18
4.2 - Physical data 30RQP 160-520
30RQP
160
180
210
230
240
270
310
330
380
430
470
520
Sound levels
Standard unit
Sound power
(1)
dB(A)
90
91
91
91
92
92
93
93
94
94
94
94
Sound pressure at 10 m
(2)
dB(A)
58
59
59
59
60
60
61
61
62
62
62
62
Standard unit + option 15
(3)
Sound power
(1)
dB(A)
89
90
90
90
91
91
91
92
92
93
93
93
Sound pressure at 10 m
(2)
dB(A)
57
58
58
58
59
59
59
60
60
61
61
61
Standard unit + option 15LS
(3)
Sound power
(1)
dB(A)
84
85
86
86
86
87
87
87
88
89
89
89
Sound pressure at 10 m
(2)
dB(A)
52
53
54
54
54
55
55
55
56
57
57
57
Dimensions
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Unit length with water buffer tank module opt
mm
3604
4798
5991
Operating weight
(4)
Standard unit
kg
1462 1542 1670
1693
2105 2252
2378 2608
3076 3347
3359 3408
Standard unit + option 15 /15LS
kg
1545 1624
1778 1801
2213
2378
2504 2752
3239
3527
3539 3588
Standard unit + option 15/15LS + option 116W
(3)
kg
1685
1764
1930 1952
2373
2587
2722
2957
3443 3772
3821 3870
Unit + option 15 + option 116W + Water buffer tank module
kg
2644 2723
2889 2911
3332 3546
3681 3916
4402 4731
4780 4829
Compressors
Hermetic Scroll 48.3 r/s
Circuit A
1
1
2
2
2
2
2
2
3
4
4
4
Circuit B
2
2
2
2
2
3
3
4
4
4
4
4
No. of control stages
3
3
4
4
4
5
5
6
7
8
8
8
Refrigerant
(4)
R-410A
Circuit A charge
kg
14.5 22.0 23.0 24.0 27.0 27.0 30.0 33.0 42.0 53.0 54.0 56.0
tCO
2
e
30.3 45.9 48.0 50.1 56.4 56.4 62.6 68.9 87.7 110.7 112.8 116.9
Circuit B charge
kg
23.0 23.0 23.0 24.0 35.0 36.0 48.5 53.0 53.0 53.0 54.0 56.0
tCO
2
e
48.0 48.0 48.0 50.1 73.1 75.2 101.3 110.7 110.7 110.7 112.8 116.9
Control
Touch Pilot Control
Minimum capacity
%
33% 33% 25% 25% 25% 20% 20% 17% 14% 13% 13% 13%
Air heat exchanger
Grooved copper tubes and aluminium fins
Fans
Axial Flying Bird 4 with rotating shroud
Quantity
3
4
4
4
5
5
6
6
7
8
8
8
Maximum total air flow
l/s
13542
18056 18056 18056 22569 22569 27083 27083 31597
36111 36111 36111
Maximum rotation speed
rps
16
16
16
16
16
16
16
16
16
16
16
16
Water heat exchanger
Dual-circuit plate heat exchanger
Water volume
l
15
15
15
19
27
27
35
44
44
44
47
53
Max. water-side operating pressure without hydraulic module
kPa
3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200 3200
Hydraulic module (option)
Pump, Victaulic screen filter, safety relief valve, water and air bleed valve, pressure
sensors, expansion vessel (option)
Pump
Centrifugal pump, monocell, 48.3 rps, low- or high-pressure (as required), single or dual
(as required)
Expansion vessel volume
l
50
50
50
50
80
80
80
80
80
80
80
80
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic type
Connections
inch
3
3
3
3
4
4
4
4
4
4
4
4
External diameter
mm
88.9 88.9 88.9 88.9 114.3 114.3 114.3 114.3 114.3 114.3 114.3 114.3
Chassis paintwork
Colour code: RAL 7035
(1)
In dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measurements according to ISO 9614-1
under nominal operating conditions EN14511 - cooling mode.
(2) In dB ref 20µPa, weighting (A). Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound
power Lw(A).
(3) Options: 15 = low noise level, 15LS = very low noise level, 116W = variable speed high-pressure dual-pump hydraulic module.
(4) Values are guidelines only. Refer to the unit nameplate.
Eurovent certified values