μC
2
SE - +030220426 - rel. 2.1 - 09.06.2010
1. INTRODUCTION
1.1 General description
The μC
2
SE is a new compact CAREL electronic controller, the same size as a normal thermostat, for
the complete management of chillers and heat pumps: it can control air-air, air-water, water-water
and condensing units.
1.1.1 Main functions
• control of the water inlet and evaporator outlet temperature;
• defrost management by time and/or by temperature or pressure;
• fan speed control;
• complete alarm management;
• connection to serial line for supervision/telemaintenance;
• elimination of the expansion vessel.
- Driver function
• Management of electronic expansion valves.
1.1.2 Controlled devices
•
compressor;
• condenser
fans;
• reversing
valve;
• water pumps for evaporator and/or condenser, and outlet fan (air-air);
• antifreeze
heater;
• alarm signal device.
1.1.3 Programming
CAREL off ers the possibility to confi gure all the unit parameters not only from the keypad on the
front panel, but also using:
• a hardware key;
• a serial line.
1.2 User interface
1.2.1 Display
The display features 3 digits, with the display of the decimal point between -99.9 and 99.9.
Outside of this range of measurement, the value is automatically displayed without the decimal
(even if internally the unit still operates considering the decimal part).
In normal operation, the value displayed corresponds to the temperature read by probe B1, that
is, the evaporator water inlet temperature (for water chillers) or the ambient air temperature for
direct expansion units.
Fig. 1.a show the symbols present on the display and on the keypad and their meanings.
1.2.2 Symbols on the display
Display with 3 green digits (plus sign and decimal point), amber symbols and red alarm symbols.
symbol
colour
meaning
reference
refrigerant
circuit
with LED ON
with LED fl ashing
1; 2
amber
compressor 1 and/or 2 ON
start up request
1
1; 3
amber
compressor 1 and/or 3 ON
start up request
2
A
amber
at least one compressor ON
1/2
B
amber
pump/air outlet fan ON
start up request
1/2
C
amber
condenser fan ON
1/2
D
amber
defrost active
defrost request
1/2
E
amber
heater ON
1/2
F
red
alarm active
1/2
G
amber
heat pump mode (P6=0)
heat pump mode request
(P6=0)
1/2
H
amber
chiller mode (P6=0)
chiller mode request
(P6=0)
1/2
Table 1.a
Fig. 1.a
Содержание uC2SE
Страница 1: ...C2 SE electronic control User manual...
Страница 2: ......
Страница 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 75: ......