Note: Use 75ºC Copper (Cu) conductors

Connection Specifications

Main conductors (R, Rc, L /L1, N / L2, ON, S, Sc)

Flexible (solid or stranded)

0.5 – 16 mm

2

, AWG 20 - 6

Terminal screws

M4

Maximum tightening torque

1.19 Nm (10.5 lb-in)

Stripping length

8.0 mm

Auxiliary conductors (11, 12, 14)

Flexible (solid or stranded)

0.2 – 1.5 mm

2

, AWG 30 - 12

Terminal screws

M3

Maximum tightening torque

0.5 Nm (4.5 lb-in)

Stripping length

7.0 mm - 8.0 mm

 

Wiring diagram - RSBS..V23C..HP

L/L1

N/L2

K1

C

R

S

M1

~

Run 

cap

R

Rc

L/L1

N/L2

ON

S

Wiring diagram - RSBS..V23C00HP

L/L1

N/L2

K1

C

R

S

M1

~

Run 

cap

Start 

cap

R

Rc

L/L1

N/L2

ON

S

Sc

Wiring Diagrams

Note: Install a 15 kΩ (2W) resistor in parallel to the start capacitor in case of RSBS..C00HP.

Содержание RSBS Series

Страница 1: ...ht flicker RSBS reduces the compressor start current by 50 to reduce light flickering Description The RSBS V23C is a single phase soft starter for 1 phase compressors up to 32 Arms The RSBS can limit...

Страница 2: ...3C10HP 145 175 F RSBS2332A2V23C17HP External RSBS2332A2V23C00HP For proper model selection refer to our online soft starter selector tool http www gavazziautomation com nsc HQ EN soft_starters The int...

Страница 3: ...ose Component name code Notes External start capacitor kit STARTCAP 200UF SMA For RSBS2332A2V23C00HP models Selection guide Category Compressor maximum operating current IMAX Model selection Compresso...

Страница 4: ...ery between starts the RSBS will not respond to control voltage C Outputs R Connection to compressor main winding R Rc Connection to run capacitor L L1 Mains supply connection N L2 Supply neutral conn...

Страница 5: ...orithm During the ramp up sequence the RSBS will check if the motor is rotating If the RSBS finds that the motor is in locked rotor condition it will trigger the HP function after 250 ms See Fig 2 Dur...

Страница 6: ...avazzi Ltd RSBS RSBS DS ENG 27 05 20 Features Material PA66 Assembly DIN or panel Touch protection IP20 Weight Approx 450 g Overvoltage category II General data Fig 4 RSBS2332A2V23C HP Fig 3 RSBS2332A...

Страница 7: ...ickup voltage 90 VAC Drop out voltage 25 VAC Power supply Environmental Operating temperature RSBS2332A2V23C00HP 20 C to 65 C 4 F to 149 F RSBS2332A2V23C HP 20 C to 55 C 4 F to 131 F Storage temperatu...

Страница 8: ...gnetic compatibility EMC emissions Radio interference field emissions conducted CISPR 11 EN IEC 55011 Class B1 Harmonics IEC EN 61000 3 21 IEC EN 61000 3 121 Disturbance power CISPR 14 IEC EN 55014 11...

Страница 9: ...of output relay 1 Function of relay Alarm Rated operational voltage 250 VAC 30 VDC Rated insulation voltage 250 VAC Dielectric withstand voltage 2 5 kV Overvoltage category II Type of control circuit...

Страница 10: ...o IEC EN 60947 4 2 Terminal markings Marking R Connection to compressor main winding R Rc Connection to run capacitor L L1 Mains supply connection N L2 Supply neutral connection L2 connection for U S...

Страница 11: ...ing length 8 0 mm Auxiliary conductors 11 12 14 Flexible solid or stranded 0 2 1 5 mm2 AWG 30 12 Terminal screws M3 Maximum tightening torque 0 5 Nm 4 5 lb in Stripping length 7 0 mm 8 0 mm Wiring dia...

Страница 12: ...rm recovery ON OFF Flashing 11 14 Recovery time2 between starts ON ON OFF 11 12 Internal power supply fault Flashing OFF OFF 11 12 LED and Relay status indications 2 If supply on RSBS is removed befor...

Страница 13: ...after the recovery period Voltage dips interruptions during re covery between starts and or alarm recovery shall be ignored Troubleshooting Check for any loose connections on L L1 and N L2 terminals C...

Страница 14: ...paci tor This results in less starting torque and therefore the compressor might not start Alarm recovery period 5 minutes Consecutive alarms for hard reset 4 Action to recover alarm The alarm will se...

Страница 15: ...ery from alarm If during transition from alarm recovery to start of ramp up the measured current is 2 AAC 1 mains cycle the RSBS will re trigger the alarm The alarm will self recover after 5 minutes T...

Страница 16: ...temperature alarm Alarm description The RSBS will trigger this alarm if it measures an internal temperature 130 C for 100 ms Alarm recovery period Alarm does not self recover Consecutive alarms for h...

Страница 17: ...e than 5 000 symmetrical Amperes 240 Volts maximum when protected by fuses Tests at 5 000 A were performed with Class RK5 fuses please refer to the table below for maximum allowed Ampere rating of the...

Отзывы: