38

ENG

pC0300020EN rel. 1.2 - 07.11.2013

3. 

Press Enter to confi rm.

 Terminal config
   press ENTER

  to continue

Fig. 6.l

4. 

Set terminal 1 (Trm1) with address 2 as private (Priv) or shared (Shared) 
according to the application and confi rm to exit. The connection is 
established after a few seconds.

P:07 Adr Priv/Shared
Trm1  02    Pr
Trm2  None  --
Trm3  None  -- Ok?

Yes

Fig. 6.m

5. 

To add a second terminal repeat steps 1 to 4.

6.5 Uploading 

software

The following methods can be used to update the fi rmware and acquire 
the log fi les on pCO controllers:

• 

smart Key programming key;

• 

pCO Manager, a program to install on the PC;

• 

a pendrive.

If you are using a pendrive, before proceeding you must connect the 
terminal to the controller following the instructions in par. 4.5 and then 
establish the connection. The terminal can be either private or shared.

Smart key

The PCOS00AKY0 key is an electronic device used to program and service 
pCO Sistema controllers. The PCOS00AKY0 key simplifi es data transfer 
between the controllers installed and a personal computer by exploiting 
the high capacity fl ash memory for storing software applications, BIOS 
and variable logs. The pCO is connected directly via the telephone 
connector using the cable supplied, while to transfer data to a personal 
computer the PCOS00AKC0 USB adapter is required. The device is 
powered either by the USB port on the PC or by the controller, therefore 
no external power supply is necessary.

USB

cavo telefonico 
telephone cable

PCOS00AKC0

SMART

KEY

start 

mode 

C1

NO1

NO2

NO3

C1

C4

NO4

NO5

NO6

C4

C7

NO7

C7

NO8

C8

NC8

G

G0

U1

u2

U3

GND

+VDC

+V

term

GND

+5 V

REF

U4

GND

U5

GND

VG

VG0

Y1

Y2

Y3

Y4

ID

1

ID

2

ID

3

ID

4

ID

5

ID

6

ID

7

ID

8

IDC1

J1

J24

J2

J3

J4

J5

J14

J10

J13

J12

J15

FieldBus card

B M S card

input: 24 V    50...60 Hz / 28...36 V
max. power: 45 VA/20 W

J11 pLAN

J31

CANL

CANH

GND

J25 BMS2

J26 FBus2

connessioni in alternativa
alternative connections

Fig. 6.n

The steps to follow are described in par. 9.1.

pCO Manager

On all pCO Sistema controllers the resident software can be updated 
using a PC. For this purpose, CAREL provides the pCO Manager program 
and a serial converter with RS485 output to connect to the pCO. pCO 
Manager is part of the “1Tool” program suite; it can also be installed by 
itself and can be obtained free of charge at http://ksa.carel.com, from the 
section “pCO Sistema”-> “pCO_manager”. The fi gure below shows the 
connection diagram.

CVSTDUTLF0

POWER SUPPLY

USB-RS485 converter

USB

C1

NO1

NO2

NO3

C1

C4

NO4

NO5

NO6

C4

C7

NO7

C7

NO8

C8

NC8

G

G0

U1

u2

GND

+VDC

+V

term

GND

+5 V

REF

U4

GND

U5

GND

VG

VG0

Y1

Y2

Y3

Y4

ID

1

ID

2

ID

3

ID

4

ID

5

ID

6

ID

7

ID

8

IDC1

J1

J10

FieldBus card

B M S card

input: 24 V    50...60 Hz / 28...36 V
max. power: 45 VA/20 W

CANL

CANH

GND

OFF

4

3

2

1

ON

 

J 2 5

B M S2

CVSTDUMOR0

CVSTDUMOR0

pCO Manager

connessioni in alternativa
alternative connections

CVSTDUMOR0

Fig. 6.o

The controller can be connected directly to the PC via the RS485 serial 
port used for the “pLAN” connection or via the BMS or Fieldbus serial port 
using the optional RS485 serial card. Lastly, connection can be made 
using the slave USB port, if present.
pCO Manager can communicate with all the programmable controllers 
of the pCO family. The program can also be used to update and download 
to the PC the BOOT, BIOS, application program, confi guration and log fi les 
and also to save fi les to the NAND fl ash memory.

As a rule, CAREL advises NOT to update the BOOT; CAREL always loads the 
BOOT best suited for the controller’s operation during construction. Only 
in very special cases will CAREL ask the user to update the BOOT.
The BIOS can only be updated via the pLAN serial connection. This 
procedure causes the controller to switch to low-level operation. In this 
operating mode log data cannot be downloaded to the PC. To bring the 
controller back to normal communications with pCO Manager, reset 
the pCO after successfully loading the BIOS. For further information on 
the operation of pCO Manager see the online help inside the program. 
Download options are shown in the table below.

LOCAL CONNECTION

Serial

pLAN BMS1/BMS2 FieldBus1 USB slave

Uploading the BOOT

YES

NO

NO

NO

Uploading the BIOS

YES

NO

NO

YES

Uploading the application 
and parameters

YES

YES

YES

YES

Uploading/downloading 
log fi les

YES

YES

YES

YES

Uploading/downloading to 
NAND fl ash memory 

YES

NO

NO

YES

Tab. 6.a

The steps to follow are described in par. 9.2.

Содержание pCO5+

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s pCO5 NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Programmable Controller User manual...

Страница 2: ......

Страница 3: ...corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those speci ed in the technical manual All of the above suggestions likewi...

Страница 4: ...4 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 5: ...12 pCO5 terminals description 24 5 INPUT OUTPUT CONNECTIONS 26 5 1 Power supply 26 5 2 Universal inputs outputs 26 5 3 Digital inputs 29 5 4 Optically isolated analogue outputs 31 5 5 Connecting the...

Страница 6: ...6 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 7: ...ding software and commissioning fast upload download of controller software using a Smart Key or any pendrive provided the controller is equipped with the relative port universal inputs outputs con gu...

Страница 8: ...RS485 Sch interfaccia Ethernet BACnet Servocontrollo della serranda BELIMO Valvola di servocontrollo MP BUS Scheda MP BUS 5 8 4 S R s u t a t s GNX RS485 P1 P2 P3 B A Cnet MS TP FieldBus 1 BMS 1 J1 J2...

Страница 9: ...s terminal panel installation This model can be installed on the panel Its graphics properties are identical to those of the PGDE000 terminal Accessories for installation telephone connection cable co...

Страница 10: ...ntroller consequently acts as a MASTER i e supervisor therefore other con trollers or devices can be connected as SLAVES Up to 64 devices can be connected PCO100TLN0 tech lea et Code 050003270 tLAN an...

Страница 11: ...er e g pCO5 Small EVD Evolu tion external Ultracap module pCOE tech lea et code 050003265 Expansion card Increases the number of inputs outputs on the controller A maximum of 5 expan sion cards can be...

Страница 12: ...White press together with DOWN and ENTER to change the terminal s address only for PGDE terminal see par 6 4 press to increase value Enter White press to con rm value DOWN White press together with UP...

Страница 13: ...NO16 NO17 NO18 C16 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 ONLY FOR LARGE AND EXTRALARGE MODELS Fig 3 a S...

Страница 14: ...s2 J11 pLAN pCO5 SLAVE SLAVE Fig 3 d pLAN network J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 J25 BMS2 J26 FBus2 J11 pLAN pCO5 MASTER SLAVE MASTER SLAVE MASTER SLAVE Fig 3 e Impo...

Страница 15: ...ange of operation see Technical Speci cations large rapid uctuations in room temperature strong magnetic and or radio frequency interference avoid installing near transmitting antennas strong vibratio...

Страница 16: ...ompliance with national and local regulations All the very low voltage connections 24 Vac Vdc or 28 to 36 Vdc analogue and digital inputs analogue outputs serial bus connections power supplies must ha...

Страница 17: ...nel Terminating resistors are not required L 100m 230 Vac 24 Vac L N J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 J25 BMS2 J26 FBus2 J11 pLAN pCO5 G G0 Fig 4 c The proce...

Страница 18: ...ion slip the connector into terminal J10 until it clicks To remove the connector press lightly on the plastic catch on the connector and slip it out Graphic L 50 m cavo telefonico telephone cable J10...

Страница 19: ...onnected to a pCO controller which is itself connected to other controllers in a pLAN network the terminal is directly powered by the controller Be sure to avoid the terminal being powered by two powe...

Страница 20: ...ed PWM output 5 8 10 8 8 U Out Universal I O Analogue output max tot 5 max tot 8 max tot 10 max tot 8 max tot 8 Digital inputs Optically isolated 24 Vac Vdc input 8 12 14 12 12 ID In Digital input 4 I...

Страница 21: ...J8 J1 4 J10 J1 3 J1 2 J16 J1 7 J18 J15 J6 FieldBus card BMS card J11 pLAN J2 5BMS2 J2 6FBus2 4 3 2 1 4 5 1 6 2 3 3 3 8 9 7 8 10 13 14 11 12 15 18 16 17 Fig 4 r Ref Description Ref Description 1 POWER...

Страница 22: ...U7 U8 GND ID9 ID10 ID11 ID12 IDC9 ID13H ID13 IDC13 ID14 ID14H J1 J24 J2 J3 J4 J5 J7 J8 J14 J10 J13 J12 J16 J17 J18 J15 J6 FieldBus card BMS card J23 FBus2 J11 pLAN J25 BMS2 J26 FBus2 4 3 2 1 4 5 1 6...

Страница 23: ...nnector 6 VG voltage A to optically isolated analogue output VG0 power to optically isolated analogue output 0 Vac Vdc 18 Fieldbus BMS selector microswitch 7 Analogue outputs 20 Electronic valve A con...

Страница 24: ...N RS485 port J11 2 Tx Rx Tx Rx pLAN RS485 port J11 3 GND GND pLAN RS485 port 12 Reserved 13 Reserved 14 Reserved Ref Term Label Description 15 J12 1 C1 Common for relays 1 2 3 J12 2 NO1 Normally open...

Страница 25: ...connection J28 2 3 J28 3 2 J28 4 4 22 J30 1 VBAT Power from external Ultracap module J30 2 G0 J30 3 G 23 J29 1 GND Common for power supply to probes J29 2 VREF Power to driver probes J29 3 S1 Probe 1...

Страница 26: ...o handle their respective signals from the application program the universal inputs outputs cannot be used as digital outputs Max number of connectable analogue inputs The maximum number of analogue i...

Страница 27: ...nical Speci cations table The probe has three wires connect one to GND and the other two to two separate but adjacent universal inputs on the same controller e g U1 U2 GND or U4 U5 GND G G0 U1 U2 U3 G...

Страница 28: ...scription Wire colour 5 VREF Power Black GND Power reference Green U1 Signal White Connecting active probes with 0 to 10 V output For information on the maximum number of probes that can be connected...

Страница 29: ...ty devices alarms device status indicators and remote switches These inputs are all optically isolated from the other terminals They can work at 24 Vac 10 15 or at 28 to 36 Vdc 20 10 indicated with ID...

Страница 30: ...6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 24Vac Fig 5 n 24 Vdc digital inputs The ID digital inputs can be controlled at 24 Vdc Example of connection diagram LARGE model G G0 U1 U2 U3 GN...

Страница 31: ...D14H J1 J24 J2 J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND FieldBus card BMS card 230Vac L N Fig 5 q Example 2 Connection diagram with digital inputs at...

Страница 32: ...C13 ID14 ID14H J3 J4 J5 J7 J8 J20 J6 J19 ID15H ID15 IDC15 ID16 ID16H Y5 Y6 ID17 ID18 IDC17 U9 GND U10 GND eldBus card BMS card 24Vac 28 36 Vdc 0 V ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 ID9 ID10 ID11 ID...

Страница 33: ...2 serial port J26 is however electrically isolated from the driver s serial line this ensures that in case of external faults on the line connected to FBus2 the internal driver can keep on working ind...

Страница 34: ...dconsecutively at very close intervals e g star delta motor starter in the order of hundreds of ms use relays belonging to the same group according to the following table RELAY GROUPS FOR CONSECUTIVE...

Страница 35: ...G0 Y1 Y2 Y3 Y4 ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 IDC1 out H M NTC NTC G digitalinput9 CP digitalinput10 digitalinput11 digitalinput12 digital input 13 digital input 14 digital output 9 digital output 10...

Страница 36: ...Each pCO constantly updates the displays on the private terminals while the shared terminals if present are updated only by the pCO that is controlling the terminal at that time The gure below illust...

Страница 37: ...hed the terminal will display a blank screen In this case proceed as follows Procedure 1 Press the UP DOWN and Enter buttons together to go to the screen for setting the terminal address Display addre...

Страница 38: ...CO Manager program and a serial converter with RS485 output to connect to the pCO pCO Manager is part of the 1Tool program suite it can also be installed by itself and can be obtained free of charge a...

Страница 39: ...the controller immediately executes Autorun and upon con rmation from the terminal performs the operations contained in the le Upload and Download UPLOAD can be performed in three di erent ways 1 manu...

Страница 40: ...the clock E is displayed as follows Select a memory to view its status T M E M O R Y S T A T U S P M E M O R Y S T A T U S E M E M O R Y S T A T U S 4 FLASH USB MEMORY Selecting this string displays t...

Страница 41: ...llegamento sonde seriali DP 4 th Tune AT PCO100FD10 scheda seriale FieldBus PGD Touch EEV PGD1 Power PSD0 PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS4...

Страница 42: ...vi terze parti FAN PUMP INVERTER PCOS004850 scheda seriale RS485 PCO10000F0 schede LON PCO10W0BA0 scheda interfaccia BACnet RS485 PCO10W0WB0 pCOWeb sch interfaccia Ethernet BACnet 5 8 4 S R s u t a t...

Страница 43: ...43 ENG pCO5plus 0300020EN rel 1 2 07 11 2013...

Страница 44: ...EVD200 x EVD Evolution x x CAREL slave devices tLAN x CAREL slave devices 485 x x x x x pCOexp 485 x x x x x pCOexp tLAN x Chiller2 expansion x Hydronic fan coil and CANbus x x PlantVisorPRO local x x...

Страница 45: ...serial port protocols PSTN GSM Modbus Slave and CAREL Slave cannot be used on BMS serial port Modbus slave extended with pCOweb Modbus slave extended only for pCOWEB serial card with FW version 1 4 Mo...

Страница 46: ...C 1Y in SSR versions Type of disconnection or microswitching microswitching Category of resistance to heat and re Category D UL94 V2 Ageing characteristics operating hours 80 000 No of automatic opera...

Страница 47: ...kHz asynchronous 100 Hz asynchronous 5 8 10 Power supply for probes and terminals Vdc Active probes can be powered by the 24 21 Vdc 10 P 5 P 3 available on terminal VDC J2 The max available current i...

Страница 48: ...tion of groups Model 1 2 3 4 5 6 7 8 9 10 11 SMALL 1 3 4 6 7 8 Type of relay Type A Type A Type A Type A MEDIUM BUILT IN DRIVER 1 3 4 6 7 8 9 11 12 13 Type of relay Type A Type A Type A Type A Type A...

Страница 49: ...10 m or AWG14 shielded 4 wire cable Lmax 50 m Digital input connection Digital input to be activated with voltage free contact or transistor to GND Making current 5mA max length 10 m Probes Max lengt...

Страница 50: ...A Non optically isolated BMS2 Non optically isolated Fieldbus2 P 5 B Optically isolated BMS2 Non optically isolated Fieldbus2 P 5 C Optically isolated BMS2 Optically isolated Fieldbus2 P 5 0 No USB p...

Страница 51: ...mbols Flashing The key is connecting to the pCO During this phase which may last a few seconds the start button is disabled start Flashing The key has detected the pCO and is checking the access right...

Страница 52: ...d corner Choose 1 connessione locale local connection 2 baud rate Auto 3 ricerca dispositivo nd device Auto pLAN As for the port number follow the Wizard s instructions for the port to be identi ed au...

Страница 53: ...f the variables logged during monitoring Therefore to con gure Commissioning the following les are required 2CF 2CD and if necessary the DEV le which can be imported or exported For monitoring purpose...

Страница 54: ...wnloaded to the pendrive as the directories created can only be numbered with XY 00 to 99 FILE TYPES FOR DOWNLOAD controller pLAN address 1 File extension Directory name Description DWL LOG00_01 Logge...

Страница 55: ...and must be entered in the order shown in the table UPLOAD le labels No Label File type No Label File type 1 BIO le bin 6 PVT le pvt 2 IUP le iup 7 LCT le lct 3 BIN le bin blb 8 OED le oed 4 DEV le d...

Страница 56: ...OS is updated and then the application The information is shown on the pCO s built in display and on the pGD1 terminal when both are featured Procedure 1 Connect the pendrive to port A USB key BMS car...

Страница 57: ...e directory level press ESC Once the upload has started the messages shown on the screen are the same as in automatic and autorun mode Download As mentioned above the DOWNLOAD operation can be managed...

Страница 58: ...to con gure pCOnet parameters Con guring pCOWeb When you select PCOWEB settings the following screen will appear D H C P I P A D D R E S S After a short time the elds are populated with the current pa...