Housing colours
Black (front red, optional green).
Module connection
Screw terminals.
7.1.2 Supply Specifications
Rated operational
230 VAC ± 10%, 50/60 Hz ± 5 Hz (5100520).
voltage
Also usable at line voltages of:
240 VAC +6/-15%, 220 VAC +15/-6%.
115 VAC ± 10%, 50/60 Hz ± 5 Hz (5100521).
Also usable at line voltages of:
120 VAC +6/-15%, 110 VAC +15/-6%.
48 VAC ± 10%, 50/60 Hz ± 5 Hz (5100522).
24 VAC ± 10%, 50/60 Hz ± 5 Hz (5100523).
12 to 48 VDC ± 15% (5100524).
Rated operational power 6 VA (12 to 48 VDC: 6 W).
7.1.3 Programming Specifications
Scaling
Electrical input range
Prog. within the whole measuring range.
Display range
Programmable within the whole scale.
Decimal point position Programmable
Alarm setpoints
Number of setpoints
0, 1 or 2
Setpoint adjustment
-1999 to 1999.
Hysteresis adjustment 1 - 1999.
Time delay adjustment 0 - 99 s.
Alarm type
High or low, programmable.
Relay status
“Normally energized” or “Normally de-ener-
gized relay coil, programmable.
Diagnostics
Overrange
EE
Underrange
-EE