6. TABLE OF ALARMS
Key to the table of alarms:
*:
if the probe is set for the compensation function, in the event of probe faults, the unit continues to operate.
ON*:
if the expansion card is not present.
EVD 1= EVD400 connected to μC
2
SE (1st circ.)
EVD 2= EVD400 connected to the expansion (2nd circ.)
alarm
display
alarm type
resetting
Compressor
pump
fan
heater Valve alarm warning superv.
variable
superv. variab.
description
variab.
type
HP1
High pressure
Depends on P05 OFF C1-2
-
ON(60”)
-
-
ON
-
41 (R)
Circuit 1 alarm
Digital
HP2
High pressure
Depends on P05 OFF C3-4
-
ON(60”)
-
-
ON
-
42 (R)
Circuit 2 alarm
Digital
LP1
Low pressure
Depends on P05 OFF C1-2
-
OFF 1
-
-
ON
-
41 (R)
Circuit 1 alarm
Digital
LP2
Low pressure
Depends on P05 OFF C3-4
-
OFF 2
-
-
ON
-
42 (R)
Circuit 2 alarm
Digital
PL1
Capacity-control for low pressure
circuit 1
Automatic
OFF C2
-
-
-
-
-
ON
-
Signal on display
-
PL2
Capacity-control for low pressure
circuit 2
Automatic
OFF C4
-
-
-
-
-
ON
-
Signal on display
-
TP
General overload
Depends on P08 OFF
OFF
OFF
-
-
ON
-
45 (R)
General warning
Digital
tC1
Circuit 1 overload
Depends on P08 OFF C1-2
-
OFF 1
-
-
ON
-
41 (R)
Circuit 1 alarm
Digital
tC2
Circuit 2 overload
Depends on P08 OFF C3-4
-
OFF 2
-
-
ON
-
42 (R)
Circuit 2 alarm
Digital
LA
advice
Depends on P08 -
-
-
-
-
ON*
ON
50 (R)
General advice
Digital
FL
Flow controller alarm
Depends on P08 OFF
OFF
OFF
-
-
ON
-
45 (R)
General alarm
Digital
FLb
Backup pump warning
Automatic
-
-
-
-
-
-
ON
50 (R)
General advice
Digital
E1
Probe B1 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E2
Probe B2 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E3*
Probe B3 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E4*
Probe B4 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E5
Probe B5 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E6
Probe B6 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E7*
Probe B7 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
E8*
Probe B8 alarm
Automatic
OFF
OFF
OFF
OFF
-
ON
-
46 (R)
Probe alarm
Digital
Hc1-4
Hour warning C1-4
Automatic
-
-
-
-
-
-
ON
47 (R)
Compressor
advice
Digital
EPr
EEPROM error during operation
Automatic
-
-
-
-
-
-
ON
50 (R)
General advice
Digital
EPb
EEPROM error at the start-up
Automatic
OFF
OFF
OFF
OFF
OFF
OFF
OFF
45 (R)
General alarm
Digital
ESP
Expansion Error
Automatic
OFF
OFF
OFF
OFF
OFF
ON
-
45 (R)
General alarm
Digital
EL1-2
Zero cross
Automatic
-
-
100%
-
-
ON*
ON
52 (R)
Fan advice
Digital
dF1-2
Defrosting error
Automatic
-
-
-
-
-
-
ON
50 (R)
General warning
Digital
d1-2
Defrost on circuit in question
-
-
-
-
-
-
-
-
-
Signal on display
-
Fd
Dirty fi lter warning
Automatic
-
-
-
-
-
-
-ON
-
Signal on display
-
A1
Frost alarm circ. 1
Depends on P05 OFF C1-2
-
OFF 1
-
-
ON
-
41 (R)
Circuit 1 alarm
Digital
A2
Frost alarm circ. 2
Depends on P05 OFF C3-4
-
OFF 2
-
-
ON
-
42 (R)
Circuit 2 alarm
Digital
Ht
High temperature
Automatic
-
-
-
-
-
ON*
ON
51 (R)
Temperature
advice
Digital
Lt
Low ambient temp.
Depends on P05 -
-
-
-
-
ON*
ON
51 (R)
Temperature
advice
Digital
AHt
High temperature at the start-up
Automatic
OFF
-
OFF
OFF
-
-
ON
50 (R)
General warning
Digital
ALt
Low temperature at the start-up
Automatic
OFF
-
OFF
OFF
-
-
ON
50 (R)
General warning
Digital
ELS
Low supply voltage
Automatic
-
-
-
-
-
-
ON
50 (R)
General warning
Digital
EHS
High supply voltage
Automatic
OFF
OFF
OFF
OFF
OFF
OFF
OFF
45 (R)
General alarm
Digital
tEr
Terminal communication error
Automatic
OFF
OFF
OFF
OFF
OFF
ON
-
-
Signal on display
-
Ed1
EVD 1 tLAN error
Automatic
OFF C1-2
-
OFF
-
-
ON
-
43 (R)
EVD 1 warning
Digital
Ed2
EVD 2 tLAN error
Automatic
OFF C3-4
-
OFF
-
-
ON
-
44 (R)
EVD 2 warning
Digital
SH1
EVD 1 superheat alarm
-
OFF C1-2
-
OFF-
-
-
ON
-
43 (R)
EVD 1 warning
Digital
SH2
EVD 2 superheat alarm
-
OFF C3-4
-
OFF-
-
-
ON
-
44 (R)
EVD 2 warning
Digital
nO1
MOP 1 warning
Automatic
-
-
-
-
-
-
ON
48 (R)
EVD 1 advice
Digital
nO2
MOP 2 warning
Automatic
-
-
-
-
-
-
ON
49 (R)
EVD 2 advice
Digital
LO1
LOP 1 warning
Automatic
-
-
-
-
-
-
ON
48 (R)
EVD 1 advice
Digital
LO2
LOP 1 warning
Automatic
-
-
-
-
-
-
ON
49 (R)
EVD 2 advice
Digital
HA1
High inlet temperature warning
circ.1
Automatic
-
-
-
-
-
-
ON
48 (R)
EVD 1 advice
Digital
HA2
High inlet temperature warning
circ. 2
Automatic
-
-
-
-
-
-
ON
49 (R)
EVD 2 advice
Digital
EP1
EVD 1 Eeprom error
Automatic
OFF C1-2
-
OFF-
-
-
ON
-
43 (R)
EVD 1 warning
Digital
EP2
EVD 2 Eeprom error
Automatic
OFF C3-4
-
OFF-
-
-
ON
-
44 (R)
EVD 2 warning
Digital
ES1
EVD 1 probe error
Automatic
OFF C1-2
-
OFF-
-
-
ON
-
43 (R)
EVD 1 warning
Digital
ES2
EVD 2 probe error
Automatic
OFF C3-4
-
OFF-
-
-
ON
-
44 (R)
EVD 2 warning
Digital
EU1
Open valve EVD 1 error at the
start-up
Automatic
OFF C1-2
-
OFF
-
-
ON
-
43 (R)
EVD 1 warning
Digital
EU2
Open valve EVD 2 error at the
start-up
Automatic
OFF C3-4
-
OFF
-
-
ON
-
44 (R)
EVD 2 warning
Digital
Eb1
EVD 1 battery alarm
Automatic
OFF C1-2
-
OFF
-
-
ON
-
43 (R)
EVD 1 warning
Digital
Eb2
EVD 2 battery alarm
Automatic
OFF C3-4
-
OFF
-
-
ON
-
44 (R)
EVD 2 warning
Digital
L
Low load warning
Automatic
-
-
-
-
-
-
-
-
Signal on display
-
Ed1
tLan EVD 1 communication error
Automatic
OFF C1-2
-
OFF
-
-
ON
-
43 (R)
EVD 1 warning
Digital
Ed2
tLan EVD 2 communication error
Automatic
OFF C3-4
-
OFF
-
-
ON
-
44 (R)
EVD 2 warning
Digital
PH1
Low pressure circ. 1 warning
-
-
-
-
-
-
-
-
-
Signal on display
-
PH2
Low pressure circ. 2 warning
-
-
-
-
-
-
-
-
-
Signal on display
SUL
Low outlet temperature warning
-
-
-
-
-
-
-
-
-
Signal on display
CP1
compressor 1 alarm
Automatic
OFF C1
-
-
-
-
ON
-
25 (R)
Compr. error alarm Digital
CP2
compressor 2 alarm
Automatic
OFF C2
-
-
-
-
ON
-
25 (R)
Compr. error alarm Digital
CP3
compressor 3 alarm
Automatic
OFF C3
-
-
-
-
ON
-
25 (R)
Compr. error alarm Digital
CP4
compressor 4 alarm
Automatic
OFF C4
-
-
-
-
ON
-
25 (R)
Compr. error alarm Digital
Table 6.a
Note:
The warning relay diff ers from the alarm relay as it is only activated for warnings, that is, signals only, which
have no direct eff ect on the operation of the unit, and the display does not show the alarm symbol (bell).
Compressor
N.B.
The alarm relating to the circuit with the fault must not interact with the operation of the other circuit, as
long as the condenser is not shared in common.
Содержание uC2SE
Страница 1: ...C2 SE electronic control User manual...
Страница 2: ......
Страница 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 75: ......