36
DIAGNOSIS AND SOLUTION (CONT)
IPM malfunction or IGBT over−strong current protection diagnosis and solution (P0)
Error Code
P0
Malfunction decision conditions
When the voltage signal, that the IPM sends to the compressor drive chip is abnormal, the display
LED displays P0
”
and the air conditioner turns off.
Supposed causes
S
Wiring mistake
S
IPM malfunction
S
Outdoor fan assembly faulty
S
Compressor malfunction
S
Outdoor PCB faulty
Troubleshooting
Check the wiring between main the
PCB and the compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM
No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of
Ǐ
Fan
Speed Has Been Out Of Control
ǐ
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
Содержание 38MHRB series
Страница 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 3 Size 24K...
Страница 11: ...11 WIRING DIAGRAMS COOLING ONLY Fig 7 Wiring Diagram Size Cooling Only Size 12K 115V...
Страница 12: ...12 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 8 Wiring Diagram Cooling Only Size 12K 230V...
Страница 13: ...13 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 9 Wiring Diagram Cooling Only Sizes 18 24K...
Страница 14: ...14 WIRING DIAGRAMS HEAT PUMP Fig 10 Wiring Diagram Heat Pump Size 12K 115V...
Страница 15: ...15 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 11 Wiring Diagram Heat Pump Sizes 09 12 18 230V...
Страница 16: ...16 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 12 Wiring Diagram Heat Pump Size 24 230V...
Страница 37: ...37 DIAGNOSIS AND SOLUTION CONT Fig 36 P U Fig 37 P V...
Страница 38: ...38 DIAGNOSIS AND SOLUTION CONT Fig 38 P W Fig 39 N U...
Страница 39: ...39 DIAGNOSIS AND SOLUTION CONT Fig 40 N V Fig 41 N W...
Страница 50: ...50 DISASSEMBLY INSTRUCTIONS SIZES 12K 115V CONT 5 4 Remove the fan motor screws 4 then remove the motor...