background image

Service 

 

 

 

 
 

 

 

 

 
 

 

 

 

 
 

 

 

Outdoor Fan— A reinforced wire mount holds the outdoor fan assembly in place. 

 
Compressor Pressure Relief Valve — Valve is located in compressor.  Relief valve opens at a pressure differential of 

approximately 600 ± 50 psig between suction (low side) and discharge (high side) to allow pressure equalization. 

 

Internal Current and Temperature Sensitive Overload — Control resets automatically when internal compressor 

motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal 
overload is suspected of being open, check by using an ohmmeter or continuity tester. If necessary, refer to Carrier 

Standard Systems Techniques Manual, Chapter 2, for complete information. 

Pump down Procedure — Service valves provide a convenient shut-off valve useful for certain refrigeration system 

repairs. System may be pumped down to make repairs on low side without losing complete refrigerant charge. 

1. Attach pressure gage to suction service valve gage port. 
2. Front seat the liquid line valve. 

3. Start unit in cooling mode. Run until low-pressure switch opens at 54 psig (472Kpa). Do not allow compressor     

to pump to a vacuum. 

4. Shut unit off and front seat suction valve. 

5. Depressurize low side of unit and recover refrigerant following accepted practice. 
 

Filter Drier – The filter drier is specifically designed to operate with R-410A, use only factory-authorized components. 

When removing a filter drier, use a tubing cutter to cut drier from system. 

Do not unsweat a filter drier 

from system. 

Heat from unsweating will release moisture and contaminants from drier into the system. 

 

 

 

Loss of Charge Pressure Switch — This switch, mounted on the suction line, has fixed non-adjustable settings. To 
check pressure switch, attach pressure gage to suction service valve gage port.  Slowly close liquid shutoff valve and 

allow compressor to pump down. Do not allow compressor to pump down below 2 psig.   Compressor   should   shut   

down   when suction pressure drops to cutout pressure in Physical Data Table, and should restart when pressure 

builds up to cut-in pressure shown in Physical Data Table. 

 
High Pressure Switch — This switch, mounted on the discharge line, has fixed non- adjustable   settings   &   auto   

reset. To check pressure switch, attach pressure gauge to compressor discharge service port, block condenser coil, 

monitor pressure till compressor trips, remove blockage and observe at which pressure compressor restarts. 

The 38C unit coils hold only the factory designated amount of refrigerant. Additional refrigerant may cause 
units to relieve pressure through compressor internal pressure relief valve (indicated by sudden rise of suction 
pressure) before suction pressure reaches 5 pisg. If this occurs, shut off immediately, then front seat the 
suction valve and remove and recover excess refrigerant following accepted practice. 

Caution 

Before performing service or maintenance, be sure the indoor unit main power switch is off and indoor blower 

has completely stopped. Failure to do so may result in electrical shock or injury from rotating fan blades. 

Warning 

Do not leave system open to atmosphere. Product damage could occur. Compressor oil is highly susceptible to 

moisture absorption. 

Caution 

The compressor used in this product is specifically designed to operate with R-410A refrigerant and cannot be 

interchanged. 

Caution 

Page 13

Содержание 38C Series

Страница 1: ...ries energy efficient split top discharge condensing units incorporate innovative technology to provide reliable summer cooling performance The units are pre wired pre charged with Puron R 410A refrig...

Страница 2: ...the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will re...

Страница 3: ...frigerant Charge kg 2 31 2 44 3 12 4 05 4 17 4 52 Connection Type Liquid Line Vapour Line Max Length ft Max Lift ft Outdoor Fan Motor Type Motor Voltage RPM CFM Diameter No Blades Motor Horsepower Con...

Страница 4: ...393 7 349 2 36 792 2 981 1 98 4 19 0 166 7 627 1 231 8 74 6 15 9 406 4 393 7 393 7 42 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74 6 15 9 406 4 393 7 323 8 48 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74...

Страница 5: ...07 4 115 8 929 4 115 5 5 6 5 38CKPS48DS40 42TPM048 11 415 3 50 Ducted 47 500 43 000 12 2 9 0 3 893 4 778 10 511 4 778 6 6 7 8 38CKPS60DS40 42TPM060 11 415 3 50 Ducted 60 000 51 000 11 8 8 3 5 085 6 14...

Страница 6: ...Typical Wiring Schematic 38CKP18 24 30 36 230V 240V 1PH 50Hz Ducted 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted Page 6...

Страница 7: ...Typical Wiring Schematic Continued 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted With Capacitor Bank Page 7...

Страница 8: ...nit operation sound may disturb customer 2 Insure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns...

Страница 9: ...rovisions are made for water drainage and noise vibration dampening Rigging Keep unit upright Lift unit using sling Use cardboard or padding under sling and spreader bars to prevent sling damage to un...

Страница 10: ...nnecessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure Also when passing refrigerant tubes through the wall...

Страница 11: ...uate above or below permissible limits When making electrical connections provide clearance at unit for refrigerant piping connections NOTE Use copper wires only between disconnect switch and unit NOT...

Страница 12: ...the Pre startup and Startup included with the fan coil units for correct start up procedures Be sure that field disconnect is closed Set room thermostat below ambient temperature Operate unit for 15 m...

Страница 13: ...nts from drier into the system Loss of Charge Pressure Switch This switch mounted on the suction line has fixed non adjustable settings To check pressure switch attach pressure gage to suction service...

Страница 14: ...den hose or other suitable equipment to flush coil from the outside to remove dirt Be sure to flush all dirt and debris from drain holes in the base of unit Fan motors are waterproof Leak Detection Ne...

Страница 15: ...4 liquid line What charge adjustment is required Formula 27 oz ft x 25ft 13 5 oz 6 75 oz 8 0 g m x 7 6 m 382 7 g 321 9 g Net result is to remove 6 75 oz of refrigerant from the system Example 2 System...

Страница 16: ...9 4 10 6 11 7 12 8 13 9 4 6 1 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 6 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 7 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 8 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 18...

Страница 17: ...262 86 9 364 110 0 466 128 7 596 148 4 60 8 6 162 57 0 264 87 4 366 110 4 468 129 0 600 149 0 62 10 0 164 57 7 266 87 9 368 110 8 470 129 3 604 149 5 64 11 3 166 58 4 268 88 4 370 111 2 472 129 7 608...

Страница 18: ...26 335 90 92 94 96 88 90 92 94 86 88 90 92 84 86 88 90 82 84 86 88 80 82 84 86 345 354 364 374 98 100 102 104 96 98 100 102 94 96 98 100 92 94 96 98 90 92 94 96 88 90 92 94 384 395 406 416 106 108 110...

Страница 19: ...filter driers in line longer than 72 hours Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certa...

Страница 20: ...OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSU...

Страница 21: ...control wires connected to the same circuit as associated refrigerant lines Check to make sure the subbase mounting to wall is secure Don t apply excessive force to mounting screw Are the refrigerant...

Страница 22: ...NOTES Page 22...

Страница 23: ...used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Страница 24: ...mode thus in some cases heat pumps have additional line set limitations from air conditioning units Table 3 in this guideline can be used to properly size suction lines Follow all suction line sizing...

Страница 25: ...tdoor units Equivalent length takes into account pressure losses from both tubing length and losses due to fittings and accessories such as elbows liquid line solenoid and filter drier Losses from fit...

Страница 26: ...nformation Use subcooling as the primary method for charging longline applications Outdoor units are pre charged for 15 ft 4 6 m of 3 8 liquid line When using different length diameter liquid lines ch...

Страница 27: ...le 6 Vapor line should slope towards indoor unit Maximum actual liquid line is up to 100 61 m See Table 5 Maximum total equivalent length is up to 120 76 2 m See Table 5 Heat pump only Bi flow liquid...

Страница 28: ...150 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 150 150 150 150 24000 AC Only 1 4 75 75 75 50 50 AC Only 5 16 150 150 150 150 150 150 150 125 100 AC HP 3 8 150 150 150 150 150 150 150 150 150 30...

Страница 29: ...9 15 2 51 75 15 5 22 9 76 100 23 2 30 5 101 125 30 8 38 1 18000 AC Only 1 4 150 150 150 150 150 AC Only 5 16 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 24000 AC Only 1 4 100 125 150 150 150 AC...

Страница 30: ...ss than 20 ft 6 1 m vertical separation Outdoor unit BELOW indoor unit See Tables 6 8 and 11 for longline thresholds An inverted vapor line trap must be installed at indoor unit The top peak of trap m...

Страница 31: ...Page 31...

Страница 32: ...ts to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version 38C 50Hz IOM 01 Catalog Number 38C 50 EN IOM 02 Effective Date...

Отзывы: