The Average Occupied Cool Set Point displays the Occu-
pied Cool set point from the Linkage Thermostat.
Average Occupied
Cool Set Point:
Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None
The Average Unoccupied Heat Set Point displays the Unoc-
cupied heat set point from the Linkage Thermostat.
Average Unoccupied
Heat Set Point:
Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None
The Average Unoccupied Cool Set Point displays the Unoc-
cupied cool set point from the Linkage Thermostat.
Average Unoccupied
Cool Set Point:
Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None
The Average Zone Temperature displays the space tempera-
ture from the Linkage Thermostat.
Average Zone
Temperature:
Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None
The Average Occupied Zone Temperature displays the
space temperature from the Linkage Thermostat during occu-
pied periods.
Average Occupied
Zone Temperature:Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None
The Occupancy Status point displays a 1 if occupancy is re-
ported by the Linkage Thermostat. The Occupancy Status point
displays a 0 if occupancy is not reported by the Linkage Ther-
mostat.
Occupancy
Status:
Display Range
0, 1
Default Value
0
Network Access None
Water System Manager Maintenance
Screen —
The Water System Manager Maintenance screen
is used to provide maintenance information for the water sys-
tem. See Fig. 44.
COOLING LINK ACTIVE — The Cooling Link Active de-
cision displays the status of communications between the fan
coil and the cool source with which it is linked. If Yes dis-
played, it indicates that the WSM (Water System Manager) is
successfully transmitting information to the fan coil from a
linked, configured, cooling source.
A No indicates that the fan coil is not currently communi-
cating with a cooling source. The lack of communication may
indicate that the WSMs algorithms are disabled, that the Load
Configuration Table is misconfigured, or that communication
has failed. The fan coil controller will determine that communi-
cation has failed when 5 minutes pass without any cool source
data being received from the WSM.
When No is displayed, the Chilled Water Temperature and
Cool Source Status decisions continue to display their last valid
data.
Cooling Link
Active?
Display Units
Yes/No
Default Value
No
HEATING LINK ACTIVE — The Heating Link Active deci-
sion displays the status of communications between the fan coil
and the heat source with which it is linked. If Yes displayed, it
indicates that the WSM is successfully transmitting informa-
tion to the fan coil from a linked, configured, heating source.
A No indicates that the fan coil is not currently communi-
cating with a heating source. The lack of communication may
indicate that the WSMs algorithms are disabled, that the Load
Configuration Table is misconfigured, or that communication
has failed. The fan coil controller will determine that communi-
cation has failed when 5 minutes pass without any heat source
data being received from the WSM. When No is displayed
here, the Hot Water Temperature and Heat Source Status deci-
sions continue to display their last valid data.
Heating Link
Active?
Display Units
Yes/No
Default Value
No
COOL SOURCE NUMBER — The Cool Source Number
decision displays the number of the cool source that is linked to
the fan coil by a WSM. Cool source numbers are determined
by the number of the associated Cool Source Configuration
Table at the WSM. A 0 will be displayed in this decision if no
cool source is configured for the fan coil at the WSM.
Cool Source
Number:
Display Units
1 to 4 (cool source
numbers)
Default Value
0 = no cool source
HEAT SOURCE NUMBER — The Heat Source Number de-
cision displays the number of the heat source that is linked to
the fan coil by a WSM. Heat source numbers are determined
by the number of the associated Heat Source Configuration
Table at the WSM. A 0 will be displayed in this decision if no
heat source is configured for the fan coil at the WSM.
Heat Source
Number:
Display Units
1 to 4 (heat source
numbers)
Default Value
0 = no heat source
OCCUPANCY MODE — The current occupancy status of
the fan coil is displayed in this decision. The occupancy mode
is occupied when the fan coil’s occupancy time schedule is oc-
cupied (or biased occupied). It is unoccupied when the fan
coil’s occupancy schedule is unoccupied.
Occupancy
Mode:
Display Units
0 = unoccupied 1 =
occupied (or biased
occupied)
Default Value
1
CHILLED WATER TEMPERATURE — The Chilled Water
Temperature decision displays the current leaving water
temperature at the cool source that is linked to the fan coil by
the WSM. The decision will display the value 0.0 if no cool
source is configured for the fan coil at the WSM.
Chilled Water
Temperature:
Display Units
degrees F (degrees C)
Default Value
0.0