Setting the pLAN address

Procedure:

1. 

Press button A for 5 seconds; the pLAN address starts fl ashing.

2. 

Press repeatedly or hold the button until reaching the desired 
address (e.g. 7), then remove the screwdriver.

3. 

Wait until the address starts fl ashing quickly. The address is now 
saved but is not yet active for the application program.

4. 

Power off  the controller.

5. 

Power on the controller. The address is now active.

G

G0

U1

u2

U3

GND

+VDC

+V

term

GND

+5 V

REF

U4

GND

U5

GND

VG

VG0

Y1

Y2

Y3

Y4

ID

1

J1

J24

J2

J3

J4

F i e l d B u s   c a r d

B M S   c a rd

Fig. 6.d

2. Setting the address using an external terminal

The controller is assigned a private (Pr=private) or shared (Sh=shared) 
terminal with address 32. The external terminal can be given an address 
from 0 to 32. Addresses between 1 and 32 are used by the pLAN protocol, 
while address 0 identifi es the Local Terminal protocol, used for point-to-
point connections and to confi gure the controller (this can be done with 
a single pGD terminal and a single pCO).
If the controller with default setting (address=1) is connected to an 
external terminal (address=32), communication is established and the 
external terminal replicates the display on the built-in terminal, if featured. 
If however the controller has a diff erent address (e.g. 7) and the terminal 
is not set to communicate with the controller at this address, once the 
connection is established the terminal will display a blank screen.
In this case, proceed as follows.

Procedure:

1. 

Press the UP, DOWN and Enter buttons together to go to the screen 
for setting the terminal address.

Display address
setting......................................:02

I/O Board address.................:07

Fig. 6.e

2. 

Set the display’s address to 0 to set the point-to-point connection. 
Press Enter to confi rm.

Display address
setting..........:00

Fig. 6.f

3. 

Power off  the controller.

C1

NO1

NO2

NO3

C1

C4

NO4

NO5

NO6

C4

C7

NO7

C7

NO8

C8

NC8

G

G0

U1

u2

U3

GND

+VDC

+V

term

GND

+5 V

REF

U4

GND

U5

GND

VG

VG0

Y1

Y2

Y3

Y4

ID

1

ID

2

ID

3

ID

4

ID

5

ID

6

ID

7

ID

8

IDC1

J1

J24

J2

J3

J4

J5

J14

J10

J13

J12

J15

FieldBus card

B M S card

J11 pLAN

J25 BMS2

J26 FBus2

4

3

2

1

Fig. 6.g

4. 

Power on the controller while pressing the Alarm and Up buttons 
together until the following screen appears.

#######################

        selftest
     please wait...

#######################

Fig. 6.h

5. 

Using the UP and DOWN buttons, set the controller’s pLAN address 
to 7 and press Enter to confi rm.

pLAN address: 7
UP:     increase
DOWN:   decrease
ENTER:  save & exit

Fig. 6.i

6.4  Setting the terminal’s address and 

connecting the controller to the 
terminal

After setting the controller’s network address (see previous paragraph), to 
establish connections between the controller and the terminal you need 
to set the terminal’s address.

Procedure:

1. 

Press the UP, DOWN and Enter buttons together. The screen for 
setting the terminal’s address is displayed. Set the address to 2 and 
press Enter to confi rm.

Display address
setting..........:02

Fig. 6.j

2. 

Press the UP, DOWN and Enter buttons together. Press Enter twice and set 
the controller’s address: 7. Press Enter to confi rm.

Display address
setting...........:02

I/O Board address:07

Fig. 6.k

Содержание pCO5+

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s pCO5 NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Programmable Controller User manual...

Страница 2: ......

Страница 3: ...corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those speci ed in the technical manual All of the above suggestions likewi...

Страница 4: ...4 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 5: ...12 pCO5 terminals description 24 5 INPUT OUTPUT CONNECTIONS 26 5 1 Power supply 26 5 2 Universal inputs outputs 26 5 3 Digital inputs 29 5 4 Optically isolated analogue outputs 31 5 5 Connecting the...

Страница 6: ...6 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 7: ...ding software and commissioning fast upload download of controller software using a Smart Key or any pendrive provided the controller is equipped with the relative port universal inputs outputs con gu...

Страница 8: ...RS485 Sch interfaccia Ethernet BACnet Servocontrollo della serranda BELIMO Valvola di servocontrollo MP BUS Scheda MP BUS 5 8 4 S R s u t a t s GNX RS485 P1 P2 P3 B A Cnet MS TP FieldBus 1 BMS 1 J1 J2...

Страница 9: ...s terminal panel installation This model can be installed on the panel Its graphics properties are identical to those of the PGDE000 terminal Accessories for installation telephone connection cable co...

Страница 10: ...ntroller consequently acts as a MASTER i e supervisor therefore other con trollers or devices can be connected as SLAVES Up to 64 devices can be connected PCO100TLN0 tech lea et Code 050003270 tLAN an...

Страница 11: ...er e g pCO5 Small EVD Evolu tion external Ultracap module pCOE tech lea et code 050003265 Expansion card Increases the number of inputs outputs on the controller A maximum of 5 expan sion cards can be...

Страница 12: ...White press together with DOWN and ENTER to change the terminal s address only for PGDE terminal see par 6 4 press to increase value Enter White press to con rm value DOWN White press together with UP...

Страница 13: ...NO16 NO17 NO18 C16 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 ONLY FOR LARGE AND EXTRALARGE MODELS Fig 3 a S...

Страница 14: ...s2 J11 pLAN pCO5 SLAVE SLAVE Fig 3 d pLAN network J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 MASTER SLAVE MASTER SLAVE MASTER SLAVE Fig 3 e Impo...

Страница 15: ...ange of operation see Technical Speci cations large rapid uctuations in room temperature strong magnetic and or radio frequency interference avoid installing near transmitting antennas strong vibratio...

Страница 16: ...ompliance with national and local regulations All the very low voltage connections 24 Vac Vdc or 28 to 36 Vdc analogue and digital inputs analogue outputs serial bus connections power supplies must ha...

Страница 17: ...nel Terminating resistors are not required L 100m 230 Vac 24 Vac L N J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 Fig 4 c The proce...

Страница 18: ...ion slip the connector into terminal J10 until it clicks To remove the connector press lightly on the plastic catch on the connector and slip it out Graphic L 50 m cavo telefonico telephone cable J10...

Страница 19: ...onnected to a pCO controller which is itself connected to other controllers in a pLAN network the terminal is directly powered by the controller Be sure to avoid the terminal being powered by two powe...

Страница 20: ...ed PWM output 5 8 10 8 8 U Out Universal I O Analogue output max tot 5 max tot 8 max tot 10 max tot 8 max tot 8 Digital inputs Optically isolated 24 Vac Vdc input 8 12 14 12 12 ID In Digital input 4 I...

Страница 21: ...J8 J1 4 J10 J1 3 J1 2 J16 J1 7 J18 J15 J6 FieldBus card BMS card J11 pLAN J2 5BMS2 J2 6FBus2 4 3 2 1 4 5 1 6 2 3 3 3 8 9 7 8 10 13 14 11 12 15 18 16 17 Fig 4 r Ref Description Ref Description 1 POWER...

Страница 22: ...U7 U8 GND ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14 ID14H J1 J24 J2 J3 J4 J5 J7 J8 J14 J10 J13 J12 J16 J17 J18 J15 J6 FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 4 5 1 6...

Страница 23: ...nnector 6 VG voltage A to optically isolated analogue output VG0 power to optically isolated analogue output 0 Vac Vdc 18 Fieldbus BMS selector microswitch 7 Analogue outputs 20 Electronic valve A con...

Страница 24: ...N RS485 port J11 2 Tx Rx Tx Rx pLAN RS485 port J11 3 GND GND pLAN RS485 port 12 Reserved 13 Reserved 14 Reserved Ref Term Label Description 15 J12 1 C1 Common for relays 1 2 3 J12 2 NO1 Normally open...

Страница 25: ...connection J28 2 3 J28 3 2 J28 4 4 22 J30 1 VBAT Power from external Ultracap module J30 2 G0 J30 3 G 23 J29 1 GND Common for power supply to probes J29 2 VREF Power to driver probes J29 3 S1 Probe 1...

Страница 26: ...o handle their respective signals from the application program the universal inputs outputs cannot be used as digital outputs Max number of connectable analogue inputs The maximum number of analogue i...

Страница 27: ...nical Speci cations table The probe has three wires connect one to GND and the other two to two separate but adjacent universal inputs on the same controller e g U1 U2 GND or U4 U5 GND G G0 U1 U2 U3 G...

Страница 28: ...scription Wire colour 5 VREF Power Black GND Power reference Green U1 Signal White Connecting active probes with 0 to 10 V output For information on the maximum number of probes that can be connected...

Страница 29: ...ty devices alarms device status indicators and remote switches These inputs are all optically isolated from the other terminals They can work at 24 Vac 10 15 or at 28 to 36 Vdc 20 10 indicated with ID...

Страница 30: ...6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 24Vac Fig 5 n 24 Vdc digital inputs The ID digital inputs can be controlled at 24 Vdc Example of connection diagram LARGE model G G0 U1 U2 U3 GN...

Страница 31: ...D14H J1 J24 J2 J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 230Vac L N Fig 5 q Example 2 Connection diagram with digital inputs at...

Страница 32: ...C13 ID14 ID14H J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND eldBus card BMS card 24Vac 28 36 Vdc 0 V ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 ID9 ID10 ID11 ID...

Страница 33: ...2 serial port J26 is however electrically isolated from the driver s serial line this ensures that in case of external faults on the line connected to FBus2 the internal driver can keep on working ind...

Страница 34: ...dconsecutively at very close intervals e g star delta motor starter in the order of hundreds of ms use relays belonging to the same group according to the following table RELAY GROUPS FOR CONSECUTIVE...

Страница 35: ...G0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 out H M NTC NTC G digitalinput9 CP digitalinput10 digitalinput11 digitalinput12 digital input 13 digital input 14 digital output 9 digital output 10...

Страница 36: ...Each pCO constantly updates the displays on the private terminals while the shared terminals if present are updated only by the pCO that is controlling the terminal at that time The gure below illust...

Страница 37: ...hed the terminal will display a blank screen In this case proceed as follows Procedure 1 Press the UP DOWN and Enter buttons together to go to the screen for setting the terminal address Display addre...

Страница 38: ...CO Manager program and a serial converter with RS485 output to connect to the pCO pCO Manager is part of the 1Tool program suite it can also be installed by itself and can be obtained free of charge a...

Страница 39: ...the controller immediately executes Autorun and upon con rmation from the terminal performs the operations contained in the le Upload and Download UPLOAD can be performed in three di erent ways 1 manu...

Страница 40: ...the clock E is displayed as follows Select a memory to view its status T M E M O R Y S T A T U S P M E M O R Y S T A T U S E M E M O R Y S T A T U S 4 FLASH USB MEMORY Selecting this string displays t...

Страница 41: ...llegamento sonde seriali DP 4 th Tune AT PCO100FD10 scheda seriale FieldBus PGD Touch EEV PGD1 Power PSD0 PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS4...

Страница 42: ...vi terze parti FAN PUMP INVERTER PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS485 PCO10W0WB0 pCOWeb sch interfaccia Ethernet BACnet 5 8 4 S R s u t a t...

Страница 43: ...43 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 44: ...EVD200 x EVD Evolution x x CAREL slave devices tLAN x CAREL slave devices 485 x x x x x pCOexp 485 x x x x x pCOexp tLAN x Chiller2 expansion x Hydronic fan coil and CANbus x x PlantVisorPRO local x x...

Страница 45: ...serial port protocols PSTN GSM Modbus Slave and CAREL Slave cannot be used on BMS serial port Modbus slave extended with pCOweb Modbus slave extended only for pCOWEB serial card with FW version 1 4 Mo...

Страница 46: ...C 1Y in SSR versions Type of disconnection or microswitching microswitching Category of resistance to heat and re Category D UL94 V2 Ageing characteristics operating hours 80 000 No of automatic opera...

Страница 47: ...kHz asynchronous 100 Hz asynchronous 5 8 10 Power supply for probes and terminals Vdc Active probes can be powered by the 24 21 Vdc 10 P 5 P 3 available on terminal VDC J2 The max available current i...

Страница 48: ...tion of groups Model 1 2 3 4 5 6 7 8 9 10 11 SMALL 1 3 4 6 7 8 Type of relay Type A Type A Type A Type A MEDIUM BUILT IN DRIVER 1 3 4 6 7 8 9 11 12 13 Type of relay Type A Type A Type A Type A Type A...

Страница 49: ...10 m or AWG14 shielded 4 wire cable Lmax 50 m Digital input connection Digital input to be activated with voltage free contact or transistor to GND Making current 5mA max length 10 m Probes Max lengt...

Страница 50: ...A Non optically isolated BMS2 Non optically isolated Fieldbus2 P 5 B Optically isolated BMS2 Non optically isolated Fieldbus2 P 5 C Optically isolated BMS2 Optically isolated Fieldbus2 P 5 0 No USB p...

Страница 51: ...mbols Flashing The key is connecting to the pCO During this phase which may last a few seconds the start button is disabled start Flashing The key has detected the pCO and is checking the access right...

Страница 52: ...d corner Choose 1 connessione locale local connection 2 baud rate Auto 3 ricerca dispositivo nd device Auto pLAN As for the port number follow the Wizard s instructions for the port to be identi ed au...

Страница 53: ...f the variables logged during monitoring Therefore to con gure Commissioning the following les are required 2CF 2CD and if necessary the DEV le which can be imported or exported For monitoring purpose...

Страница 54: ...wnloaded to the pendrive as the directories created can only be numbered with XY 00 to 99 FILE TYPES FOR DOWNLOAD controller pLAN address 1 File extension Directory name Description DWL LOG00_01 Logge...

Страница 55: ...and must be entered in the order shown in the table UPLOAD le labels No Label File type No Label File type 1 BIO le bin 6 PVT le pvt 2 IUP le iup 7 LCT le lct 3 BIN le bin blb 8 OED le oed 4 DEV le d...

Страница 56: ...OS is updated and then the application The information is shown on the pCO s built in display and on the pGD1 terminal when both are featured Procedure 1 Connect the pendrive to port A USB key BMS car...

Страница 57: ...e directory level press ESC Once the upload has started the messages shown on the screen are the same as in automatic and autorun mode Download As mentioned above the DOWNLOAD operation can be managed...

Страница 58: ...to con gure pCOnet parameters Con guring pCOWeb When you select PCOWEB settings the following screen will appear D H C P I P A D D R E S S After a short time the elds are populated with the current pa...

Страница 59: ......

Страница 60: ...L INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency pCO5plus 0300020EN rel 11 2 07 11 2...

Отзывы: