![Carel kVent Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/carel/kvent/kvent_manual_2557421047.webp)
kVent – rel 3.1 – 22/06/2018
47
Code
Description on display
Reset
Action
Variable name
BMS
BacNet
A081
Return fan - Uin Low (FW 10)
Auto reset
Stop unit
Al_UIN_LO_ZA_2
DI1081
BV1081
A082
Return fan - Uin High (FW 10)
Auto reset
Stop unit
Al_UIN_HI_ZA_2
DI1082
BV1082
A083
Return fan - UZK low
Auto reset
Stop unit
Al_UZK_Low_ZA_2
DI1083
BV1083
A084
Return fan - UZK high
Auto reset
Stop unit
Al_UZK_High_ZA_2
DI1084
BV1084
A085
Return fan - IGBT fault
Auto reset
Stop unit
Al_IGBTfault_ZA_2
DI1085
BV1085
A086
Return fan - Earth-GND fault
Auto reset
Stop unit
Al_EarthGNDfault_ZA_2
DI1086
BV1086
A087
Return fan - Peak current error
Auto reset
Stop unit
Al_PeakCurrent_ZA_2
DI1087
BV1087
A088
Return fan - Hall sensor error
Auto reset
Stop unit
Al_HallSensor_ZA_2
DI1088
BV1088
A089
Return fan - Offline
Auto reset
Stop unit
Al_Offline_EBM_2
DI1089
BV1089
A090
Return fan - Phase Failure
User reset
Stop unit
Al_PhaseFault_EBM_2
DI1090
BV1090
A091
Return fan - Motor blocked
User reset
Stop unit
Al_MotBlocked_EBM_2
DI1091
BV1091
A092
Return fan - Mains undervolt.
User reset
Stop unit
Al_MainsUnderV_EBM_2
DI1092
BV1092
A093
Return fan - Mains overvoltage
User reset
Stop unit
Al_MainsOverV_EBM_2
DI1093
BV1093
A094
Return fan - DC-link overvoltage
User reset
Stop unit
Al_DClinkOverV_EBM_2
DI1094
BV1094
A095
Return fan - DC-link undervoltage
User reset
Stop unit
Al_DClinkUnderV_EBM_2
DI1095
BV1095
A096
Return fan - Motor overheat
User reset
Stop unit
Al_MotSuperHeating_EBM_2
DI1096
BV1096
A097
Return fan - Intern.circ.overheat
User reset
Stop unit
Al_IntCircSuperHeat_EBM_2
DI1097
BV1097
A098
Return fan - Out stage overheat.
User reset
Stop unit
Al_OutStageSuperHeat_EBM_2
DI1098
BV1098
A099
Return fan - Hall sensor error
User reset
Stop unit
Al_HallSenErr_EBM_2
DI1099
BV1099
A100
Return fan - Communic. Error
User reset
Stop unit
Al_CommunicationErr_EBM_2
DI1100
BV1100
A101
Return fan - Generic error
User reset
Stop unit
Al_GenericErr_EBM_2
DI1101
BV1101
A102
Return fan - Out stage high temp.
Auto reset
Stop unit
Al_OutStageHighTemp_EBM_2
DI1102
BV1102
A103
Return fan - Int.circ.high temp.
Auto reset
Stop unit
Al_InternCircHighTemp_EBM_2
DI1103
BV1103
A104
Return fan - Motor high temp.
Auto reset
Stop unit
Al_MotHighTemp_EBM_2
DI1104
BV1104
A105
Return fan - DC-link volt.low
Auto reset
Stop unit
Al_DClinkV_Low_EBM_2
DI1105
BV1105
A106
Return fan - Lim.mains power
Auto reset
Stop unit
Al_LimMainsPwr_EBM_2
DI1106
BV1106
A107
Return fan - Lim.mains current
Auto reset
Stop unit
Al_LimMainsA_EBM_2
DI1107
BV1107
A108
Return fan - Brake mode
Auto reset
Stop unit
Al_BrakeMode_EBM_2
DI1108
BV1108
A109
Return fan - Cable break
Auto reset
Stop unit
Al_CableBreak_EBM_2
DI1109
BV1109
A110
Return fan - Ice protection
Auto reset
Stop unit
Al_IceProtection_EBM_2
DI1110
BV1110
A111
Return fan - Heating: motor stop
Auto reset
Stop unit
Al_HeatMotStopped_EBM_2
DI1111
BV1111
A112
Return fan - Speed under limit
Auto reset
Stop unit
Al_SpeedUnderLim_EBM_2
DI1112
BV1112
A113
Return fan - DC-voltage high
Auto reset
Stop unit
Al_DC_VoltageHigh_EBM_2
DI1113
BV1113
A114
Return fan - Supply volt.high
Auto reset
Stop unit
Al_SupplyVoltageHigh_EBM_2
DI1114
BV1114
A115
Return fan - Line imp. High
Auto reset
Stop unit
Al_LineImpHigh_EBM_2
DI1115
BV1115
A404
VOC air quality probe not working
Auto reset
Stop VOC regulation
Al_RetAir_VOC_Prb
DI1404
BV1404
A405
Supply filter 2 alarm
Auto reset
None
Al_SupplyFilter_2
DI1405
BV1405
A406
Return filter alarm
Auto reset
None
Al_ReturnFilter
DI1406
BV1406
A407
Fresh air humidity probe not working
Auto reset
Stop humidity check for
freecooling
Al_FreshAirHumPrb
DI1407
BV1407
A408
Preheating coil maintenance required
Auto reset
None
Al_PreheatCoilWorkHrsWarn
DI1408
BV1408
A412
IEC humidifier maintenance required
Auto reset
None
Al_HumIEC_WorkHrsWarn
DI1412
BV1412
A413
Cool device maintenance required
Auto reset
None
Al_CoolWorkHrsWarn
DI1413
BV1413
A414
Cool device 2 maintenance required
Auto reset
None
Al_Cool2_WorkHrsWarn
DI1414
BV1414
A415
Heat device maintenance required
Auto reset
None
Al_HeatWorkHrsWarn
DI1415
BV1415
A416
Heat device 2 maintenance required
Auto reset
None
Al_Heat2_WorkHrsWarn
DI1416
BV1416
A417
Reverse device maintenance required
Auto reset
None
Al_RevWorkHrsWarn
DI1417
BV1417
A418
Reverse device 2 maintenance required
Auto reset
None
Al_Rev2_WorkHrsWarn
DI1418
BV1418
A422
Out of design temperature limits alarm
Auto reset
Open mixing or stop
ventilation if not present
Al_OutDesignTemp
DI1422
BV1422
A429
Recovery clogeed
Auto reset
Stop recovery
Al_Recovery_clogeed
DI1429
BV1429
A430
Door switch
Auto reset
Stop unit
Al_Door_switch
DI1430
BV1431
A431
Hepa 1 pressure probe alarm
Auto reset
None
Al_HEPA_pressProb1
DI1441
BV1456
A432
Hepa 1 pressure probe alarm
Auto reset
None
Al_HEPA_pressProb2
DI1442
BV1466
A433
Reversable coil alarm
Auto reset
Stop unit
Al_Reversable
DI1443
BV1467
A434
Generic external alarm
Auto reset
Stop unit
Al_Input_generic
DI1444
BV1468
A435
Hepa filter 1
Auto reset
None
Al_HEPA_Filter1
DI1445
BV1469
A436
Hepa filter 2
Auto reset
None
Al_HEPA_Filter2
DI1446
BV1470