.01
11.7
10.6
4.23
14.3
12.9
4.52
15.8
14.7
4.69
17.4
17.3
4.90
19.3
19.3
5.18
21.4
21.4
5.50
23.6
23.6
5.87
21
850
9.34
8.59
4.17
11.5
10.5
4.44
14.1
12.7
4.76
15.5
14.4
4.96
17.1
17.0
5.19
18.9
18.9
5.48
21.0
21.0
5.82
23.1
23.1
6.20
900
9.39
8.63
4.19
11.6
10.5
4.44
14.1
12.7
4.76
15.6
14.5
4.95
17.2
17.1
5.17
19.0
19.0
5.46
21.0
21.0
5.79
23.2
23.2
6.17
950
9.43
8.67
4.21
11.6
10.6
4.45
14.2
12.8
4.76
15.6
14.6
4.94
17.2
17.2
5.16
19.1
19.1
5.45
21.1
21.1
5.78
23.3
23.3
6.15
1000
9.47
8.71
4.23
11.6
10.6
4.46
14.2
12.8
4.77
15.7
14.6
4.95
17.3
17.2
5.16
19.2
19.2
5.44
21.2
21.2
5.77
23.4
23.4
6.14
24
850
9.29
8.54
4.40
11.5
10.5
4.69
14.0
12.6
5.03
15.4
14.4
5.23
16.9
16.9
5.46
18.8
18.8
5.77
20.8
20.8
6.12
22.9
22.9
6.52
900
9.34
8.59
4.42
11.5
10.5
4.69
14.1
12.6
5.02
15.5
14.4
5.21
17.0
16.9
5.44
18.9
18.9
5.74
20.9
20.9
6.09
23.0
23.0
6.48
950
9.38
8.62
4.43
11.6
10.5
4.70
14.1
12.7
5.02
15.5
14.5
5.21
17.1
17.0
5.43
18.9
18.9
5.72
21.0
21.0
6.07
23.1
23.1
6.45
1000
9.43
8.67
4.45
11.6
10.6
4.71
14.2
12.7
5.02
15.6
14.5
5.21
17.1
17.1
5.43
19.0
19.0
5.72
21.0
21.0
6.06
23.2
23.2
6.44
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4AS(F,B)
060
1.00
1.00
FG3ASA
060
0.99
1.03
FB4ASB
070
0.99
0.95
—
—
—
Содержание 38YCB