CAUTION
!
Measuring "High Voltage On" Time
The 9060 Power Supply records the amount of time the
high voltage is triggered on up to 99,999 hours. These
units are displayed in the kV and µA displays of the unit.
There are two registers that retain this information, one
that may be reset, the other that is permanently retained
in memory. The number of hours the unit's high voltage
has been on may be displayed by depressing at the same
time the preset 1 and reset buttons. The display will show
hours of use for 3 seconds. This is the re-settable register.
Figure 13: View of Applicator LED Display
Figure 14: Display In "High Voltage On" Time
To reset this register, press the reset button while the hours
are displayed. Pressing the preset 2 and reset buttons
at the same time will show the number of hours on the
non-re-settable register.
Local/Remote
The Vector product line is designed currently for applicators
only. The local/remote high voltage control switch should
be set to local for all Vector applicator applications.
Figure 15: High Voltage Control Switch
FAULT DESCRIPTIONS
For in depth troubleshooting information on the 9060, refer
to CP-XX-XX. When a fault occurs, the Fault Indicator on
the front of the control unit will light, a fault code will be
displayed on the microamp meter and the 6 LED’s at the
rear of the applicator will flash. Faults can be reset by
pressing the Reset button on the front of the control unit
or by pressing and holding the kV switch at the rear of the
applicator for 2-3 seconds.
The unit will not function if it is in remote mode
without external inputs.
AH-06-01-R17 (08/2019)
34 / 79
www.carlisleft.com
OPERATION
EN