PROGRAMMING WM30-96
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
13
EXAMPLE OF ALARM PARAMETERS PROGRAMMING
The disconnection of a load when a set value of absorbed power is
required. For example when 300kW are exceeded, the alarm occurs and
a set load is disconnected. An UP alarm is selected. Below you’ll find the
recommended programming:
ENABLE:
YES
VARIABLES
: W system (W
∑
)
SET POINT 1
: 300kW
SET POINT 2
: 295kW
ON DELAY
: set the desired number of seconds: “5 seconds”.
300kW
295kW