Humidifiers
www.carnes.com
G-15
Humidifiers | Unit Availability
MODELS AVAILABLE AND ELECTRICAL DATA -
Table 8
Model
Max
Lb/Hr
Voltage
Phase
kW
Line
Amp
Disc.
Size
Optional
Cir.
Breaker*
Steam
Cylinder
Cyl Wire
Current
HBGH
HCGH
HSGH
HTGH
H_GHCU
50
208
3
17.2
47.8
80
2-35 Amp
C62
23.9
H_GHEU
50
230
3
17.2
43.2
70
1-60 Amp
C62
21.6
H_GHTU
50
380
3
17.2
26.2
40
1-40 Amp
C65
26.2
H_GHWU
50
415
3
17.2
24.0
40
1-40 Amp
C65
24
H_GHGU
50
460
3
17.2
21.6
35
1-30 Amp
C65
21.6
H_GHHU
50
575
3
17.2
17.3
30
1-25 Amp
C65
17.3
H_GHCU
*
60
208
3
20.7
57.4
*
90
2-40 Amp
*
C62
28.7
H_GHEU
*
60
230
3
20.7
51.9
*
80
2-40 Amp
*
C62
26
H_GHTU
60
380
3
20.7
31.4
50
1-50 Amp
C65
31.4
H_GHWU
60
415
3
20.7
28.8
45
1-45 Amp
C65
28.8
H_GHGU
60
460
3
20.7
26.0
40
1-40 Amp
C65
26
H_GHHU
60
575
3
20.7
20.8
35
1-30 Amp
C65
20.8
H_GHCU
*
80
208
3
27.5
76.5
*
125
2-60 Amp
*
C62
38.2
H_GHEU
*
80
230
3
27.5
69.2
*
110
2-50 Amp
*
C62
34.6
H_GHTU
80
380
3
27.5
41.9
70
1-60 Amp
C12
21
H_GHWU
80
415
3
27.5
38.4
60
1-60 Amp
C12
19.2
H_GHGU
80
460
3
27.5
34.6
60
1-50 Amp
C12
17.3
H_GHHU
80
575
3
27.5
27.7
45
1-40 Amp
C12
13.9
H_GHCU
*
100
208
3
34.4
95.6
*
150
2-60 Amp
*
C62
47.8
H_GHEU
*
100
230
3
34.4
86.4
*
150
2-60 Amp
*
C62
43.2
H_GHTU
*
100
380
3
34.4
52.3
*
110
2-50 Amp
*
C12
34.2
H_GHWU
100
415
3
34.4
47.9
80
2-40 Amp
C12
24
H_GHGU
100
460
3
34.4
43.3
70
1-60 Amp
C12
21.7
H_GHHU
100
575
3
34.4
34.6
60
1-50 Amp
C12
17.3
HBHH
HCHH
HSHH
HTHH
H_HHCU
*
125
208
3
43
119.5
*
200
4-40 Amp
*
C62 (2)
29.8
H_HHEU
*
125
230
3
43
108
*
175
4-40 Amp
*
C62 (2)
27
H_HHTU
*
125
380
3
43
65.3
*
100
2-50 Amp
*
C12 (2)
16.3
H_HHWU
*
125
415
3
43
59.8
*
90
2-45 Amp
*
C12 (2)
15
H_HHGU
*
125
460
3
43
54.0
*
90
2-40 Amp
*
C12 (2)
13.5
H_HHHU
125
575
3
43
43.2
70
2-30 Amp
C12 (2)
10.8
H_HHCU
*
150
208
3
51.7
143.5
*
225
4-50 Amp
*
C62 (2)
35.8
H_HHEU
*
150
230
3
51.7
129.7
*
200
4-50 Amp
*
C62 (2)
32.4
H_HHTU
*
150
380
3
51.7
78.6
*
125
2-60 Amp
*
C12 (2)
19.7
H_HHWU
*
150
415
3
51.7
71.9
*
110
2-60 Amp
*
C12 (2)
18
H_HHGU
*
150
460
3
51.7
64.8
*
100
2-50 Amp
*
C12 (2)
16.2
H_HHHU
*
150
575
3
51.7
51.9
*
80
2-35 Amp
*
C12 (2)
13
H_HHCU
*
175
208
3
60.3
167.3
*
300
4-60 Amp
*
C62 (2)
41.8
H_HHEU
*
175
230
3
60.3
151.3
*
250
4-60 Amp
*
C62 (2)
37.8
H_HHTU
*
175
380
3
60.3
91.6
*
150
4-35 Amp
*
C12 (2)
22.9
H_HHWU
*
175
415
3
60.3
83.9
*
150
2-60 Amp
*
C12 (2)
21
H_HHGU
*
175
460
3
60.3
75.6
*
125
2-60 Amp
*
C12 (2)
18.9
H_HHHU
*
175
575
3
60.3
60.5
*
100
2-50 Amp
*
C12 (2)
15.1
H_HHCU
*
200
208
3
68.9
191.2
*
300
4-60 Amp
*
C62 (2)
47.8
H_HHEU
*
200
230
3
68.9
172.9
*
300
4-60 Amp
*
C62 (2)
43.2
H_HHTU
*
200
380
3
68.9
104.7
*
175
4-40 Amp
*
C12 (2)
26.2
H_HHWU
*
200
415
3
68.9
95.9
*
150
4-35 Amp
*
C12 (2)
23.9
H_HHGU
*
200
460
3
68.9
86.4
*
150
2-60 Amp
*
C12 (2)
21.6
H_HHHU
*
200
575
3
68.9
69.2
*
110
2-50 Amp
*
C12 (2)
17.2
* = Circuit Breaker is REQUIRED per NEC 48 amp guidelines.