9.14 - Fan arrangement
CKT A
CKT B
CKT A
CKT B
CKT A
CKT A
CKT A
30RQM/30RQP 240-270
30RQM/30RQP 310-330
30RQM/30RQP 380
CKT B
30RQM/30RQP 160
30RQM/30RQP
180-210-230
CKT B
CKT A
CKT B
CKT B
30RQM/30RQP 430-470-520
El
ec
11
21
22
11
12
21
22
11
12
21
31
32
22
11
21
31
32
22
41
42
11
12
21
31
32
22
41
42
11
12
21
31
32
22
11
12
21
31
32
El
ec
Elec
Elec
Elec
Elec
9.15 - Fan stages (30RQM units only)
30RQM standard
unit
Circuit Stage 1 Stage 2
Stage 3
Stage 4
Variable drive on 30RQP
Variable drive on
Option 28
160
A
EV11
EV11
EV11
B
EV21
EV21+EV22
EV21+EV22
EV21
180-210-230
A
EV11
EV11+ EV12
EV11+ EV12
EV11
B
EV21
EV21+ EV22
EV21+ EV22
EV21
240-270
A
EV11
EV11 + EV12
EV11 + EV12
EV11
B
EV31
EV31+EV21
EV31+EV21+EV32
EV31+EV21+EV32
EV31
310-330
A
EV11
EV11+ EV12
EV11+ EV12
EV11
B
EV21
EV21+EV31
EV21+EV31+EV22
EV21+EV31+EV22+EV32
EV21+EV31+EV22+EV32
EV21
380
A
EV21
EV21+EV11
EV21+EV11+EV22
EV21+EV11+EV22
EV21
B
EV31
EV31+EV41
EV31+EV41+EV32
EV31+EV41+EV32+EV42
EV31+EV41+EV32+EV42
EV31
430-470-520
A
EV11
EV11 + EV21
EV11 + EV21 + EV12
EV11 + EV21 + EV12 + EV22
EV11 + EV21 + EV12 + EV22
EV11
B
EV31
EV31 + EV41
EV31 + EV41 + EV32
EV31 + EV41 + EV32 + EV42
EV31 + EV41 + EV32 + EV42
EV31
9.16 - Variable speed ventilation (30RQP units only)
30RQP units differ from the 30RQM units by the introduction
of variable speed drives on the fans to optimise the efficiency of
the unit depending on the conditions of use (air temperature,
circuit capacity) and thereby improve the seasonal efficiency
(ESEER and SCOP).
All fans in the same refrigerant circuit are controlled by a single
variable speed drive. Therefore, they operate together at the
same rotational speed. The rotational speed at full load or part
load of each circuit is controlled by an algorithm that
continuously optimises the condensing temperature in cooling
mode or the evaporation temperature in heating mode to obtain
the best energy efficiency of the units (EER and COP) whatever
the operating conditions.
Fan motor electrical protection
The motors of a same circuit are electrically protected by the
variable frequency drive in case of short-circuit, locked rotor or
general overload. Each variable drive follows a variable current
curve, based on the frequency from 5 to 50 Hz and the number
of fans controlled.
In case of fan failure (e.g. motor disconnected) the variable drive
will detect this problem and an alert will be sent to the user
interface. Refer to the 30RQM/30RQP control manual for the
list of alarms.
9.17 - Touch Pilot control
The interface of the "Touch Pilot Control" has the following
characteristics:
•
It has a 5-inch colour screen.
•
It is intuitive and user-friendly. Clear and concise information
is presented in the local language (choice of 8 languages).
•
The screen menus can be adapted for different users (end
client, maintenance personnel, Carrier engineer).
•
Unit setting and use are secure. Password protection prevents
unauthorised access to advanced parameters.
•
No password is required to access the most important
operating parameters.