Carel kVent Скачать руководство пользователя страница 47

 

kVent – rel 3.1 – 22/06/2018 

47

Code 

Description on display 

Reset 

Action 

Variable name 

BMS 

BacNet 

A081 

Return fan - Uin Low (FW 10) 

Auto reset 

Stop unit 

Al_UIN_LO_ZA_2 

DI1081 

BV1081 

A082 

Return fan - Uin High (FW 10) 

Auto reset 

Stop unit 

Al_UIN_HI_ZA_2 

DI1082 

BV1082 

A083 

Return fan - UZK low 

Auto reset 

Stop unit 

Al_UZK_Low_ZA_2 

DI1083 

BV1083 

A084 

Return fan - UZK high 

Auto reset 

Stop unit 

Al_UZK_High_ZA_2 

DI1084 

BV1084 

A085 

Return fan - IGBT fault 

Auto reset 

Stop unit 

Al_IGBTfault_ZA_2 

DI1085 

BV1085 

A086 

Return fan - Earth-GND fault 

Auto reset 

Stop unit 

Al_EarthGNDfault_ZA_2 

DI1086 

BV1086 

A087 

Return fan - Peak current error 

Auto reset 

Stop unit 

Al_PeakCurrent_ZA_2 

DI1087 

BV1087 

A088 

Return fan - Hall sensor error 

Auto reset 

Stop unit 

Al_HallSensor_ZA_2 

DI1088 

BV1088 

A089 

Return fan - Offline 

Auto reset 

Stop unit 

Al_Offline_EBM_2 

DI1089 

BV1089 

A090 

Return fan - Phase Failure 

User reset 

Stop unit 

Al_PhaseFault_EBM_2 

DI1090 

BV1090 

A091 

Return fan - Motor blocked 

User reset 

Stop unit 

Al_MotBlocked_EBM_2 

DI1091 

BV1091 

A092 

Return fan - Mains undervolt. 

User reset 

Stop unit 

Al_MainsUnderV_EBM_2 

DI1092 

BV1092 

A093 

Return fan - Mains overvoltage 

User reset 

Stop unit 

Al_MainsOverV_EBM_2 

DI1093 

BV1093 

A094 

Return fan - DC-link overvoltage 

User reset 

Stop unit 

Al_DClinkOverV_EBM_2 

DI1094 

BV1094 

A095 

Return fan - DC-link undervoltage 

User reset 

Stop unit 

Al_DClinkUnderV_EBM_2 

DI1095 

BV1095 

A096 

Return fan - Motor overheat 

User reset 

Stop unit 

Al_MotSuperHeating_EBM_2 

DI1096 

BV1096 

A097 

Return fan - Intern.circ.overheat 

User reset 

Stop unit 

Al_IntCircSuperHeat_EBM_2 

DI1097 

BV1097 

A098 

Return fan - Out stage overheat. 

User reset 

Stop unit 

Al_OutStageSuperHeat_EBM_2 

DI1098 

BV1098 

A099 

Return fan - Hall sensor error 

User reset 

Stop unit 

Al_HallSenErr_EBM_2 

DI1099 

BV1099 

A100 

Return fan - Communic. Error 

User reset 

Stop unit 

Al_CommunicationErr_EBM_2 

DI1100 

BV1100 

A101 

Return fan - Generic error 

User reset 

Stop unit 

Al_GenericErr_EBM_2 

DI1101 

BV1101 

A102 

Return fan - Out stage high temp. 

Auto reset 

Stop unit 

Al_OutStageHighTemp_EBM_2 

DI1102 

BV1102 

A103 

Return fan - Int.circ.high temp. 

Auto reset 

Stop unit 

Al_InternCircHighTemp_EBM_2 

DI1103 

BV1103 

A104 

Return fan - Motor high temp. 

Auto reset 

Stop unit 

Al_MotHighTemp_EBM_2 

DI1104 

BV1104 

A105 

Return fan - DC-link volt.low 

Auto reset 

Stop unit 

Al_DClinkV_Low_EBM_2 

DI1105 

BV1105 

A106 

Return fan - Lim.mains power 

Auto reset 

Stop unit 

Al_LimMainsPwr_EBM_2 

DI1106 

BV1106 

A107 

Return fan - Lim.mains current 

Auto reset 

Stop unit 

Al_LimMainsA_EBM_2 

DI1107 

BV1107 

A108 

Return fan - Brake mode 

Auto reset 

Stop unit 

Al_BrakeMode_EBM_2 

DI1108 

BV1108 

A109 

Return fan - Cable break 

Auto reset 

Stop unit 

Al_CableBreak_EBM_2 

DI1109 

BV1109 

A110 

Return fan - Ice protection 

Auto reset 

Stop unit 

Al_IceProtection_EBM_2 

DI1110 

BV1110 

A111 

Return fan - Heating: motor stop 

Auto reset 

Stop unit 

Al_HeatMotStopped_EBM_2 

DI1111 

BV1111 

A112 

Return fan - Speed under limit 

Auto reset 

Stop unit 

Al_SpeedUnderLim_EBM_2 

DI1112 

BV1112 

A113 

Return fan - DC-voltage high 

Auto reset 

Stop unit 

Al_DC_VoltageHigh_EBM_2 

DI1113 

BV1113 

A114 

Return fan - Supply volt.high 

Auto reset 

Stop unit 

Al_SupplyVoltageHigh_EBM_2 

DI1114 

BV1114 

A115 

Return fan - Line imp. High 

Auto reset 

Stop unit 

Al_LineImpHigh_EBM_2 

DI1115 

BV1115 

A404 

VOC air quality probe not working 

Auto reset 

Stop VOC regulation 

Al_RetAir_VOC_Prb 

DI1404 

BV1404 

A405 

Supply filter 2 alarm 

Auto reset 

None 

Al_SupplyFilter_2 

DI1405 

BV1405 

A406 

Return filter alarm 

Auto reset 

None 

Al_ReturnFilter 

DI1406 

BV1406 

A407 

Fresh air humidity probe not working 

Auto reset 

Stop humidity check  for 

freecooling 

Al_FreshAirHumPrb 

DI1407 

BV1407 

A408 

Preheating coil maintenance required 

Auto reset 

None 

Al_PreheatCoilWorkHrsWarn 

DI1408 

BV1408 

A412 

IEC humidifier maintenance required 

Auto reset 

None 

Al_HumIEC_WorkHrsWarn 

DI1412 

BV1412 

A413 

Cool device maintenance required 

Auto reset 

None 

Al_CoolWorkHrsWarn 

DI1413 

BV1413 

A414 

Cool device 2 maintenance required 

Auto reset 

None 

Al_Cool2_WorkHrsWarn 

DI1414 

BV1414 

A415 

Heat device maintenance required 

Auto reset 

None 

Al_HeatWorkHrsWarn 

DI1415 

BV1415 

A416 

Heat device 2 maintenance required 

Auto reset 

None 

Al_Heat2_WorkHrsWarn 

DI1416 

BV1416 

A417 

Reverse device maintenance required 

Auto reset 

None 

Al_RevWorkHrsWarn 

DI1417 

BV1417 

A418 

Reverse device 2 maintenance required 

Auto reset 

None 

Al_Rev2_WorkHrsWarn 

DI1418 

BV1418 

A422 

Out of design temperature limits alarm 

Auto reset 

Open mixing or stop 

ventilation if not present  

Al_OutDesignTemp 

DI1422 

BV1422 

A429 

Recovery clogeed 

Auto reset 

Stop recovery 

Al_Recovery_clogeed 

DI1429 

BV1429 

A430 

Door switch 

Auto reset 

Stop unit 

Al_Door_switch 

DI1430 

BV1431 

A431 

Hepa 1 pressure probe alarm 

Auto reset 

None 

Al_HEPA_pressProb1 

DI1441 

BV1456 

A432 

Hepa 1 pressure probe alarm 

Auto reset 

None 

Al_HEPA_pressProb2 

DI1442 

BV1466 

A433 

Reversable coil alarm 

Auto reset 

Stop unit 

Al_Reversable 

DI1443 

BV1467 

A434 

Generic external alarm 

Auto reset 

Stop unit 

Al_Input_generic 

DI1444 

BV1468 

A435 

Hepa filter 1 

Auto reset 

None 

Al_HEPA_Filter1 

DI1445 

BV1469 

A436 

Hepa filter 2 

Auto reset 

None 

Al_HEPA_Filter2 

DI1446 

BV1470 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание kVent

Страница 1: ...kVent rel 3 1 22 06 2018 1 kVent Controller for ventilation units Manual H i g h E f f i c i e n c y S o l u t i o n s...

Страница 2: ...kVent rel 3 1 22 06 2018 2...

Страница 3: ...ontrollers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and...

Страница 4: ...kVent rel 3 1 22 06 2018 4...

Страница 5: ...CO2 Regulation 25 5 12 Boost function 25 5 13 Minor functions 25 5 14 Import Export parameters 25 6 PARAMETERS TABLE 26 6 1 INFO menu in main mask 26 6 2 SET menu in main mask 29 6 3 MODE menu in mai...

Страница 6: ...e control Air flow control Protection Filters Fire Smoke alarm Frost protection Door switch Interface Browser interface based on WebKit pGDE for advanced function and service thTune for end user 3 dif...

Страница 7: ...cables be laid parallel to the power cables Keep the paths of the probe cables as short as possible and avoid making spiral paths that enclose power devices In case of malfunctions do not attempt to r...

Страница 8: ...ame FieldBus port for ModbusMaster 19200 8N2 With the following parameters is possible to define a different Frame Ha91 Stop bits Ha92 Parity Display protocol on port DISP ModBus master protocol on po...

Страница 9: ...alog outputs Out Y PWM output not optically isolated 2 Analog outputs Out Y Output for single pole stepper motor 1 TOTAL ANALOG OUTPUTS 2 Digital outputs Out NO NC relay output 1 Out NO relay output 5...

Страница 10: ...kVent rel 3 1 22 06 2018 10 Connections example 2 4 3...

Страница 11: ...ure AI4 Fresh temperature AI3 Recovery ON OFF DO10 Recovery 3point valve DO23 DO24 Modulating recovery AO6 Recovery 2 steps DO36 DO37 3 Glycol Supply temperature AI1 Exhaust temperature AI4 Fresh temp...

Страница 12: ...ve control Back water temperature AI6 Fresh temperature AI3 Heat 1 DO4 Modulating heat AO3 Heat 2 DO6 Heat 3 point valve DO17 DO18 Cool Heat common AO12 3 0 10V valve in common with cool Back water te...

Страница 13: ...3 point valve DO27 DO28 Modulating preheater AO7 4 1 modulating After preheater temperature AI11 Modulating preheater AO7 Preheater back water temperature AI10 Preheater 3 point valve DO27 DO28 Prehea...

Страница 14: ...ulating exhaust fan AO2 1 VAV Supply air pressure AI13 Exhaust air pressure AI14 Modulating supply fan AO1 Modulating exhaust fan AO2 2 CAV Supply air pressure AI13 Exhaust air pressure AI14 Modulatin...

Страница 15: ...r 14 Ga66 Exhaust air pressure 12 Gb23 Comfort 11 Gc21 Preheater 11 Gd11 IEC 15 Ga 71 Supply humidity 13 Gb25 Supply filter alarm 12 Gc23 Humidifier 12 Gd12 Cool Heat signal 24 GaB6 VOC sensor 14 Gb27...

Страница 16: ...update the application software of the controllers family with the following methods 1 Update from computer by USB cable 2 Update via USB flash drive 3 Update with file transfer via FTP Attention only...

Страница 17: ...directory on the computer to the UPGRADE directory on the kVent controller 3 Access the system menu on the kVent and select UPGRADE Note when having loaded the update file to the UPGRADE directory vi...

Страница 18: ...and probes are available in a menu connected to the synoptics The individual screens of the synoptics are shown below Set In this menu is possible to see the current setpoint and the working mode def...

Страница 19: ...ck Enable scheduler Clock 2s thTune scheduler settings Fan Change working setpoint 1 ECO 2 PRECOMFORT 3 COMFORT 4 STOP On Off Switch ON OFF th Tune display Exit from settings Clock Mode for 3s Run boo...

Страница 20: ...e comfort zones are ECO PRECOMFORT and COMFORT This working mode can change the following sets if the functions are activated 1 Supply temperature a Economy Z001 b Precomfort Z002 c Comfort Z003 2 Roo...

Страница 21: ...ured by Service I003 No serious alarm On by digital input On by the OR of the following conditions o On by pGD X00a o On by BMS o On by thTune if present o On by scheduler if enabled Variable mode is...

Страница 22: ...reshold The bypass damper can be modulated to reach the desired temperature for the supply air temperature because the freecooling can be considered as the first step of sequential PID regulation In c...

Страница 23: ...e below an example with devices with the same power Min inverter power 20 Max heaters power 33 3kW In this case the second heater will start when the request reach the threshold calculated in the foll...

Страница 24: ...decrease the efficiency of the unit kVent provides a control on external temperature and after preheater device If the unit has a preheater the after preheater temperature is considered for recovery...

Страница 25: ...mode menu X00b or by TH Tune pressing thogheter the buttons Clock Mode for 3s The maximum Boost time is settable on the Setting menu through the parameter H023 5 13 Minor functions Antistack procedure...

Страница 26: ...0l Supply humidity probe Probe value Real rh R SupplyHum ReadVal IR88 AV88 Y00l Suction temperature probe Probe value Real rh R FreshAirHum ReadVal IR89 AV89 Y00l Return CO2 sensor Probe value Real pp...

Страница 27: ...nt valve close Value Bool R CoolVlv_Cl Ctrl DI84 BV269 Y00y Reverse 3point valve open Hardware value Bool R CoolHeatVlv_Op HW_Val DI85 BV270 Y00y Reverse 3point valve open Value Bool R CoolHeatVlv_Op...

Страница 28: ...8 Y0ag Ziehl Abegg return fan electrical info Motr temperature C Real R MB_Devices FanElectricalInfo_Z A_2 MotTemp IR119 AV119 Y0ah Supply fan Value Bool R SupplyFan Ctrl DI5 BV172 Y0ah Modulating sup...

Страница 29: ...dity setpoint Economy Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP Economy HR7 AV7 Z008 Humidity setpoint PreComfort Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP PreComfort HR8 AV8 Z009 Humidity setpoin...

Страница 30: ...ed 0 StartMont h HR48 PIV48 Z00e Last day of period USInt 2 1 31 R W Scheduler_OnOffUnit Scheduler _1 VacationsSched 0 EndDay HR49 PIV49 Z00e Last month of period USInt 1 1 12 R W Scheduler_OnOffUnit...

Страница 31: ...PIV77 Z00f Special month USInt 1 1 12 R W Scheduler_OnOffUnit Scheduler _1 SpecDaysSched 5 SpecialM onth HR78 PIV78 Z00f Unit status of the special day 0 OFF 1 ECONOMY 2 PRE COMFORT 3 COMFORT 4 AUTO...

Страница 32: ...R210 PIV210 A042 Time minimum ON ON reheater device UInt 60 s 0 65535 R W ReHeatMinOnOnSameT HR211 PIV211 A043 Minimum reheater hot water valve Real 20 0 0 0 100 0 R W ReHW_MinPID HR212 AV212 A044 Min...

Страница 33: ...Hours counter reverse 2nd step UDInt 0 0 999999 R W HC_Rev_2 MaintThrsh HR326 PIV326 C006 Hours counter reverse 2nd step Bool 0 1 R W HC_Rev_2 Res C38 BV814 C007 Reverse device 2nd step Manual value U...

Страница 34: ...999 9 R W ManSupplyFanIdle HR151 AV151 D025 Delay to switch OFF supply fan UInt 70 s 0 65535 R W DOff_SupplyFan HR152 PIV152 D026 Delay between fan and damper UInt 15 s 0 65535 R W DT_Dmp HR153 PIV15...

Страница 35: ...ating running Bool 0 1 R W FastHeatTrig C30 BV734 E032 Fast heating stop Bool 0 1 R W FastHeatStop C31 BV735 E033 Fast heating time UInt 1500 s 0 65535 R W FastHeatT HR272 PIV272 E034 Fast cooling thr...

Страница 36: ...999 9 999 9 R W AI_ReadFnt 4 Param Min_Val HR781 AV781 Ga19 Analog input functions Maximum value Real 105 0 C 999 9 999 9 R W AI_ReadFnt 4 Param Max_Val HR782 AV782 Ga20 Analog input functions Offset...

Страница 37: ...nt 0 0 70 R W AI_ReadFnt 15 Ch HR844 IV844 Ga72 Analog input functions Type USInt 43 0 50 R W AI_ReadFnt 15 Param Typ HR846 PIV846 Ga73 Analog input functions Minimum value Real 0 0 rh 999 9 999 9 R W...

Страница 38: ...5 Analog input functions Offset Real 0 0 rh 99 9 99 9 R W AI_ReadFnt 25 Param Offset HR909 AV909 DIGITAL IN SET menu 6 10 2 Mask code Description Type Default UoM Range R W Variable Name BMS BacNet Di...

Страница 39: ...s Priority USInt R DI_ReadFnt 20 Prio IR405 PIV405 Digital input functions Status Bool R DI_ReadFnt 20 Hw_Val DI270 BV1797 Gb39 Digital input functions Channel DInt 0 0 70 R W DI_ReadFnt 20 Ch HR948 I...

Страница 40: ...ctions Channel DInt 0 0 50 R W DO_ReadFnt 15 Ch HR984 IV984 Gc30 Digital output functions Logic Bool FALSE 0 1 R W DO_ReadFnt 15 Logic C311 BV1870 Digital output functions Priority USInt R DO_ReadFnt...

Страница 41: ...igital output functions Status Bool R DO_ReadFnt 35 Hw_Val DI308 BV1948 Gc69 Digital output functions Channel DInt 0 0 70 R W DO_ReadFnt 35 Ch HR1024 IV1024 Gc70 Digital output functions Logic Bool FA...

Страница 42: ...72 PIV472 Analog output functions Request Real R AO_ReadFnt 10 Hw_Val IR473 AV473 Gd10 Analog output functions Channel DInt 0 0 60 R W AO_ReadFnt 10 Ch HR1066 IV1066 Analog output functions Priority U...

Страница 43: ...s_PreHeat Economy_Ti HR1113 IV1520 H033 Modes set PID regulations PreHeat Real 5 0 999 9 999 9 R W PIDs_PreHeat Precomfort_Kp HR1132 AV1539 H034 Modes set PID regulations PreHeat Int 120 s 0 65535 R W...

Страница 44: ...uration not allowed Alarm status Bool R Al_UnitCfgError Active DI1037 BV2068 I001 Recovery application code USInt 0 0 4 R W AppCode_Rec HR83 PIV83 I001 Application heating code USInt 0 0 4 R W AppCode...

Страница 45: ...wing alarms log display screen The alarms log memorizes the kVent operation status when the alarms are triggered Each log entry is an even that can be displayed from among all of the events available...

Страница 46: ...eset Stop humidifier Al_SupplyAirHum_Prb DI1036 BV1036 A037 Unit configuration not allowed Auto reset Stop unit Al_UnitCfgError DI1037 BV1037 A038 Supply fan Offline Auto reset Stop unit Al_Offline_ZA...

Страница 47: ...current Auto reset Stop unit Al_LimMainsA_EBM_2 DI1107 BV1107 A108 Return fan Brake mode Auto reset Stop unit Al_BrakeMode_EBM_2 DI1108 BV1108 A109 Return fan Cable break Auto reset Stop unit Al_Cable...

Страница 48: ...m the release 2 1 0 there is the possibility to setup a different PID values for each devices in base of the working mode set The enabling is manage under the menu Settings parameter H028 8 4 HEPA fil...

Страница 49: ...ed the unit of measure from s to min on the time setting for the pump on the heating coils during the off time Fixed the DEV configuration changed FloatValve management now at the startup of the unit...

Страница 50: ...ant value added all the masks to set up the PID parameters for each coils in base of the working mode added the fresh modulating damper Condensing Unit Management Add the RU language Add the CZ langua...

Страница 51: ...kVent rel 3 1 22 06 2018 51...

Страница 52: ...changes or modifications to its products without prior notice All trademarks hereby referenced are the property of their respective owners CAREL is a registered trademark of CAREL INDUSTRIES Hqs in It...

Страница 53: ...kVent rel 3 1 22 06 2018 53 CAREL INDUSTRIES S p a Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com...

Отзывы: