MECHANICAL INSTALLATION

The Controller is designed to be sleeve mounted in a 1/16 DIN panel cutout with only the
front panel rated to NEMA4/IP66, provided that:

●  

the panel is smooth and the panel cutout is accurate;

●  

the mounting instructions are carefully followed.

DIN PANEL CUTOUT

1/16 DIN

: 45.0mm +0.6 / -0.0 wide, 45.0mm +0.6 / -0.0 high

Maximum panel thickness

9.5mm

Minimum spacing

20mm vertical, 10mm horizontal

MOUNTING

To mount a Controller proceed as follows:

1  Check that the controller is correctly orientated and then slide the unit into the cutout.

2  Slide the panel clamp over the controller sleeve pressing it firmly against the panel until

the controller is held firmly.

3  The controller front bezel and circuit board assembly can be unplugged from the sleeve.

Grasp the bezel firmly by the recesses on each side and pull. A screwdriver can be used
as a lever if required.                       

4  When refitting the bezel assembly it is important to press it firmly into the sleeve until the

latch clicks in order to compress the gasket and seal to NEMA4X/IP66.

CLEANING

Wipe down with damp cloth (water only)

CAUTION:  The controller should be isolated before removing or refitting it
in it’s sleeve. Live circuits can hold a charge for short periods after isolation
from voltage supply. Electrostatic precautions should be observed when
handling the controller outside it’s sleeve.

DIMENSIONS

Bezel*

Behind Panel 

Overall 

Behind panel

Width Height  Width  Height Length 

Length*

51.0 51.0 44.8 44.8 116.2 

106.7

Dimensions in mm
* includes gasket 

ELECTRICAL INSTALLATION

(See important Safety Information page 20)

OUTPUT DEVICES

WARNING:

Three types of output device may be factory fitted to the controllers, and users must choose
how to allocate these to outputs SP1 and SP2. (SP3 is always RLY). Check the model number
and output configuration against the 

Output Options Table

on page 8 before wiring the

instrument and applying power.

1  Solid state relay drive (SSd1/SSd2)

6Vdc (nominal) 20mA max.
To switch remote SSR (or logic)

2  Miniature power relay (rLY/rLY1/rLY3)

2A/250V AC resistive, Form A/SPST contacts.

3  Analog Output (

AnLG) (isolated)

Specify; 4–20mA 500

max +/- 0.1% fs typical

0–5Vdc 10mA (500

min) +/- 0.1% fs typical

0–10Vdc 10mA (1K

min) +/- 0.1% fs typical

SUPPLY VOLTAGE

100–240V 50–60HZ 6.0VA (nominal)
+/- 10% maximum permitted fluctuation

WIRING THE CONNECTOR

Prepare the cable carefully, remove a maximum of 8mm insulation and ideally tin to avoid
bridging. Prevent excessive cable strain. Maximum recommended wire size: 32/0.2mm 1.0mm

2

(18AWG).

INDUCTIVE LOADS

To prolong relay contact life and suppress interference it is recommended engineering practice
to fit a snubber (0.1uf/100 ohms) between relay output terminals.

CAUTION: 
Snubber leakage current can cause some electro-mechanical devices to be held ON.
Check with the manufacturers specifications.

Содержание T2000P Series

Страница 1: ...PID TEMPERATURE AND PROCESS CONTROLLER T2000P SERIES CARLO GAVAZZI A u t o m a t i o n C o m p o n e n t s...

Страница 2: ...or Orange Display Setpoint value or program selection Green LED Setpoint 1 output indicator Upper Red LED Setpoint 2 output indicator Lower Red LED Setpoint 3 output indicator Green Display Process va...

Страница 3: ...200 sec 25 sec Derivative approach 0 5 to 5 0 x bAnd 1 5 Cycle time or on off On off 0 1 to 81 sec 20 sec Offset manual reset 0 to 50 x bAnd In t off Setpoint lock SP1 Off on Adjust SP2 setpoint sens...

Страница 4: ...n a temperature application Re tuning after a large setpoint change Tuning multi zone and or heat cool applications Notes DAC is not re adjusted by Tune at setpoint Proportional Cycle Time can be pre...

Страница 5: ...S SECOND AND THIRD SETPOINTS SP2 and SP3 PRIMARY ALARM MODES Configure SP2 output to operate as an alarm from SP2 A in Level 2 and set the alarm setting in SEt 2 Level 1 Configure SP3 alarm mode SP3 A...

Страница 6: ...t range 10 to 50 mV using multiplier of 2 5 When using a transducer with an output less than 4 20mA the input maximum and minimum mV values can be calculated using the same multiplier Models with 0 to...

Страница 7: ...N OFF mode oFSt 0 to C F units 0 SP1 offset manual reset 50 bAnd Applicable in proportional and ON OFF mode with integral disable Int t oFF SP LK oFF on Lock main setpoint Locks the setpoint preventin...

Страница 8: ...ettings in Level A Re transmission These models above offer the option of using the analog output for Re transmission Select bAnd or bnd 2 value in LEVL 1 to equal the full range setting in LEVL A and...

Страница 9: ...rent settings LEVEL 4 Access to level 4 is gained through UEr in level 3 Press and hold and for 10 seconds Enter level 4 at Lock release and together Display reads LoCK nonE Program security using Loc...

Страница 10: ...nce the Linear Input option has been selected the setting here over rides the scale resolution setting di SP in Level 2 and will affect the following display readings Level A An hi An Lo Set 3 hYS 3 L...

Страница 11: ...s three modes of recovery from a power failure are available These either automatically Re start the Program from the beginning Continue it from where it stopped or Hold it waiting for a user re start...

Страница 12: ...nd 15 Program Run Mode To run a Program from LEVL P Press once then use to select the required program number from the PrOG list Press again once then use to select the run on option Press and hold fo...

Страница 13: ...G 1 SEG 2 SEG 3 SEG 4 SEG 5 PROG 3 SEG 1 SEG 2 SEG 3 SEG 4 STOP 30 SPRR 55 T SP 30 EXAMPLE PROGRAM Temp Time See segment configuration of this program detailed on page 18 Ramp Function Rate 105 deg ho...

Страница 14: ...es the selected program Paste only appears after a program is copied To add new program press once Add new programs at top of existing menu Select the required program number Default 1 Memory used Sel...

Страница 15: ...nt 2 becomes 3 To select operational mode of each segment Default Ramp SINT 10 PCYC 1 SUB P NONE SPRR 100 Important note Up button must be used after selecting the segment type to confirm it s selecti...

Страница 16: ...Program called at Call above Edit dEL Delete segment Edit inS Insert new segment FUNCTION LIST LEVEL P PROGRAMMER LEVEL P Access Level P from Level 1 Press and hold Function Settings Factory settings...

Страница 17: ...t 2E 3E SP2A and SP3A energised to mark event 2d 3E SP2A de energised SP3A energised to mark event To Return to LEVL P Press and hold To Read Programmer memory used USEd Press and together in LEVL P P...

Страница 18: ...C 1 T SP 137 T SP 85 T SP 30 HB V OFF E OP NONE PROG 3 Program settings for functions run FAiL St U and SPru not shown are all set to Default Program Segment Configuration See Program 3 illustrated on...

Страница 19: ...should be observed when handling the controller outside it s sleeve DIMENSIONS Bezel Behind Panel Overall Behind panel Width Height Width Height Length Length 51 0 51 0 44 8 44 8 116 2 106 7 Dimension...

Страница 20: ...EUTRAL conductors simultaneously A clear instruction shall be provided not to position the equipment so that it is difficult to operate the disconnecting device EMC Immunity EMC immunity may be improv...

Страница 21: ...X H X X RTD PT100 3 wire OUTPUT HARDWARE OPTIONS TERMINATIONS 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 SSd SSd SSd AnLG A...

Страница 22: ...ecification mV range 0 to 50mV Applicable to all inputs SM sensor maximum Calibration accuracy 0 25 SM 1 C Sampling frequency input 10Hz CJC 2 sec Common mode rejection Negligible effect up to 140dB 2...

Страница 23: ...CARLO GAVAZZI warrant this product free from defect in workmanship and materials for three 3 years from date of purchase 1 Should the unit malfunction return it to the factory If defective it will be...

Страница 24: ...ol It Current Monitors Panel Meters Phase Monitors Timers Transducers Voltage Monitors Distributed I O Dupline Field and Installation Bus Over a Twisted Pair Up to 6 Miles 10km Send It Sense It Capaci...

Отзывы: