Startup & Operation 

(continued)

  Burner ON 

After the self-test, amber LED turns off. The ignitor starts, followed 2 seconds later by the motor.

  

Pump 

To enter pump prime: 1. Start a CFH cycle. During Pre-Ignition, press Reset until motor turns   

 

  

Prime  

 off (10 seconds), then release the button. When motor turns back on, within 5 seconds, press the Reset button 

until the amber LED starts to flash. You are in Pump Prime, release Reset button.

    

 Optional Pump Prime notes: 1) If lost, press Reset for 1 second and release, then if the control is not in 

Pump Prime, restart the sequence.  2) If Reset is released before end of first 10 seconds, the control re-

turns to Standby and restarts another CFH cycle.  3) If reset is not pressed the second time, a normal CFH 

cycle will continue.  4) If motor and igniter are on and amber LED is flashing, the control is in Pump Prime.  

5) Pump Prime will exit standby if flame is detected, or 60 seconds has elapsed, or loss of TT or Limit, or 

Reset button is pressed.

  TFI 

 The CAD cell must sense flame within the TFI time limit (trial for ignition). After CAD cell senses flame, the 

ignitor stays on another 10 seconds (flame stabilization period).

  Run 

 The burner continues firing during call for heat if the CAD cell is sensing flame. Only the green LED is on 

during normal running.

  Lockout 

 If CAD cell does not sense flame within the TFI time limit after the burner starts, 

lockout occurs. The con-

trol turns the red LED on constant and closes the alarm contact.

  

To Reset 

Push in and hold reset button for 1 second, then release. 

 

Latch-up 

 If the control locks out 3 times during a single call for heat, latch-up occurs. The control turns on both the 

amber and red LEDs constant. You must use the special procedure below to reset the control after latch-

up.

  

  

Reset after latch-up: only a qualified service technician should attempt to reset the control after latch-up.

The problem that caused the repeated burner lockouts must be corrected before returning the burner to 

normal operation.

   

Push in and hold the reset button for 10 seconds. The amber LED will begin to flash.

   

 After the LED begins flashing, continue holding the reset button for 20 seconds. The LEDs will turn off.  

Release the reset button and the control will restart (releasing the button before the LEDs turn off will 

cause the control to remain in latch-up).

  

 

The 50200 control will not reset from lockout or latch-up if power is interrupted.

 

Flame 

If the CAD cell loses flame signal during operation (after the TFI), the red LED flashes. The burner shuts off  

  

Failure  

 within 2 seconds. 

 Recycle: Control waits for 65 seconds (with red LED flashing), then begins again at Self-test 2. Red LED 

goes off.

 

 

If the green LED is blinking during a run, the flame is weak or unstable and may go into recycle.

 

End cycle 

 Set thermostat (or aquastat) to stop call for heat. The burner shuts off within 2 seconds after end of call for 

heat.

 

Stand-by 

 Control remains in stand-by mode until limit circuit sends power to the black wire and thermostat circuit 

closes (call for heat).

© Copyright 2015 - Carlin Combustion Technology, Inc.  

MN50200  022415

Содержание 50200

Страница 1: ...th applicable codes and ordinances 2 Thermostat terminals T T provide a current source Never apply external power to these terminals under any circumstances 3 Alarm terminals provide a 24 VAC VDC rated dry contact suitable for use with security fire alarm systems Mounting The control may be mounted on a 4 x 4 junction box in any convenient location on the burner furnace or wall The location must n...

Страница 2: ...is successful amber LED turns off and control waits for thermostat circuit to close and a limit input Call for Set thermostat to call for heat Thermostat circuit must be closed and black wire must receive heat power from the limit circuit Self test 2 If a failure occurs in this self check the control won t start and the amber LED blinks 1 second on 4 sec onds off until serviced or the problem clea...

Страница 3: ...d closes the alarm contact To Reset Push in and hold reset button for 1 second then release Latch up If the control locks out 3 times during a single call for heat latch up occurs The control turns on both the amber and red LEDs constant You must use the special procedure below to reset the control after latch up Reset after latch up only a qualified service technician should attempt to reset the ...

Страница 4: ...sing Check for stray light by measuring the CAD cell resistance looking into the inactive combustion chamber It should read at least 50 kohms Repeated flame failures flashing red LED Check for CAD cell is defective Replace Air leaking into oil line causing flame out Check oil line connections and filter gasket Defective nozzle causing flame to be erratic Change nozzle Excessive airflow or draft ca...

Отзывы: