26
PCB DIAGRAMS (CONT)
Fig. 29 – Sizes 18−24 208−230V
NOTE: After power on, LED3(Green color) and LED2(Red color) will flash if the unit has some problems.
Table 17—LED Codes
No.
Problems
LED3
(Green)
LED2
(Red)
IU display
1
standby for normal
O
X
2
Operation normally
X
O
3
IPM malfunction or IGBT over-strong current protection
☆
X
P0
4
Over voltage or too low voltage protection
O
O
P1
5
EEPROM parameter error
O
☆
E5
6
Inverter compressor drive error
X
☆
P4
7
Inverter compressor drive error
☆
O
P4
8
Inverter compressor drive error
☆
☆
P4
O(light) X(off)
☆
(2.5Hz flash)
Содержание 38MHRB series
Страница 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 3 Size 24K...
Страница 11: ...11 WIRING DIAGRAMS COOLING ONLY Fig 7 Wiring Diagram Size Cooling Only Size 12K 115V...
Страница 12: ...12 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 8 Wiring Diagram Cooling Only Size 12K 230V...
Страница 13: ...13 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 9 Wiring Diagram Cooling Only Sizes 18 24K...
Страница 14: ...14 WIRING DIAGRAMS HEAT PUMP Fig 10 Wiring Diagram Heat Pump Size 12K 115V...
Страница 15: ...15 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 11 Wiring Diagram Heat Pump Sizes 09 12 18 230V...
Страница 16: ...16 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 12 Wiring Diagram Heat Pump Size 24 230V...
Страница 37: ...37 DIAGNOSIS AND SOLUTION CONT Fig 36 P U Fig 37 P V...
Страница 38: ...38 DIAGNOSIS AND SOLUTION CONT Fig 38 P W Fig 39 N U...
Страница 39: ...39 DIAGNOSIS AND SOLUTION CONT Fig 40 N V Fig 41 N W...
Страница 50: ...50 DISASSEMBLY INSTRUCTIONS SIZES 12K 115V CONT 5 4 Remove the fan motor screws 4 then remove the motor...