Humidifiers | Displays & Internal Controls

Humidifiers

G-6

 

www.carnes.com

“SETTINGS”

The Settings menu is the page where all operational 
values can be set. It is password protected by default, 
with a default password of ‘1212’.

The password can be disabled under the ‘Settings 
Password’ on the second Settings page. See ‘Settings 
Password’ section for more details.

Any adjustment made to any setting can be done ‘on-the-
fly’. Which means when a change occurs, the humidifier 
will react accordingly without the need of shutting off the 
unit or even stopping steam output. In general, any page 
within the True Touchscreen system can be accessed, 
monitored, or changed ‘on-the-fly’.

Max Output Adjust

 –

This page adjusts the Maximum Output of the humidifier. 
The Maximum Output can be adjusted lower from the 
nominal output value of the unit (set at the factory). The 
unit cannot be set lower than 20% of the nominal value 

This page consists of a counter where the user can 
monitor the life, in hours, of the cylinder. When changing 
a cylinder, press the ‘Reset’ button on this page to reset 
the timer. The Cylinder Life Counter only counts the 
amount of actual runtime of the cylinder (the time when 
the contactor is pulled in). The counter value is saved 
even when the humidifier is powered down. The national 
average cylinder life is about 1150 hours, but this can 
vary greatly depending on individual water conditions.

Fan Speed Adjust

 –

This page consists of a slider bar that can change the 
speed of the fans when the humidifier is connected to 
an optional blower box. This slider bar will not affect the 
operation of the humidifier if no blower box is attached. 
The bar can change the speeds of the fans from 0 to 
100% of the max fan speed. Also displayed on this page 
is an estimate of the current fan air output, in Cubic Feet 
per Minute (CFM). This adjustment is particularly useful 
if the humidifier is of a smaller capacity, and less noise 
from the fans is appreciated.

of the humidifier. The Maximum Output value, when 
changed, also changes the Max Setpoint value on the 
Setpoints page.

Cylinder Life Counter

 –

Содержание HBAH

Страница 1: ...Humidifiers www carnes com G 1 Humidifiers Steam Humidifiers COMMERCIAL INDUSTRIAL AND INSTITUTIONAL STEAM HUMIDIFIERS HCHH Shown...

Страница 2: ...oportional Humidistat or External Signal from DDC Controls Optional internal circuit breaker available Please note certain units require circuit breakers per NEC 48 amp guidelines True Touchscreen con...

Страница 3: ...omponent Activity menu HIGH WATER LED The HIGH WATER LED is an orange light illuminated when the High Water Sensor is activated An activated High Water Sensor indicates that the water has risen to the...

Страница 4: ...midifier if any Indicator light to the left of the button turns red when service is needed and will otherwise remain green Refer to the separate Service 5 Maize Help buttons are used exclusively in th...

Страница 5: ...her filling or draining the cylinder The Drain Valve is on when the humidifier is draining the cylinder The Contactor is on when the humidifier is producing steam The High Water Sensor is on when the...

Страница 6: ...user can monitor the life in hours of the cylinder When changing a cylinder press the Reset button on this page to reset the timer The Cylinder Life Counter only counts the amount of actual runtime of...

Страница 7: ...ater situa tion the humidifier will continue to run If the humidifier cannot work it s way back up the normal max controlled setpoint the humidifier will shut down after the High Water Timeout value e...

Страница 8: ...humidifier is programmed into the unit This page is password protected and number should not be modified by the end user Contact the factory if further information is needed Corrective Drain Length Th...

Страница 9: ...cted to the steam distributor pipe The circuit board reacts to current flow between the electrodes and automatically opens the fill solenoid valve when more water is required to maintain the desired o...

Страница 10: ...n in Figure B The distance between the humidifier cabinet and the steam distributor should be the minimum distance possible Refer to Table 5 for maximum length that may be installed based on static pr...

Страница 11: ...tube is used a minimum of one inch of insulation must be applied to prevent excessive condensation A short length of steam hose must be used to connect the cylinder in the humidifier to the copper tu...

Страница 12: ...If the steam distributor pipe is located in a duct where there is no air flow and the control humidistat is calling for humidity steam would be discharged into the duct where it would immediately cond...

Страница 13: ...ing recommended No 20 AWG wire Avoid running control wiring near high voltage primary wires Connections shown in Figure H are for typical on off controls For Carnes proportional controls see Figure J...

Страница 14: ...18 1 H_DHQU 20 415 1 6 9 16 6 25 1 25 Amp B600 16 6 H_DHMU 20 460 1 6 9 15 0 25 1 25 Amp B700 15 H_DHNU 20 575 1 6 9 12 0 20 1 15 Amp B700 12 H_DHCU 20 208 3 6 9 19 1 30 1 25 Amp B500 19 1 H_DHEU 20...

Страница 15: ..._GHWU 100 415 3 34 4 47 9 80 2 40 Amp C12 24 H_GHGU 100 460 3 34 4 43 3 70 1 60 Amp C12 21 7 H_GHHU 100 575 3 34 4 34 6 60 1 50 Amp C12 17 3 HBHH HCHH HSHH HTHH H_HHCU 125 208 3 43 119 5 200 4 40 Amp...

Страница 16: ...stallation anywhere between 100 and 25 of maximum capacity Voltage and Phase designate available phase and nominal voltages Single phase units may be operated from two legs of a three phase supply but...

Страница 17: ...ble in the unit to reduce the risk of costly damage in the event of internal failure It is not meant to be the primary protection as may be required by local and national electrical codes All units in...

Страница 18: ...HXPBB024S 23 13 16 605mm 7 8 HXPBB030S 29 13 16 757mm 7 8 HXPBB036S 35 13 16 910mm 7 8 Minimum Maximum PIPE N N T HXPBB040S 35 889mm 38 965mm 7 8 HXPBB044S 39 991mm 42 1067mm 7 8 HXPBB048S 43 1092mm 4...

Страница 19: ...above any items that would be damaged if a water leak were to develop STANDARD MOUNTING Factory attached to humidifier OPTION Mounted remote from humidifier FAN VOLTAGE 3 fans attached 12 volt from hu...

Страница 20: ...trol takes the temperature into consideration when calculating the humidity to provide an extra degree of precision 0 to 100 set point range WALL HUMIDISTAT ON OFF CONTROL WALL HUMIDISTAT PROPORTIONAL...

Страница 21: ...ge is from 0 to 100 R H Ambient operating conditions are from 0 to 85 C The humidistat may be mounted in a return duct to provide a mean of sensing and controlling relative humidity The humidistat may...

Страница 22: ...low 10 there is no adjustment AIR FLOW SWITCH VELOCITY TYPE AIR FLOW SWITCH PRESSURE DIFFERENTIAL TYPE Model HXAAE Air flow in the duct may be sensed by using this differen tial pressure switch The di...

Страница 23: ...cations it may be desirable to have the steam generator cylinder feed two steam distributor pipes T fittings can be installed in the steam hose and condensate return line Two models of condensate retu...

Страница 24: ...ter The pump is capable of operation with a vertical lift up to 12 feet or horizontal run of 40 feet The complete package includes drain pump with six feet of cord and plug for 115 volt operation 3 Pr...

Страница 25: ...t Steam Output Mounting Flange Drain Pipe 3 8 FPT Water Inlet 1 1 2 PVC Air Gap Connection 7 8 Dia Hole For Control Wiring 1 3 8 Dia Hole For Power Wiring 9 000 229 1 500 38 24 947 634 19 813 503 19 9...

Страница 26: ...set up non Carnes installation See picture 31 3 4 806 19 5 8 498 6 152 38 965 26 660 14 3 4 375 25 3 4 654 Drain Pipe Condensate Return Inlet Condensate Return Inlet Steam Outlets TOP 9 1 2 241 2 1 4...

Страница 27: ...ap on the fill water line to prevent backflow It is recommended that a drain air gap fitting be installed by a non Carnes contractor to prevent backflow of water Carnes offers an air gap fitting as a...

Отзывы: