background image

SERVICE POLICY & PROCEDURES

YCIV

0590-1500 50Hz & 0157-0397 60Hz

StaRt-UP CHECkLISt

Supersedes: Nothing

Form 201.23-CL1 (309)

COmmISSIOnIng

PREPaRatIOn

Commissioning of this unit should only 

be  carried  out  by  Johnson  Controls 

Authorized personnel.

Commissioning personnel should be thoroughly familiar 

with the information contained in this literature.

Perform the commissioning using the detailed checks 

outlined in the EQUIPMENT START-UP CHECK as 

the commissioning procedure is carried out.

PREPaRatIOn – gEnERaL

The following basic checks should be made with the 

customer power to the unit switched OFF.

Proper electrical lock out and tag pro-

cedures must be followed.

Inspection 

Inspect  unit  for  installation  damage.  If  found,  take 

action and/or repair as appropriate.

Refrigerant Charge

Packaged units are normally shipped as standard with a 

full refrigerant operating charge. Check that refrigerant 

pressure is present in both systems and that no leaks 

are  apparent.  If  no  pressure  is  present,  a  leak  test 

must be undertaken, the leak(s) located and repaired.  

Remote systems and units are supplied with a nitrogen 

holding charge.  These systems must be evacuated with 

a suitable vacuum pump/recovery unit as appropriate 

to below 500 microns.

Do  not  liquid  charge  with  static  water  in  the  cooler.  

Care must also be taken to liquid charge slowly to avoid 

excessive thermal stress at the charging point. Once the 

vacuum is broken, charge into the condenser coils with 

the full operating charge as given in the Technical Data 

Section.

Service and Oil Line Valves

Open  each  compressor  suction,  economizer,  and 

discharge service valve.  If valves are of the back-seat 

type, open them fully (counterclockwise) then close one 

turn of the stem to ensure operating pressure is fed to 

pressure transducers. Open the liquid line service valve 

and oil return line ball valve fully in each system.

Compressor Oil

To add oil to a circuit - connect a YORK hand oil pump 

(Part  No.  470-10654-000)  to  the  1/4”  oil  charging 

valve on the oil separator piping with a length of clean 

hose  or  copper  line,  but  do  not  tighten  the  flare  nut. 

Using  clean  oil  of  the  correct  type  (“L”  oil),  pump 

oil  until  all  air  has  been  purged  from  the  hose  then 

tighten the nut.  Stroke the oil pump to add oil to the oil 

system. The oil level should be between the middle of 

the lower and middle of the upper sight glasses of the 

oil separator.  Approximately 4-5 gallons is present in 

the each refrigerant system, with typically 1-2 gallons 

in each oil separator.  Oil levels in the oil separators 

above the top sight glass in either oil separator should 

be  avoided  and  may  cause  excessive  oil  carryover 

in  the  system.    High  oil  concentration  in  the  system 

may  cause  nuisance  trips  resulting  from  incorrect 

readings on the level sensor and temperature sensors.  

Temperature  sensor  errors  may  result  in  poor  liquid 

control  and  resultant  liquid  overfeed  and  subsequent 

damage to the compressor. 

Fans

 

Check  that  all  fans  are  free  to  rotate  and  are  not 

damaged.  Ensure blades are at the same height when 

rotated.  Ensure fan guards are securely fixed.

Summary of Contents for YCIV 0590-1500 50Hz

Page 1: ...enser coils with the full operating charge as given in the Technical Data Section Service and Oil Line Valves Open each compressor suction economizer and discharge service valve If valves are of the b...

Page 2: ...ore placing the unit back in service valves should be opened and power must be switched on if power is removed for more than 8 hours for at least 8 hours 24 hours if ambient temperature is below 86 F...

Page 3: ...igerant will be seen in the liquid line sight glass After several minutes of operation and provided a full charge of refrigerant is in the system the bubbles will disappear and be replaced by a solid...

Page 4: ...the sight glass If subcooling is out of range add or remove refrigerant as required to clear the sight glass Do not overcharge the unit Subcooling should be checked with a flash tank level of approxim...

Page 5: ...roperly charged and there are no piping leaks 4 Open each system suction service valve discharge service valve economizer service valve liquid line stop valve and oil line ball valve 5 The oil separat...

Page 6: ...s the cooler Excessive flow may cause catastrophic damage to the evaporator 7 Check the control panel to ensure it is free of foreign material wires metal chips tools documents etc 8 Visually inspect...

Page 7: ...using the arrow keys scroll to the compressor overload settings Verify the Fac tory Set overload potentiometer s on the VSD logic board are set correctly In the unlikely event that they are not set c...

Page 8: ...CONTACT YORK REPRESENTATIVE Programmed Values 10 Program the required operating values into the micro for cutouts safeties etc and record them in the chart below Suction Press Cutout _________________...

Page 9: ...Daily Schedule start and stop times 14 Place the panel in Service mode and turn on each fan stage one by one Assure the fans rotate in the correct direction so air flow exits the top of the chiller 1...

Page 10: ...entering the compressor and the temperature corresponding to the suction pressure as shown in a standard pressure temperature chart SUPERHEAT Example Suction Temp 46 F 8 C minus Suction Press 30 PSIG...

Page 11: ...FORM 201 23 CL1 309 JOHNSON CONTROLS 11 notes...

Page 12: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2009 ALL RIGHTS RESERVED Form 201 23 CL1 309 Supersede...

Reviews: