18
REFRIGERANT LINES
General Refrigerant Line Sizing
1 The outdoor units are shipped with a full charge of R410A
refrigerant. All charges, line sizing, and capacities are based
on runs of 25ft. (7.6 m). For runs over 25 ft. (7.6 m),
consult the long−line applications section for the proper
charge adjustments.
2 The minimum refrigerant line length between the indoor
and outdoor units is 10 ft. (3 m).
3 Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36 in (914 mm)
should be buried. Provide a minimum 6in (152 mm)
vertical rise to the service valves to prevent refrigerant
migration.
4 Both lines must be insulated. Use a minimum of 1/2in.
(12.7 mm) thick insulation. Closed−cell insulation is
recommended in all long−line applications.
5 Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate
the the tubing so vibration or noise is not transmitted into
the structure.
IMPORTANT:
Both refrigerant lines must be insulated
separately.
Table 12 lists the maximum lengths allowed.
Table 12—Piping and Refrigerant Information
System Size
12K (115V)
9K (208-230V)
12K (208-230V)
18K (208-230V)
24K (208-230V)
Piping
Min. Piping Length
ft. (m)
10(3)
10(3)
10(3)
10(3)
10(3)
Standard Piping Length
ft. (m)
25(7.5)
25(7.5)
25(7.5)
25(7.5)
25(7.5)
Max. outdoor-indoor
height difference
(OU higher than IU)
ft. (m)
33(10)
33(10)
33(10)
66(20)
66(20)
Max. outdoor-indoor
height difference
(IU higher than OU)
ft. (m)
33(10)
33(10)
33(10)
66(20)
66(20)
Max. Piping Length with
no additional refrigerant
charge per System
(Standard Piping length)
ft. (m)
25(7.5)
25(7.5)
25(7.5)
25(7.5)
25(7.5)
Total Max. Piping
Length per system
ft. (m)
82(25)
82(25)
82(25)
98(30)
164(50)
Additional refrigerant
charge (between Standard
– Max piping length)
Oz/ft (g/m)
0.161(15)
0.161(15)
0.161(15)
0.161(15)
0.322(30)
Suction Pipe
(size - connection type)
In (mm)
1/2(12.7)
3/8(9.52)
1/2(12.7)
1/2(12.7)
5/8(15.9)
Liquid Pipe
(size - connection type)
In (mm)
1/4(6.35)
1/4(6.35)
1/4(6.35)
1/4(6.35)
3/8(
9.52
)
Refrigerant Type
Type
R410A
R410A
R410A
R410A
R410A
Refrigerant
Cooling Only Models
Charge Amount
Lbs (kg)
1.30(0.59)
N/A
1.17 (0.53)
1.98 (0.9)
2.56 (1.16)
Heat Pump Models
Charge Amount
Lbs (kg)
2.12(0.96)
1.76(0.8)
2.12(0.96)
2.82 (1.28)
3.97 (1.8)
Long Line Applications,:
1 No change in line sizing is required.
2 Add refrigerant per Table 12.
Содержание 38MHRB series
Страница 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 3 Size 24K...
Страница 11: ...11 WIRING DIAGRAMS COOLING ONLY Fig 7 Wiring Diagram Size Cooling Only Size 12K 115V...
Страница 12: ...12 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 8 Wiring Diagram Cooling Only Size 12K 230V...
Страница 13: ...13 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 9 Wiring Diagram Cooling Only Sizes 18 24K...
Страница 14: ...14 WIRING DIAGRAMS HEAT PUMP Fig 10 Wiring Diagram Heat Pump Size 12K 115V...
Страница 15: ...15 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 11 Wiring Diagram Heat Pump Sizes 09 12 18 230V...
Страница 16: ...16 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 12 Wiring Diagram Heat Pump Size 24 230V...
Страница 37: ...37 DIAGNOSIS AND SOLUTION CONT Fig 36 P U Fig 37 P V...
Страница 38: ...38 DIAGNOSIS AND SOLUTION CONT Fig 38 P W Fig 39 N U...
Страница 39: ...39 DIAGNOSIS AND SOLUTION CONT Fig 40 N V Fig 41 N W...
Страница 50: ...50 DISASSEMBLY INSTRUCTIONS SIZES 12K 115V CONT 5 4 Remove the fan motor screws 4 then remove the motor...