47
10.4 - Installation
IMPORTANT: When the 30RQP units operate in heating mode,
dehumidification of the room air and defrosting of the air heat
exchangers generate a large amount of condensate that must
be evacuated from the unit installation site.
The 30RQP units must be installed on waterproof base that
allow efficient drainage and the evacuation of the condensate
from the heat exchangers.
At low ambient temperature, when the air heat exchangers form
frost, the defrost water must be collected to ensure that there is
no risk of flooding of the area where the 30RQP heat pumps
are installed.
All the fans on the same refrigeration circuit are controlled by
a variable speed drive and therefore run at the same spped.
Each refrigerant circuit (A and B) must have a separate ducting
system to prevent any air recycling between the air heat
exchangers of the different refrigerant circuits.
Each fan of the 30RQP unit with option 12 is equipped with a
factory-installed connection interface, allowing the connection
to the ductwork.
Please refer to the unit dimensional drawings for the exact
dimensions of the connection interface.
Please refer to the section 9.12 - "Fan arrangements” to affect
each fan to its own circuit.
10.5 - Nominal and maximum air flows per circuit (A
and B) for 30RQP sizes
30RQP Circuit A
Nominal/maximum air flow (l/s)
Circuit B
Nominal/maximum air flow (l/s)
160
4514 / 5417
9028 / 10833
180-230
9028 / 10833
9028 / 10833
240-270
9028 / 10883
13542 / 16250
310-330
9028 / 10883
18056 / 21667
380
13542 / 16250
18056 / 21667
430-520
18056 / 21667
18056 / 21667
10.6 - Factory-installed duct connection interface on each fan
V-shaped air heat exchangers
Top view
Side view
Detail of the duct
connection interface frame
Size of the duct connection frame 860x860x100mm