DX OUTDOOR AIR LOCKOUT — The DX Lockout con-
figuration will prevent operation of the DX cooling if the
outdoor-air temperature is below the configured value.
DX Outdoor
Units
F
Air Lockout:
Range
–40.0 to 65.0
Default Value
–40.0
LOCAL RH SENSOR — The Local RH Sensor configura-
tion defines if a local relative humidity sensor is installed.
Local RH Sensor: Range
No/Yes
Default Value
No
REHEAT — The reheat configuration defines if the zone con-
troller will allow simultaneous heating and cooling to maintain
space temperature during the dehumidification mode.
NOTE: The heating coil must be located downstream from the
cooling coil if reheat is desired.
Reheat:
Range
Disable/Enable
Default Value
Disable
LINKAGE THERMOSTAT — The Linkage Thermostat
start time biases allow the installer to configure the time per de-
gree the space should take to recover in the heat and cool
modes for optimum start with a Linkage Thermostat. These
numbers will be used to calculate the Start Bias time.
Cool Start Bias:
Units
minutes/degree
Range
0 to 60
Default Value
10
Heat Start Bias
Units
minutes/degree
Range
0 to 60
Default Value
10
Occupancy Maintenance Table —
The Occupancy
Maintenance Table is used to check the occupied schedule. In-
formation concerning the current occupied period is displayed.
See Fig. 42.
MODE — The Mode point displays the current occupied
mode for the fan coil. If the fan coil is following its own local
schedule this is the result of the local schedule status. If the fan
coil is configured to follow a global schedule, this point dis-
plays the mode last received from a global schedule broadcast.
The point will display a 0 for unoccupied and a 1 for occupied.
Mode:
Display Range
0 to 1
Default Value
0
Network Access None
CURRENT OCCUPIED PERIOD — If the fan coil is con-
figured to determine occupancy locally, the Current Occupied
Period point is used to display the current period determining
occupancy.
Current Occupied
Period:
Display Range
1 to 8
Default Value
0
Network Access None
OVERRIDE IN PROGRESS — The Override in Progress
point is used to display if an occupancy override is in progress.
The point will display a yes if an override is in progress, or a no
if there is no override.
Override In
Progress:
Display Range
Yes/No
Default Value
No
Network Access None
OVERRIDE DURATION — The Override Duration point
displays the number of minutes remaining for an occupancy
override which is in effect. If the number of override hours was
downloaded, the value will be converted to minutes.
Override Duration:Display Units
minutes
Display Range
0 to 240
Default Value
0
Network Access None
OCCUPIED START TIME — The Occupied Start Time
point shows the time that the current occupied mode began. If
the current mode is unoccupied or the fan coil is following a
global schedule, the value displayed by this point will remain at
default.
Occupied
Start Time:
Display Range
00:00 to 23:59
Default Value
0:00
Network Access None
UNOCCUPIED START TIME — The Unoccupied Start
Time point shows the time that the current occupied mode will
end. This will also be the beginning of the next unoccupied
mode. If the current mode is unoccupied or the fan coil is fol-
lowing a global schedule, the value displayed by this point will
remain at default.
Unoccupied
Start Time:
Display Range
00:00 to 24:00
Default Value
0:00
Network Access None
Fig. 42 — Occupancy Maintenance Table Screen