ENGLISH
24
S
1. The display shows for approx. 2 s. The display then shows
the current value stored in the memory.
Accept the value by pressing .
2. To select a new value for the hysteresis press and/or
until the desired value is displayed. Now press to accept this
value and pass on to the next parameter.
4.3.5.3 Time Delay
1. When entering this parameter (from 0 to 99 s) the display will show
for approx. 2 s. Then the display shows the current value
stored in the memory - the value is expressed in seconds.
To accept this value press .
2. If you wish to change the value, press and/or until the
required value is displayed.
Press to enter the value and pass on to the next selection.
4.3.5.4 High and Low Alarm
1. When you exit from the time delay programming the display shows
if a high alarm is the current status or if the low alarm is
the current status.
To continue with the current status, press and go on with the
next parameter.
2. To change the status, press or to switch the status.
Press to accept and pass on to the next parameter.
4.3.5.5 Alarm Relay Energized/De-energized
You can choose if the relay has to be energized or de-energized in the
absence of an alarm.
1. The display will show for a normally energized relay or it will
show for a normally de-energized relay.
Press to keep the current value.
S
S
▲
▼
S
▲
▼
S
S
▲
▼
S