22
Fan data
30RY
Minimum available
Nominal available
Maximum available
static pressure*
static pressure
static pressure
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pa
l/s
Pa
l/s
Pa
l/s
017-026
0
2500
100
1940
150
1530
033
0
2920
100
2500
200
1940
040-050
0
4580
150
3890
230
3330
060
0
5560
150
4720
230
4030
070-080
0
6810
150
5830
230
5280
* Operation without duct system
Maximum air entering temperature, °C
30RY
At minimum
At nominal
At maximum
air flow
air flow
air flow
017-026
44
46
47.5
033
44
46
47
040-050
44.5
46
47
060
44.5
46
47
070-080
44.5
46
47
Performance correction factors
30RY
Cooling capacity
Power input
Min. flow
Max. flow*
Min. flow
Max. flow*
017-026
0.98
1.01
1.03
0.97
033
0.98
1.005
1.03
0.98
040-050
0.985
1.005
1.02
0.98
060
0.985
1.005
1.02
0.98
070-080
0.985
1.005
1.01
0.98
* Operation without duct system
Correction factor for the published performances, given at nominal air flow
Accessory suction filter pressure drop
Unit size
Additional pressure drop, Pa
0
2
4
6
8
10
12
14
017/026
033
040/050
060
070/080
Accessory reference number:
30RY-017-033: 30RY-900—002—EE—
30RY-040-080: 30RY-900—012—EE—
Replacement filter reference number:
—KH—12AE-005—EE—
30RY-017-033: quantity: 4
30RY-040-080: quantity: 6
The connection of the return air duct is now very easy, directly
on the air filter accessory.
Filter access for maintenance is ensured by removing the two
Metric screws on the unit side (rear view of the unit).
The cover panel, supplied with a handle, can now be removed.
The filters are attached to each other with a bracket that permits
sliding them into the frames.
10.5.3 - Fan discharge
A square flange is supplied mounted on the unit. An available
standard round flange can easily be installed at the fan discharge,
if the installer prefers the use of a round connection duct.
The unit is supplied with a cover panel on the discharge
side. This panel has to be removed before connection to the
duct system.
30RY-017-033: standard 560 mm diameter fan
30RY-040-080: standard 710 mm diameter fan
It is advisable to make the connection to the duct system with a
flexible collar. If this recommendation is not observed, a lot of
vibration and noise may be transmitted to the building structure.
The unit construction does not permit the support of a duct
weighing more than 10 kg. Non-observance may lead to
damage of the unit.
10.5.4 - Applicable regulations for units used with an air
duct system
Ensure that the return or supply air openings cannot accidentally
be obstructed by panels (for example low return air or opening
of doors).
Unit performances are given for an air-side pressure drop that
is indicated in the Physical Data table.
The three tables that follow contain fan characteristics, maxi-
mum air entering temperatures and performance correction
factors, depending on the air system used with the units.