33
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
428675
7002h
1
Force Refresh Signal
mode
UINT16
Enable or Disable the force
refresh signal
0000h: Disable
0001h: Enable
428676
7003h
1
Refresh Interval (s)
UINT16
Range: 0001h to 0258h
428677
7004h
1
Force Refresh Signal
(Heartbeat Signal)
UINT16
0001h: To send force
refresh signal. If force
refresh signal mode is
enabled, this register has to
be set to 1 within every
refresh interval otherwise
the RSGD unit will switch
OFF the output.
Delays
Read only mode (function 04h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
336865
9000h
1
Minimum Stop to Start
Delay (s)
UINT16
Stop to Start Delay [x1]
336866
9001h
1
Minimum Start to Start
Delay (s)
UINT16
Start to Start Delay [x1]
336867
9002h
1
Time from Last Stop (s)
UINT16
Time from Last Stop [x1]
336868
9003h
1
Time from Last Start (s)
UINT16
Time from Last Start [x1]
Write only mode (function 06h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
436865
9000h
1
Minimum Stop to Start
Delay (s)
UINT16
Range: 0000h to FFFFh [x1]
Protection Settings
Read only mode (function 04h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
340961
A000h
1
Supply Voltage
Unbalance Limit (%)
UINT16
Supply Voltage Unbalance
Limit [x10]
340962
A001h
1
Over Voltage Supply
Limit (%)
UINT16
Over Voltage Limit [x10]
340963
A002h
1
Under Voltage Supply
Limit (%)
UINT16
To read Under Voltage Limit
[x10]
340964
A003h
1
Load Current Unbalance
Limit (%)
UINT16
Load Current Unbalance
Limit [x10]
340965
A004h
1
I
MAX
Bypass (A
rms
)
UINT16
Maximum current in bypass
[x10]
340966
A005h
1
Phase Sequence alarm
mode
UINT16
Phase Sequence alarm
mode [x1]
0000h: Enable
0001h: Disable
340967
A006h
1
Motor Overload alarm
mode
UINT16
Motor Overload alarm mode
[x1]
0000h: Enable
0001h: Disable