32
OCCUPANCY SCHEDULE — For flexibility of scheduling,
the occupancy programming is broken into eight separate peri-
ods. For each period the schedule contains the following fields:
Day of Week, Occupied From, and Occupied To.
DAY OF WEEK — The Day of Week configuration consists
of eight fields corresponding to the seven days of the week and
a holiday field in the following order: Monday, Tuesday,
Wednesday, Thursday, Friday, Saturday Sunday, Holiday.
It is displayed as:
M T W Th Fr Sa Su Hol
0
0
0
0
0
0
0 0
If a 1 is configured in the corresponding place for a certain
day of the week, the related “Occupied from” and “Occupied
to” times for that period will take effect on that day of the
week. If a 1 is placed in the holiday field, the related times will
take effect on a day configured as a holiday. A zero means the
schedule period will not apply to that day.
Day of week:
Range
0 or 1
Default Values
11111111 for period 1,
00000000 for the rest of the periods
OCCUPIED FROM — This field is used to configure the
hour and minute, in military time, that the mode for the fan coil
controller will switch to occupied.
Occupied From: Units
Hours:Minutes
Range
00:00 to 24:00
(Minutes 00 to 59)
Default Value
00:00
OCCUPIED TO — This field is used to configure the hour
and minute, in military time, that the mode for the fan coil con-
troller switches from occupied to unoccupied.
Occupied To:
Units
Hours:Minutes
Range
00:00 to 24:00
(Minutes 00 to 59)
Default Value
24:00
Runtime Configuration Screen —
The Runtime
Configuration screen is used to configure the Runtime system
function. See Fig. 38.
The Runtime system function determines how long the con-
figured discrete points have been on. Up to 16 points can be
configured in each Runtime table. Up to 4 tables can be config-
ured. Each point is read every minute and the amount of run-
time is recorded. This data is then used by a CCN Data Collec-
tion III option. Once an hour, the Data Collection supervisory
device transmits an inquiry to the Comfort Controller. The
Comfort Controller sends back the run-time value for each
configured point.
POINT n NAME — The Point n Name set point specifies the
discrete point being monitored. There are 16 points where n
represents the numbers 1 through 16.
Point n Name:
Units
ASCII
Range
8 characters (Bldg Spvr)
96 characters (LID 6400)
32 characters (LID 1600)
Default Value
SENSDI00
POINT n TYPE — The Point n Type set point specifies
whether the discrete point being monitored is a normal on/off
type or and inverted off/on type. There are 16 points where n
represents the numbers 1 through 16.
Point n Type:
Units
ASCII (Bldg Spvr)
0 or 1 (LID)
Range
Normal or Invert (Bldg
Spvr)
0 or 1 (LID)
Default Value
Normal (Bldg Spvr)
1 (LID)
Set Point Screen —
The Set Point screen is used to con-
figure the occupied and unoccupied set points. See Fig. 39.
OCCUPIED LOW — The Occupied Low set point describes
the low temperature limit of the space during Occupied mode.
Occupied Low:
Units
degrees F (degrees C)
Range
40.0 to 90.0
Default Value
70.0
OCCUPIED HIGH — The Occupied High set point describes
the high temperature limit of the space during occupied mode.
This value must be at least 1.0
°
F above the occupied low limit
or the fan coil controller will automatically adjust the value to
be 1.5 F above the occupied low limit.
Occupied High:
Units
degrees F (degrees C)
Range
45.0 to 99.9
Default Value
74.0
UNOCCUPIED LOW — The Unoccupied Low set point de-
scribes the low temperature limit of the space during Unoccu-
pied mode.
Unoccupied Low: Units
degrees F (degrees C)
Range
40.0 to 90.0
Default Value
55.0
UNOCCUPIED HIGH — The Unoccupied High set point de-
scribes the high temperature limit of the space during unoccu-
pied mode. This value must be at least 1.0
°
F above the unoc-
cupied low limit or the fan coil controller will automatically ad-
just the value to be 1.5 F above the unoccupied low limit.
Unoccupied High: Units
degrees F (degrees C)
Range
45.0 to 99.9
Default Value
90.0
OCCUPIED HIGH RELATIVE HUMIDITY — The Occu-
pied High Relative Humidity set point describes the high hu-
midity limit of the space during Occupied mode.
Occupied High
Relative
Humidity:
Units
% RH
Range
0.0 to 100.0
Default Value
100.0
UNOCCUPIED HIGH RELATIVE HUMIDITY — The
Unoccupied High Relative Humidity set point describes the
high humidity limit of the space during Unoccupied mode.
Unoccupied High
Relative
Humidity:
Units
% RH
Range
0.0 to 100.0
Default Value
100.0
Fig. 36 — Holiday Configuration Screen
Fig. 35 — Controller Identification Screen
Description
Value
Units
Name
Notes
Description:
Fan Coil Control
DevDesc
Location:
Location
Software Part Number:
CESR131212-05
PartNum
Model Number:
ModelNum
Serial Number:
SerialNo
Reference Number:
Version 2.0
RefNum
→
506