32
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
No of
Flashes
Alarm Status
1
Internal fault
2
Wrong phase
sequence
3
Line voltage out
of range
4
Phase loss
(motor side)
5
Locked rotor
7
Over
temperature
8
Overload
9
Supply voltage
unbalance
10
Shorted SCR
320489
5008h
1
Alarm reset mode
UINT16
0000h: Auto alarm reset
0001h: Manual alarm reset
Device Status
Write only mode (function 06h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
420489
5008h
1
Alarm Reset Mode
UINT16
Set the alarm reset mode
0000h: Auto alarm reset
0001h: Manual alarm reset
420490
5009h
1
Soft Alarm Reset
UINT16
Reset the alarm:
0000h: No action
0001h: Reset alarm
Control
Read only mode (function 04h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
328673
7000h
1
Control Mode
UINT16
Control Mode [x1]
0000h: A1, A2 control mode
0001h: Modbus control mode
328674
7001h
1
Control Input Status -
Modbus
UINT16
Control Input Status [x1]
0000h: Switch OFF
0001h: Switch ON
328675
7002h
1
Force Refresh Signal
mode
UINT16
Force Refresh Signal mode
[x1]
0000h: Disable
0001h: Enable
328676
7003h
1
Refresh Interval (s)
UINT16
Refresh Interval [x1]
328677
7004h
1
Force Refresh Signal
(Heartbeat Signal)
UINT16
Refresh Signal [x1]
Write only mode (function 06h):
Modicon
Address
Physical
Address
Length
(words)
Description
Data
Format
Notes
[Scaling Factor]
428673
7000h
1
Set the Control Mode
UINT16
0000h: A1, A2 control mode
0001h: Modbus control mode
428674
7001h
1
Start/Stop Device
UINT16
0000h: Switch OFF
0001h: Switch ON