5.5 - Electrical data 30RB 170R-380R
30RB
170R 190R 210R 230R 270R 310R 340R 380R
Power circuit supply
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1) or (2)
Circuit A&B
kW
74,6
81,2
90,8
99,4 118,6 133,9 148,3 163,5
Power factor at maximum power
(1) or (2)
Displacement Power Factor (Cos Phi), standard unit
0,83
0,83
0,83
0,83
0,83
0,83
0,83
0,83
Maximum operating current draw (Un)
(1) or (2)
Standard unit
A
129,0 141,2 157,8 172,0 205,2 231,6 256,5 282,9
Maximum current (Un-10%)
(1) or (2)
Standard unit
A
137,7 150,6 168,6 183,6 219,6 247,5 274,5 302,4
Maximum start-up current (Un)
(2) + (3)
Standard unit
A
305
354
370
348
418
444
469
496
Unit + option 25/25E
A
262
302
318
305
366
392
417
444
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan c locked rotor current of the largest compressor.
5.6 - Electrical data 30RBP 170R-950R
30RBP
170R 190R 210R 230R 270R 310R 340R 380R 410R
Power circuit supply
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1) or (2)
Circuit A&B
kW
74,8
81,5
91,1
99,8 118,9 134,3 148,7
164
178,4
Power factor at maximum power
(1) or (2)
Displacement Power Factor (Cos Phi), standard unit
0,85
0,86
0,85
0,85
0,85
0,85
0,85
0,85
0,85
Maximum operating current draw (Un)
(1) or (2)
Standard unit
A
126,3 137,6 154,2 168,4 201,6 227,1 252,0 277,5 302,4
Maximum current (Un-10%)
(1) or (2)
Standard unit
A
135
147
165
180
216
243
270
297
324
Maximum start-up current (Un)
(2) + (3)
Standard unit
A
302
350
367
344
414
440
465
490
515
Unit + option 25/25E
A
259
298
315
301
362
388
413
438
463
30RBP
450R 480R 550R 610R 670R 720R 770R 800R 870R 950R
Power circuit supply
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1) or (2)
Circuit A&B
kW
193,7 208,1 237,8 256,4 282,7 306,1 328,5 340,2 374,4 405,6
Power factor at maximum power
(1) or (2)
Displacement Power Factor (Cos Phi), standard unit
0,85 0,85 0,85 0,84 0,84 0,84 0,84 0,84 0,84 0,84
Maximum operating current draw (Un)
(1) or (2)
Standard unit
A
327,9 352,8 403,2 439,5 486,0 525,0 565,0 584,5 644,0 696,0
Maximum current (Un-10%)
(1) or (2)
Standard unit
A
351
378
432
472
522
564
607
628
692
748
Maximum start-up current (Un)
(2) + (3)
Standard unit
A
541
565
616
770
823
856
902
915
981 1027
Unit + option 25/25E
A
489
513
564
687
740
773
819
832
898
944
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan c locked rotor current of the largest compressor.