5.2 - Physical data 30RBP 170R to 950R
30RBP
170R 190R 210R 230R 270R 310R 340R 380R 410R
Sound levels
Standard unit
Sound power
(1)
dB(A)
91,0
90,5
90,5
92,0
92,0
93,0
93,0
93,5
93,5
Sound pressure at 10 m
(2)
dB(A)
58,5
58,5
58,5
60,0
60,0
60,5
60,5
61,0
61,5
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
85,5
85,5
85,5
86,5
86,5
87,5
87,5
88,0
88,0
Sound pressure at 10 m
(2)
dB(A)
53,0
53,5
53,5
54,5
54,5
55,5
55,5
55,5
56,0
Dimensions - standard unit
Standard unit
Length
mm
2410 2410 2410 2410 2410 3604 3604 3604 3604
Width
mm
2253 2253 2253 2253 2253 2253 2253 2253 2253
Height
mm
2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + option 307
(3)
Length
mm
3604 3604 3604 3604 3604 4798 4798 4798 4798
Operating weight
(4)
Standard unit
kg
1349 1397 1397 1521 1556 1995 2049 2211 2269
Unit + option 15LS
(3)
kg
1432 1480 1480 1630 1665 2122 2176 2356 2414
Unit + option 15LS + option 116W
(3)
kg
1567 1615 1615 1765 1811 2271 2371 2551 2609
Unit + option 15LS + option 116W + option 307
(3)
kg
2550 2598 2598 2748 2794 3258 3357 3537 3594
Compressors
Hermetic Scroll 48,3 r/s
Circuit A
1
1
1
2
2
2
2
3
3
Circuit B
2
2
2
2
2
3
3
3
3
Number of power stages
3
3
3
4
4
5
5
6
6
Unit PED category
III
III
III
III
III
III
III
III
III
Refrigerant
(4)
R32 / A2L /GWP= 675 as per AR4
Circuit A
kg
6,1
9,3
9,3
10,9
11,3
11,9
12,7
17,3
18,0
tCO
2
e
4,1
6,3
6,3
7,4
7,6
8,0
8,6
11,7
12,2
Circuit B
kg
10,9
10,9
10,9
10,9
11,3
16,7
17,5
17,3
18,0
tCO
2
e
7,4
7,4
7,4
7,4
7,6
11,3
11,8
11,7
12,2
Oil
Circuit A
l
6,6
6,6
6,6
13,2
13,2
13,2
13,2
19,8
19,8
Circuit B
l
13,2
13,2
13,2
13,2
13,2
19,8
19,8
19,8
19,8
Capacity control
SmartVu
TM
Minimum capacity
%
33
33
25
25
25
20
20
17
17
Condenser
All-aluminium micro-channel coils (MCHE)
Fans
Axial Flying Bird 6 with rotating shroud
Standard unit
Quantity
3
3
4
4
4
5
5
6
6
Maximum total air flow
l/s
14460 19280 19280 19280 19280 24100 24100 28920 28920
Maximum rotation speed
r/s
16
16
16
16
16
16
16
16
16
Evaporator
Direct expansion brazed-plate heat exchanger
Water volume
l
15
15
15
19
27
27
35
44
44
Max. water-side operating pressure without hydraulic module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydronic module (option)
Pump, Victaulic screen filter, relief valve, water and air vent valve,
pressure sensors
Pump
Centrifugal pump, monocell, 48,3 r/s, low- or high-pressure
(as required), single or dual (as required)
Expansion tank volume (Option)
l
50
50
50
50
50
80
80
80
80
Buffer tank volume (option)
l
550
550
550
550
550
550
550
550
550
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic
®
type
Connections
inches
3
3
3
3
3
4
4
4
4
External diameter
mm
88,9
88,9
88,9
88,9
88,9 114,3 114,3 114,3 114,3
Casing paint colour
Colour code RAL 7035
(1) In dB ref=10
-12
W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in accordance
with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information, calculated
from the sound power Lw(A).
(3) Options: 15LS = Very low noise level, 116W = Variable-speed high pressure dual-pump hydraulic module, 307 = Water buffer tank module,
(4) Values are guidelines only. Refer to the unit name plate.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
11
Содержание 30RB-170R
Страница 2: ......
Страница 51: ...11 13 Fan arrangement 11 MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS 51...
Страница 90: ......
Страница 91: ......