Installation
Provide sufficient air circulation space for cooling as shown in the examples below. Do not obstruct the RSBS vents.
5 cm
(1.97”)
5 cm
(1.97”)
Front view
5 cm
(1.97”)
5 cm
(1.97”)
Top view
R
Rc
L/L1
N/L2
ON
S
5 cm
(1.97”)
5 cm
(1.97”)
5 cm
(1.97”)
Number of flashes
Fully ON
Alarm
Critical over-temperature alarm
Alarm description
The RSBS will trigger this alarm if it measures an internal temperature >130ºC for ≥ 100
ms
Alarm recovery period
Alarm does not self-recover
Consecutive alarms for
hard reset
1
Action to recover alarm
This alarm is considered to be a critical condition and the RSBS will immediately switch
OFF its output. The alarm is non-resettable. Once this alarm is triggered the user needs
to replace the RSBS.
Troubleshooting
• Check that there is proper ventilation around RSBS.
• Replace the RSBS with a new one.