PROGRAMMING WM30-96
Key-pad
NOTE
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
200 AN OUT 1:
this submenu allows the programming of the analog out-
puts (0-20mA, 0-10V). 201 VARIABLES: select the variable to be retran-
smitted by means of the analog output. 202 MIN OUT: set the value
expressed as % of the output range (0-20mA, 0-10V) to be coupled to the
minimum measured value. 203 MAX OUT: select the value expressed as %
of the output range (0-20mA, 0-10V) to be coupled to the maximum mea-
sured value. 204 MIN INPUT: minimum value of the variable input range to
which the “MIN OUT” value, retransmitted by the analog output, will be
coupled. 205 MAX INPUT: maximum value of the variable input range to
which the “MAX OUT” value, retransmitted by the analog output, will be
coupled.
220 METERS:
reset the ENERGY METERS choosing among: TOTAL,
PARTIAL: resets all energy meters, both total and partial. TOTAL +: resets
the total meters of imported energy. TOTAL -: resets the total meters of
exported energy. P: resets the partial meters of imported energy.
PARTIAL -: resets the partial meters of exported energy.
230 RESET:
carry out the reset of the MAX or dmd stored values.
240 CLOCK,
241 FORMAT: UE, set the time format as 24h european
(00:00) or USA as 12h american (12:00 AM). 242 TIME: set the current
time. 243 DATE: set the current date.
Some specific menus display only if the relevant modules are instal-
led.
10
Push for at
least 2 s
Page 9 (190)
Save the set
parameters and come
back to the measuring
mode.
List of available
variables
As AN OUT 1
Page 7 (10)