background image

Wiring

Startup & Operation  

 Do not start the burner if the combustion chamber  

contains oil or oil vapor.

 

 Per UL requirements, the control will not turn on if the  

CAD cell senses flame during the self-test. If the CAD cell sees light (flame) at the beginning of a cycle, the control will remain in 

self-test mode until the CAD cell no longer senses light (flame). The amber LED will blink momentarily   every 3 to 4 seconds and 

green LED will be on or flashing.

  Power ON 

 Open all manual oil line valves. Close the line switch. (If Red LED turn on constant  , control is in lockout. 

See below to reset.)

 

Self-test 1 

 The control performs a “boot-up” test to verify internal operation each time power is applied to the black 

wire. The amber LED turns on and the test continues for about 5 seconds. If the test fails, the control turns 

the amber LED off and repeats this test sequence until successful.

 

Stand-by 

 (Thermostat circuit open and/or limit circuit open) If Self-test 1 is successful, amber LED turns off and 

control waits for thermostat circuit to close and a limit input.

  

Call for 

Set thermostat to call for heat. Thermostat circuit must be closed and black wire must receive  

 

  

heat  

power from the limit circuit.

  Self-test 2 

 If a failure occurs in this self-check, the control won’t start and the amber LED blinks 1 second on, 4 sec-

onds off, until serviced or the problem clears. These failures include CAD cell seeing light, internal failure, 

or line voltage <90V. See service section.

© Copyright 2015 - Carlin Combustion Technology, Inc.  

MN50200  022415

Bundled Neutrals Can Be Attached to Any L2 T

erminal

Latch-Up:

 

Pr

events excessive r

esets by locking out after 3 

consecutive r

esets during any one call for heat. 

To

 r

eset fr

om Latch-Up:

1. Depr

ess and hold the r

ed button. Amber light will 

blink after 10 seconds, r

ed light will stay on solid. 

2. After amber light stops blinking (appr

oximately 

20 seconds), 

re

lease r

ed button.

Releasing red button during step 1 and 2 will result 

in the control returning to latch-up

Model 50200 Diagnostic LEDs

 – Amber OFF 

 – Amber ON 

 – Amber FLASHING

 – Green OFF 

 – Green ON 

 – Green FLASHING

 – Red OFF 

 – Red ON 

 – Red FLASHING

Содержание 50200

Страница 1: ...th applicable codes and ordinances 2 Thermostat terminals T T provide a current source Never apply external power to these terminals under any circumstances 3 Alarm terminals provide a 24 VAC VDC rated dry contact suitable for use with security fire alarm systems Mounting The control may be mounted on a 4 x 4 junction box in any convenient location on the burner furnace or wall The location must n...

Страница 2: ...is successful amber LED turns off and control waits for thermostat circuit to close and a limit input Call for Set thermostat to call for heat Thermostat circuit must be closed and black wire must receive heat power from the limit circuit Self test 2 If a failure occurs in this self check the control won t start and the amber LED blinks 1 second on 4 sec onds off until serviced or the problem clea...

Страница 3: ...d closes the alarm contact To Reset Push in and hold reset button for 1 second then release Latch up If the control locks out 3 times during a single call for heat latch up occurs The control turns on both the amber and red LEDs constant You must use the special procedure below to reset the control after latch up Reset after latch up only a qualified service technician should attempt to reset the ...

Страница 4: ...sing Check for stray light by measuring the CAD cell resistance looking into the inactive combustion chamber It should read at least 50 kohms Repeated flame failures flashing red LED Check for CAD cell is defective Replace Air leaking into oil line causing flame out Check oil line connections and filter gasket Defective nozzle causing flame to be erratic Change nozzle Excessive airflow or draft ca...

Отзывы: