background image

Remove indoor coil piston if unit is to be installed on system
with a TXV metering device.

IMPORTANT:

The TXV should be mounted as close to the

indoor coil as possible and in a vertical, upright position. Avoid
mounting the inlet tube vertically down. Valve is more susceptible
to malfunction due to debris if inlet tube is facing down. A factory
approved filter-drier must be installed in the liquid line.

INSTALLING TXV IN PLACE OF PISTON

1. Pump system down to 2 psig and recover refrigerant.

2. Remove hex nut from piston body. Use backup wrench on fan

coils.

3. Remove and discard factory-installed piston. Be sure Teflon

seal is in place.

4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.

NOTE:

If the piston is not removed from the body, TXV will not

function properly.

To prevent damage to the unit, use a brazing shield and wrap
TXV with wet cloth or use heat sink material.

5. Install TXV on indoor coil liquid line. Sweat swivel adapter to

inlet of indoor coil and attach to TXV outlet. Use backup
wrench to avoid damage to tubing or valve. Sweat inlet of
TXV, marked “IN” to liquid line. Avoid excessive heat which
could damage valve.

6. Install vapor elbow with equalizer adapter to suction tube of

line set and suction connection to indoor coil. Adapter has a
1/4–in. male connector for attaching equalizer tube.

7. Connect equalizer tube of TXV to 1/4–in. equalizer fitting on

vapor line adapter.

8. Attach TXV bulb to horizontal section of suction line using

clamps provided. Insulate bulb with field-supplied insulation
tape. See Fig. 5 for correct positioning of sensing bulb.

9. Proceed with remainder of unit installation.

REPLACING TXV ON R-22 INDOOR COIL

1. Pump system down to 2 psig and recover refrigerant.

2. Remove coil access panel and fitting panel from front of

cabinet.

3. Remove TXV support clamp using a 5/16-in. nut driver. Save

the clamp.

4. Remove R-22 TXV using a backup wrench on flare connec-

tions to prevent damage to tubing.

5. Using wire cutters, cut equalizer tube off flush with vapor tube

inside cabinet.

6. Remove bulb from vapor tube inside cabinet.

7. Braze equalizer stub-tube closed. Use protective barrier as

necessary to prevent damage to drain pan.

IMPORTANT:

Route the equalizer tube of Puron® TXV through

suction line connection opening in fitting panel prior to replacing
fitting panel around tubing.

8. Install TXV with 3/8-in. copper tubing through small hole in

service panel. Use wrench and backup wrench, to avoid
damage to tubing or valve, to attach TXV to distributor.

9. Reinstall TXV support clamp (removed in item 3).

10. Attach TXV bulb to vapor tube inside cabinet, in same

location as original was when removed, using supplied bulb
clamps (nylon or copper). See Fig. 5 for correct positioning of
sensing bulb.

11. Route equalizer tube through suction connection opening

(large hole) in fitting panel and install fitting panel in place.

12. Sweat inlet of TXV, marked IN, to liquid line. Avoid

excessive heat which could damage valve.

13. Install vapor elbow with equalizer adapter to vapor line of line

set and vapor connection to indoor coil. Adapter has a 1/4–in
. male connector for attaching equalizer tube.

14. Connect equalizer tube of TXV to 1/4–in. equalizer fitting on

vapor line adapter. Use backup wrench to prevent damage to
equalizer fitting.

15. Proceed with remainder of unit installation.

Remove indoor coil piston if unit is to be installed on system
with a TXV metering device.

Step 7—Making Piping Connections

Relieve pressure and recover all refrigerant before system
repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices,
including solenoid valves.

Do not leave system open to atmosphere any longer than
minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep
ends of tubing sealed during installation.

Fig. 4—AccuRater® Components (38EZA Use)

A01164

PISTON

TEFLON SEAL

PISTON RETAINER

13

16

–IN.

BRASS HEX
NUT

3

4

–IN. BRASS

HEX BODY

STRAINER

DISTRIBUTOR

COPPER TUBE

PISTON
RING

3

Содержание 38ESA

Страница 1: ...erate at higher pressures than standard R 22 systems Do not use R 22 service equipment or com ponents on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube...

Страница 2: ...must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit Step 4 Operating Ambients The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F Step 5 Check Indoor AccuRater Piston and Install Piston Ring 38EZA Standard If unit is to be installed wi...

Страница 3: ...revent damage to tubing 5 Using wire cutters cut equalizer tube off flush with vapor tube inside cabinet 6 Remove bulb from vapor tube inside cabinet 7 Braze equalizer stub tube closed Use protective barrier as necessary to prevent damage to drain pan IMPORTANT Route the equalizer tube of Puron TXV through suction line connection opening in fitting panel prior to replacing fitting panel around tub...

Страница 4: ...ubing and indoor coil are now ready for leak testing This check should include all field and factory joints EVACUATE REFRIGERANT TUBING AND INDOOR COIL Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used if the procedure outlined below is fol...

Страница 5: ...be Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 3 4 7 8 042 048 3 8 3 8 7 8 7 8 7 8 1 1 8 060 3 8 3 8 7 8 1 1 8 7 8 1 1 8 NOTES 1 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 50 ft horizontal or greater than 20 ft vertical differential consult the Application Guideline and Service ...

Страница 6: ...l Electrical Accessories Refer to the individual instructions packaged with kits or acces sories when installing Step 11 Start Up To prevent compressor damage or personal injury observe the following Do not overcharge system with refrigerant Do not operate unit in a vacuum or at negative pressure Do not vent refrigerant to atmosphere Recover during system repair or final unit disposal Do not disab...

Страница 7: ...y relay circuit the indoor blower runs an additional 90 sec to increase system efficiency Step 12 Check Charge UNIT CHARGE Factory charge and charging method are shown on unit informa tion plate Charge Puron units using a commercial type metering device in manifold hose Charge refrigerant into suction line NOTE If superheat or subcooling charging conditions are not favorable charge must be weighed...

Страница 8: ...on note superheat 7 Refer to Table 6 Find superheat temperature located in item 6 and suction pressure At this intersection note suction line temperature 8 If a unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is reached 9 If unit has a lower suction line temperature than charted temperature reclaim refrigerant until charted temperature ...

Страница 9: ...3 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85...

Страница 10: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER SEE NOTE 2 G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97594 24 VAC HOT R G W W1 Y Y2 O W2 R W2 C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER G Y1 W...

Страница 11: ...AN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NOT USED 24 VAC COM NOT USED NOT USED NOT USED OPTIONAL OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 WIRING DIAGRAM NOTES 1 CARRIER THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS TSTAT _______ 2 WIRING MUST CONFORM TO NEC OR LOCAL CODES 3 SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH E...

Страница 12: ...riers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere Poe oils may cause damage to certain plastics and roofing materials Wrap all filter driers and service valves with wet cloth when brazing A factory approved liquid line filter drier is required on every unit Do not use an R...

Отзывы: