PROGRAMMING WM30-96
Key-pad
NOTE
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
120 RS232-458:
This function allows the user to set the RS232 and RS485
serial ports as well as the optical port.
130 ETHERNET:
This function allows the user to set the Ethernet port.
140 V ALARM 1:
This function allows you to set the alarm parameters. 141
ENABLE: enable (YES) or disable (NO) the alarm. 142 VARIABLES: set the
variable to be coupled to the alarm. 143 SET POINT 1:set the first alarm
set point of the variable. 144 SET POINT 2: set the second alarm set point
of the variable. 145 ON DELAY: set a delay on activation of the alarm.
180 DIG OUT 1:
This function allows the selected function to be coupled
to the selected digital output. 181 FUNCTION:
Alarm
, the digital output is
enabled only if the expected alarm status occurs.
Pulse
, the measured
energy is retransmitted by the digital output by means of pulses.
Remote
,
the digital output can be enabled by means of a command sent by means
of serial port. 182 AL LINK: select the reference alarm. 183 AL STATUS:
“ND” (normally de-energized relay) or “NE” (normally energized relay) 185
PULSE WEIG: selects the pulse weight (kWh per pulse). 186 OUT TEST:
active the TEST (YES), deactivate the TEST (NO). 187 POWER TEST: sets
the simulated power value (kW) to which a proportional pulse sequence
according to “PULSE WEIG” corresponds. The function is active until you
remain within the menu.
Some specific menus display only if the relevant modules are instal-
led.
9
Push for at
least 2 s
Page 7 (110)
Page 10 (200)
list of available
variables
list of available
variables
As DIG OUT 1
As V ALARM 1
As V ALARM 1
As V ALARM 1