46
ENGLISH
μC
2
SE - +030220426 - rel. 2.1 - 09.06.2010
H11= 12:
associated device
outputs
H11=0
H11= 1
H11= 2
H11= 3
H11= 4
H11= 5
C1
compressor 1
compressor 1
compressor 1
compressor 1
compressor 1
compressor 1
C2
heater 1
heater 1
heater 1
reversing valve 1
reversing valve 1
heater 1
C3
Pump/evaporator (fan) (on
air/air units)
Pump/evaporator (fan) (on
air/air units)
Pump/evaporator (fan) (on
air/air units)
Pump/evaporator (fan) (on
air/air units)
evaporator pump
Pump/evaporator (fan) (on
air/air units)
C4
reversing valve 1
Compressor 2 (or capacity
control comp. 1)
Compressor 2 (or capacity
control comp. 1)
Compressor 2 (or capacity
control comp. 1)
Compressor 2 (or capacity
control comp. 1)
condenser fan 1
C5
alarm
alarm
reversing valve 1
alarm
alarm
alarm
C6
compressor 2
compressor 3
compressor 3
compressor 3
not used
compressor 2
C7
heater 2
heater 2
heater 2
reversing valve 2
heater 1
heater 2
C8
Condenser pump/backup
Condenser pump/backup
Condenser pump/backup
Condenser pump/backup
Condenser pump/backup
Condenser pump/backup
C9
reversing valve 2
Compressor 4 (or capacity
control comp. 2)
Compressor 4 (or capacity
control comp. 2)
Compressor 4 (or capacity
control comp. 2)
not used
condenser fan 2
C10
Warning
Warning
reversing valve 2
Warning
Warning
Warning
associated device
outputs
H11= 6
H11= 7
H11= 8
H11= 9
H11= 10
H11= 11
H11= 12
C1
compressor 1
compressor 1
compressor 1
compressor 1
compressor 1
compressor 1
compressor 1
C2
1 step heater
1 step heater
1 step heater
compressor 2
compressor 2
compressor 2
P25
C3
outlet fan
outlet fan
outlet fan
outlet fan
outlet fan
outlet fan
P26
C4
reversing valve 1
2 step heater
condenser fan 1
reversing valve 1
heating step 1
heating step 1
P27
C5
alarm
alarm
alarm
alarm
alarm
alarm
P28
C6
compressor 3
compressor 3
compressor 3
compressor 3
compressor 3
compressor 3
compressore 3
C7
2 step heater
P29
2 step heater
compressor 4
P29
C8
open freecooling/
freeheating
open freecooling
open freecooling
open freecooling/
freeheating
open freecooling/
freeheating
open freecooling/
freeheating
P30
C9
reversing valve 2
humidifi er
(ON/OFF)
condenser fan 2
1 step heater
heating step 2
humidifi er
P31
C10
close freecooling/
freeheating
close freecooling
close freecooling
close freecooling/
freeheating
close freecooling/
freeheating
close freecooling/
freeheating
P32
Parameters P25 to P32 can have the following meanings:
0 = no function associated with the relay
1 = compressor 2
2 = Heater 1
3 = Reversing valve 1
4 = Pump/inside fan
5 = Open freecooling/freeheating
6 = Close freecooling/freeheating
7 = Humidifi er
8 = Condenser fan 1 on/off
9 = Heater 2
10 = Alarm
11 = Boiler contact
12 = compressor 4
13 = Reversing valve 2
14 = Pump/inside fan 2nd evaporator
15 = Condenser fan 2 on/off
16 = Warning
17 = Condenser pump/Backup
Содержание uC2SE
Страница 1: ...C2 SE electronic control User manual...
Страница 2: ......
Страница 4: ...4 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 6: ...6 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 72: ...72 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 73: ...73 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 74: ...74 E N G L I S H C2 SE 030220426 rel 2 1 09 06 2010...
Страница 75: ......