ENGLISH
21
4.3 Programming
4.3.1 New Password
1. After you have entered the password the display shows .
After 2 s the stored value of the password is displayed. To retain
the present value, press to pass on to the next selection.
2. To modify the password, press and/or until the desired
value is displayed; this has to be a number between 0 and 199.
Press to pass on to the next parameter.
A password between 100 and 199 gives direct access to setpoint pro-
gramming in the following way: Enter programming mode and press ‘S’.
Then you will automatically jump directly to setpoint programming. After
the setpoint programming the programming mode is terminated.
4.3.2 Decimal Point Selection
Decimal point selection is relative to the displayed value.
1. After selection of the password the display will show for 2 s.
The current position of the decimal point is then indicated on the
display by a steady light as .
2. Change the position of the decimal point using (shift to left)
and/or (shift to right). Press to enter and pass on to next.
4.3.3 Electrical Input Range (HiE and LoE)
This feature allows you to define an electrical input range different from
the standard range. For example, for EDM with full-scale 20 mA (±19.99
mA), it is possible to select an electrical input range from 4.00 mA to
19.99 mA by proceeding as follows:
1. After programming the decimal point the display shows for 2
seconds signifying the maximum of the electrical input range.
The HiE value stored in the memory is shown on the display, for
example .
To retain the value shown, press to pass on to next parameter.
S
▲
▼
S
S
▼
▲