Table 1 — Rigging Weights, One-Piece Shipment*

UNIT
16JT

WEIGHT

lb

kg

810

11,680

5 300

812

11,900

5 400

814

12,120

5 500

816

16,090

7 300

818

16,310

7 400

821

16,530

7 500

824

16,970

7 700

828

17,410

7 900

832

20,275

9 200

836

20,935

9 500

841

23,365

10 600

847

24,025

10 900

854

26,450

12 000

857

31,740

14 400

865

32,400

14 700

873

35,265

16 000

880

38,135

17 300

080

44,080

20 000

090

49,590

22 500

100

54,440

24 700

110

59,505

27 000

120

66,120

30 000

135

71,630

32 500

150

77,140

35 000

080L

50,695

23 000

090L

56,865

25 800

100L

60,610

27 500

110L

65,020

29 500

120L

71,405

32 400

135L

83,755

38 000

150L

87,060

39 500

*Standard shipping configuration for sizes 810-880 and 080-100 is one piece.

(Two-piece shipment for these sizes is optional.)
Standard shipping configuration for sizes 110-150 and 080L-150L is two pieces.
(One-piece shipment for these sizes is optional.)

Table 2 — Rigging Weights, Two-Piece Shipment*

UNIT
16JT

WEIGHT

Absorber/Evaporator

Generator/Condenser

lb

kg

lb

kg

810

8,595

3 900

3,085

1 400

812

8,815

4 000

3,085

1 400

814

9,035

4 100

3,085

1 400

816

11,460

5 200

4,630

2 100

818

11,680

5 300

4,630

2 100

821

11,680

5 300

4,850

2 200

824

11,900

5 400

5,070

2 300

828

12,120

5 500

5,290

2 400

832

13,885

6 300

6,390

2 900

836

14,325

6 500

6,610

3 000

841

16,090

7 300

7,275

3 300

847

16,530

7 500

7,495

3 400

854

18,295

8 300

8,155

3 700

857

22,040

10 000

9,700

4 400

865

22,480

10 200

9,920

4 500

873

23,005

10 800

11,460

5 200

880

26,010

11 800

12,125

5 500

080

29,755

13 500

14,325

6 500

090

34,160

15 500

15,430

7 000

100

37,470

17 000

16,970

7 700

110

41,875

19 000

17,630

8 000

120

47,385

21 500

18,735

8 500

135

51,795

23 500

19,835

9 000

150

55,100

25 000

22,040

10 000

080L

35,265

16 000

15,430

7 000

090L

40,335

18 300

16,530

7 500

100L

42,980

19 500

17,630

8 000

110L

45,845

20 800

19,175

8 700

120L

50,690

23 000

20,715

9 400

135L

59,510

27 000

24,245

11 000

150L

62,845

28 500

24,245

11 000

*Standard shipping configuration for sizes 810-880 and 080-100 is one piece.

(Two-piece shipment for these sizes is optional.)
Standard shipping configuration for sizes 110-150 and 080L-150L is two pieces.
(One-piece shipment for these sizes is optional.)

Fig. 6 — Rigging Two-Piece Units

Fig. 5 — Rigging One-Piece Units

6

Содержание 16JT080-150

Страница 1: ...pressurized condition NEVER APPLY an open flame or live steam to a refrigerant cylinder Dangerous overpressure can result When neces sary to heat a cylinder use only warm 110 F 43 C water DO NOT REUSE disposable nonreturnable cylinders or at tempt to refill them It is DANGEROUS AND ILLEGAL When cylinder is emptied evacuate remaining gas pressure loosen the collar and unscrew and discard the valve ...

Страница 2: ...ing and rupture disc piping if the last five digits are 92XXX the model comes with rupture disc piping only For 16JT chillers sizes 810 to 880 the evaporator and ab sorber are located side by side for sizes 080 to 150 and 080L to 150L the evaporator is located above the absorber Inspect Shipment Fig 2 One piece chillers are at a deep vacuum when shipped Do not open any valves until the vacuum has ...

Страница 3: ...ator shell 2 Open the shipping valve on the generator condenser as sembly to relieve pressure To keep foreign particles out of the chiller do not leave chiller open any longer than necessary Do not remove any stock from pipe ends Do not get slag inside chiller while flamecutting 3 Remove all piping end plates by flamecutting the end plate and weld the flange around each outer diameter as shown in ...

Страница 4: ...5 2185 2185 2285 2285 2160 UNIT 16JT 836 841 847 854 857 865 873 880 Overall Length A 5335 5385 5385 5385 6985 6985 6985 7060 Overall Width B 1980 2110 2110 2235 2110 2110 2235 2310 Overall Height C 2540 2770 2770 2970 2950 2950 2870 3020 Height D 2160 2260 2260 2390 2460 2460 2335 2415 Standard shipping configuration for sizes 810 880 is one piece Dimension D is height of absorber evaporator sect...

Страница 5: ...20L 135L 150L Overall Length A 7900 7900 7925 7975 7975 8075 8075 Overall Width B 2565 2515 2690 2795 2920 3075 3250 Overall Height C 3000 3175 3350 3530 3735 3960 4165 Height D 2390 2540 2665 2845 3000 3225 3405 Standard shipping configuration for sizes 080 100 is one piece sizes 110 150 and 080L 150L are 2 piece Dimension D is height of absorber evaporator section for two piece shipment Removal ...

Страница 6: ... 815 4 000 3 085 1 400 814 9 035 4 100 3 085 1 400 816 11 460 5 200 4 630 2 100 818 11 680 5 300 4 630 2 100 821 11 680 5 300 4 850 2 200 824 11 900 5 400 5 070 2 300 828 12 120 5 500 5 290 2 400 832 13 885 6 300 6 390 2 900 836 14 325 6 500 6 610 3 000 841 16 090 7 300 7 275 3 300 847 16 530 7 500 7 495 3 400 854 18 295 8 300 8 155 3 700 857 22 040 10 000 9 700 4 400 865 22 480 10 200 9 920 4 500...

Страница 7: ...rber 9 Refrigerant from condenser Fig 9 Chiller Configuration 16JT810 880 Fig 8 Flamecutting and Welding Detail 1 Weak solution from level control box 2 Weak solution to high stage generator 3 Strong solution from high stage generator 4 Weak solution to level control box 5 Cooling water connection absorber to condenser 6 Refrigerant from condenser 7 Purge line condenser to absorber 8 Refrigerant f...

Страница 8: ...connections are vacuum leak tight 2 Cut shipping braces between upper shell assemblies Purge Exhaust Assembly Install the purge ex haust assembly on the purge exhaust valve as shown in Fig 12 Chiller Leak Test All field welded joints on the chiller must be leak tested before starting the chiller Leak test as follows 1 Close all external service valves 2 If the chiller is under vacuum bring it to a...

Страница 9: ...ign working pressure 7 Install a 3 way cooling tower 3 way bypass valve if the cooling water temperature might fall below 59 F 15 C during chiller operation 8 Install thermometer wells and thermometers on the en tering and leaving chilled water pipes Fig 14 Items T1 and T2 absorber entering and leaving cooling water pipes Fig 14 Items T3 and T4 and condenser leaving cool ing water pipe Fig 14 Item...

Страница 10: ...erator to limit the pressure to 114 psig 786 kPa The safety relief valve should be vented to the outside of the building for safety 7 Install steam condensate drain piping so that the back pres sure at the connection to the chiller is less than 7 psig 48 kPa to prevent condensate back up into the generator tubes at low load conditions Include a check valve Fig 14 Item V6 and manual shut off valve ...

Страница 11: ...ailable power supply and safety interlocks to be sure they match the chiller equipment requirements including three phase power supply for controls and chiller her metic pumps start and run interlocks for chilled water and cooling wa ter pumps and for cooling tower fan s remote chiller start stop contacts if used remote operating status and fault indication if used SENSOR ELEMENTS For all sensor e...

Страница 12: ...d with solution and refrigerant The hermetic pumps can be seriously damaged by dry operation See 16JT Start Up Operation and Maintenance instruc tions for charging procedures Fig 17 Capacity Controls Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 Tab 5b PC 211 ...

Отзывы: