Carel kVent Скачать руководство пользователя страница 22

 

kVent – rel 3.1 – 22/06/2018 

22

  Note:  To  disable  external  temperature  compensation  is 

possible  to  setup  minimum  compensation  equal  to  maximum 
compensation. 
 

 

Supply regulation 

5.4.2

The  temperature  regulation  is  based  on  supply  temperature 
and its setpoint. If the setpoint set is the room set or return set, 
according  to  configuration  parameter  (I008),  this  will  be 
converted to supply set. 
To calculate the power of devices, a PID sequence is used. 
The following graph show the PID sequence in case of cooling: 

 

The  following  graph  show  the  PID  sequence  in  case  of 
heating: 

 

With  a  unique  setpoint  and  different  sets  of  PID  parameters, 
the first request is calculated with a standard PID. The second 
request  starts  when  the  first  one  has  reached  100%.  The 
setpoint for the second device regulation is the same, while the 
PID  set  of  parameters  are  different.  According  to  the  PID 
behaviour of the second device, the percentage of activation of 
the  second  device  at  the start  up  should  be  equal  to  ‘’offset’’, 
but thanks to the incremental PID it is possible to consider only 
the  last  calculated  delta  so  that  there  aren’t  any  bumps,  then 
the  second  device  will  start  from  the  minimum  output,  then  it 
will  regulate  according  to  PID  parameters  and  supply 
temperature. 
 
In  case  we  have more  devices  and  one  is  not  available  when 
required  from  the  sequential  PID  regulation  -  for  activation 
conditions  not  verified  (i.e.  recovery  conditions)  or  active 
alarms - the request passes to the other one. If the first device 
becomes available again the device will be turned on at 100%. 
 

5.5  Fresh air regulation 

In  case  of  unit  without  the  mixing  damper,  the  supply  air  is 
always coming from the outside: if the external temperature is 
better  than  the  room  or  return  temperature  and  the  activation 
of  freecooling/freeheating  is  verified  (external  temperature 
lower  than  the  regulation  temperature  of  a settable  delta), the 
bypass damper opens and the heat exchanger is bypassed.  
 
In  the  following  picture  we  represent  the  ‘’freecooling’’ 
enabling, that in case of unit without the mixing damper is the 
by-pass  damper  activation  condition,  considering  as  example 
the room temperature as regulation variable. 
The freecooling is enabled if the external temperature is higher 
than  the  lower  supply  temperature  threshold,  while  the 
freeheating is enabled if the external temperature is lower than 
the upper supply temperature threshold. 

 

The  bypass  damper  can  be  modulated  to  reach  the  desired 
temperature  for  the  supply  air  temperature,  because  the 
freecooling  can  be  considered  as  the  first  step  of  sequential 
PID regulation. 
In 

case 

of 

unit 

with 

the 

mixing 

damper, 

the 

freecooling/freeheating  conditions  are  the  same,  but  mixing 
damper  and  external  one  modulate  accordingly,  and  the  logic 
acts on the bypass damper as in the previous case. 
 

 

Night kick 

5.5.1

If the unit is in standby mode, it starts at a certain hour (H016
in the night to check the conditions and if there is requests, the 
unit  switch  ON.  When  conditions  are  reached,  the  unit  goes 
back to standby. 
 

5.6  Humidity regulation 

The  regulation  of  the  unit  could  be  done  according  to  return, 
supply  or  room  set,  according  to  configuration  parameter 
(I009). The regulation of humidity in kVent is done by absolute 
humidity. 
Absolute  humidity  setpoint  is  the  conversion  between  the 
actual  temperature  setpoint  (room,  return  or  supply)  and  the 
relavtive humidity set that the user can change. 
Absolute  humidity  is  the  conversion  between  the  actual 
temperature and the room relative humidity. 
Based  on  these  conversions,  it’s  possible  to  determine  if  the 
unit should go in humidifying or dehumidifying mode. When the 
humidity  goes  to  change  mode,  a  delay  is  provided  to  avoid 
fast change of humidity control. 

 

In  case  of  regulation  on  return  or  room  temperature,  the 
application  check  the  supply  humidity  limits  to  avoid  water  of 
the ducts. Closer the supply humidity is to the limits, lower the 
humidity PID can act. 
In  case  of  regulation  on  supply,  the  humidity    request  goes 
directly to the devices. 
 
During dehumidification: 

The signal to control the cooling devices is calculate from 
the  maximum  between  output  temperature  PID  and  the 
output humidity PID. 

The main heating devices are disabled and the reheaters 
works to compensate the cooling effect. 

Mixing damper is closed. 

 
During humidification: 

Mixing damper is open 100%. 

 

5.7  Devices activation 

 

ON/OFF Recovery  

5.7.1

In  case  of  ON/OFF  recovery,  kVent  calculate  modulating 
recovery  request  anyway.    The  digital  output  is  activated  by 
time,  calculated  by  the  request,  with  a  fixed  period  of  10 
minutes. 
For example if the request is 60%, the digital output is ON for 
360s  and  OFF  for  240s,  so  the  following  graph  show  the 
working logic. 

Supply temp. 

Set 

Recovery 

E011 
E012 

Cooling device 

B008 
B009 

100% 

0% 

Mixing 

E024 
E025 

Set 

Recovery 

E006 
E007 

Heating device 

A016 
A017 

100% 

0% 

Reheat 

A035 
A036 

Mixing 

E022 
E023 

Supply temp. 

Set 

Room – Ext Temp. 

Delta 
2.0°C 

Set 

Dehumidification 

Humidification 

Delay 
F013 

Band 
F014 

Delay 
F013 

Содержание kVent

Страница 1: ...kVent rel 3 1 22 06 2018 1 kVent Controller for ventilation units Manual H i g h E f f i c i e n c y S o l u t i o n s...

Страница 2: ...kVent rel 3 1 22 06 2018 2...

Страница 3: ...ontrollers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and...

Страница 4: ...kVent rel 3 1 22 06 2018 4...

Страница 5: ...CO2 Regulation 25 5 12 Boost function 25 5 13 Minor functions 25 5 14 Import Export parameters 25 6 PARAMETERS TABLE 26 6 1 INFO menu in main mask 26 6 2 SET menu in main mask 29 6 3 MODE menu in mai...

Страница 6: ...e control Air flow control Protection Filters Fire Smoke alarm Frost protection Door switch Interface Browser interface based on WebKit pGDE for advanced function and service thTune for end user 3 dif...

Страница 7: ...cables be laid parallel to the power cables Keep the paths of the probe cables as short as possible and avoid making spiral paths that enclose power devices In case of malfunctions do not attempt to r...

Страница 8: ...ame FieldBus port for ModbusMaster 19200 8N2 With the following parameters is possible to define a different Frame Ha91 Stop bits Ha92 Parity Display protocol on port DISP ModBus master protocol on po...

Страница 9: ...alog outputs Out Y PWM output not optically isolated 2 Analog outputs Out Y Output for single pole stepper motor 1 TOTAL ANALOG OUTPUTS 2 Digital outputs Out NO NC relay output 1 Out NO relay output 5...

Страница 10: ...kVent rel 3 1 22 06 2018 10 Connections example 2 4 3...

Страница 11: ...ure AI4 Fresh temperature AI3 Recovery ON OFF DO10 Recovery 3point valve DO23 DO24 Modulating recovery AO6 Recovery 2 steps DO36 DO37 3 Glycol Supply temperature AI1 Exhaust temperature AI4 Fresh temp...

Страница 12: ...ve control Back water temperature AI6 Fresh temperature AI3 Heat 1 DO4 Modulating heat AO3 Heat 2 DO6 Heat 3 point valve DO17 DO18 Cool Heat common AO12 3 0 10V valve in common with cool Back water te...

Страница 13: ...3 point valve DO27 DO28 Modulating preheater AO7 4 1 modulating After preheater temperature AI11 Modulating preheater AO7 Preheater back water temperature AI10 Preheater 3 point valve DO27 DO28 Prehea...

Страница 14: ...ulating exhaust fan AO2 1 VAV Supply air pressure AI13 Exhaust air pressure AI14 Modulating supply fan AO1 Modulating exhaust fan AO2 2 CAV Supply air pressure AI13 Exhaust air pressure AI14 Modulatin...

Страница 15: ...r 14 Ga66 Exhaust air pressure 12 Gb23 Comfort 11 Gc21 Preheater 11 Gd11 IEC 15 Ga 71 Supply humidity 13 Gb25 Supply filter alarm 12 Gc23 Humidifier 12 Gd12 Cool Heat signal 24 GaB6 VOC sensor 14 Gb27...

Страница 16: ...update the application software of the controllers family with the following methods 1 Update from computer by USB cable 2 Update via USB flash drive 3 Update with file transfer via FTP Attention only...

Страница 17: ...directory on the computer to the UPGRADE directory on the kVent controller 3 Access the system menu on the kVent and select UPGRADE Note when having loaded the update file to the UPGRADE directory vi...

Страница 18: ...and probes are available in a menu connected to the synoptics The individual screens of the synoptics are shown below Set In this menu is possible to see the current setpoint and the working mode def...

Страница 19: ...ck Enable scheduler Clock 2s thTune scheduler settings Fan Change working setpoint 1 ECO 2 PRECOMFORT 3 COMFORT 4 STOP On Off Switch ON OFF th Tune display Exit from settings Clock Mode for 3s Run boo...

Страница 20: ...e comfort zones are ECO PRECOMFORT and COMFORT This working mode can change the following sets if the functions are activated 1 Supply temperature a Economy Z001 b Precomfort Z002 c Comfort Z003 2 Roo...

Страница 21: ...ured by Service I003 No serious alarm On by digital input On by the OR of the following conditions o On by pGD X00a o On by BMS o On by thTune if present o On by scheduler if enabled Variable mode is...

Страница 22: ...reshold The bypass damper can be modulated to reach the desired temperature for the supply air temperature because the freecooling can be considered as the first step of sequential PID regulation In c...

Страница 23: ...e below an example with devices with the same power Min inverter power 20 Max heaters power 33 3kW In this case the second heater will start when the request reach the threshold calculated in the foll...

Страница 24: ...decrease the efficiency of the unit kVent provides a control on external temperature and after preheater device If the unit has a preheater the after preheater temperature is considered for recovery...

Страница 25: ...mode menu X00b or by TH Tune pressing thogheter the buttons Clock Mode for 3s The maximum Boost time is settable on the Setting menu through the parameter H023 5 13 Minor functions Antistack procedure...

Страница 26: ...0l Supply humidity probe Probe value Real rh R SupplyHum ReadVal IR88 AV88 Y00l Suction temperature probe Probe value Real rh R FreshAirHum ReadVal IR89 AV89 Y00l Return CO2 sensor Probe value Real pp...

Страница 27: ...nt valve close Value Bool R CoolVlv_Cl Ctrl DI84 BV269 Y00y Reverse 3point valve open Hardware value Bool R CoolHeatVlv_Op HW_Val DI85 BV270 Y00y Reverse 3point valve open Value Bool R CoolHeatVlv_Op...

Страница 28: ...8 Y0ag Ziehl Abegg return fan electrical info Motr temperature C Real R MB_Devices FanElectricalInfo_Z A_2 MotTemp IR119 AV119 Y0ah Supply fan Value Bool R SupplyFan Ctrl DI5 BV172 Y0ah Modulating sup...

Страница 29: ...dity setpoint Economy Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP Economy HR7 AV7 Z008 Humidity setpoint PreComfort Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP PreComfort HR8 AV8 Z009 Humidity setpoin...

Страница 30: ...ed 0 StartMont h HR48 PIV48 Z00e Last day of period USInt 2 1 31 R W Scheduler_OnOffUnit Scheduler _1 VacationsSched 0 EndDay HR49 PIV49 Z00e Last month of period USInt 1 1 12 R W Scheduler_OnOffUnit...

Страница 31: ...PIV77 Z00f Special month USInt 1 1 12 R W Scheduler_OnOffUnit Scheduler _1 SpecDaysSched 5 SpecialM onth HR78 PIV78 Z00f Unit status of the special day 0 OFF 1 ECONOMY 2 PRE COMFORT 3 COMFORT 4 AUTO...

Страница 32: ...R210 PIV210 A042 Time minimum ON ON reheater device UInt 60 s 0 65535 R W ReHeatMinOnOnSameT HR211 PIV211 A043 Minimum reheater hot water valve Real 20 0 0 0 100 0 R W ReHW_MinPID HR212 AV212 A044 Min...

Страница 33: ...Hours counter reverse 2nd step UDInt 0 0 999999 R W HC_Rev_2 MaintThrsh HR326 PIV326 C006 Hours counter reverse 2nd step Bool 0 1 R W HC_Rev_2 Res C38 BV814 C007 Reverse device 2nd step Manual value U...

Страница 34: ...999 9 R W ManSupplyFanIdle HR151 AV151 D025 Delay to switch OFF supply fan UInt 70 s 0 65535 R W DOff_SupplyFan HR152 PIV152 D026 Delay between fan and damper UInt 15 s 0 65535 R W DT_Dmp HR153 PIV15...

Страница 35: ...ating running Bool 0 1 R W FastHeatTrig C30 BV734 E032 Fast heating stop Bool 0 1 R W FastHeatStop C31 BV735 E033 Fast heating time UInt 1500 s 0 65535 R W FastHeatT HR272 PIV272 E034 Fast cooling thr...

Страница 36: ...999 9 999 9 R W AI_ReadFnt 4 Param Min_Val HR781 AV781 Ga19 Analog input functions Maximum value Real 105 0 C 999 9 999 9 R W AI_ReadFnt 4 Param Max_Val HR782 AV782 Ga20 Analog input functions Offset...

Страница 37: ...nt 0 0 70 R W AI_ReadFnt 15 Ch HR844 IV844 Ga72 Analog input functions Type USInt 43 0 50 R W AI_ReadFnt 15 Param Typ HR846 PIV846 Ga73 Analog input functions Minimum value Real 0 0 rh 999 9 999 9 R W...

Страница 38: ...5 Analog input functions Offset Real 0 0 rh 99 9 99 9 R W AI_ReadFnt 25 Param Offset HR909 AV909 DIGITAL IN SET menu 6 10 2 Mask code Description Type Default UoM Range R W Variable Name BMS BacNet Di...

Страница 39: ...s Priority USInt R DI_ReadFnt 20 Prio IR405 PIV405 Digital input functions Status Bool R DI_ReadFnt 20 Hw_Val DI270 BV1797 Gb39 Digital input functions Channel DInt 0 0 70 R W DI_ReadFnt 20 Ch HR948 I...

Страница 40: ...ctions Channel DInt 0 0 50 R W DO_ReadFnt 15 Ch HR984 IV984 Gc30 Digital output functions Logic Bool FALSE 0 1 R W DO_ReadFnt 15 Logic C311 BV1870 Digital output functions Priority USInt R DO_ReadFnt...

Страница 41: ...igital output functions Status Bool R DO_ReadFnt 35 Hw_Val DI308 BV1948 Gc69 Digital output functions Channel DInt 0 0 70 R W DO_ReadFnt 35 Ch HR1024 IV1024 Gc70 Digital output functions Logic Bool FA...

Страница 42: ...72 PIV472 Analog output functions Request Real R AO_ReadFnt 10 Hw_Val IR473 AV473 Gd10 Analog output functions Channel DInt 0 0 60 R W AO_ReadFnt 10 Ch HR1066 IV1066 Analog output functions Priority U...

Страница 43: ...s_PreHeat Economy_Ti HR1113 IV1520 H033 Modes set PID regulations PreHeat Real 5 0 999 9 999 9 R W PIDs_PreHeat Precomfort_Kp HR1132 AV1539 H034 Modes set PID regulations PreHeat Int 120 s 0 65535 R W...

Страница 44: ...uration not allowed Alarm status Bool R Al_UnitCfgError Active DI1037 BV2068 I001 Recovery application code USInt 0 0 4 R W AppCode_Rec HR83 PIV83 I001 Application heating code USInt 0 0 4 R W AppCode...

Страница 45: ...wing alarms log display screen The alarms log memorizes the kVent operation status when the alarms are triggered Each log entry is an even that can be displayed from among all of the events available...

Страница 46: ...eset Stop humidifier Al_SupplyAirHum_Prb DI1036 BV1036 A037 Unit configuration not allowed Auto reset Stop unit Al_UnitCfgError DI1037 BV1037 A038 Supply fan Offline Auto reset Stop unit Al_Offline_ZA...

Страница 47: ...current Auto reset Stop unit Al_LimMainsA_EBM_2 DI1107 BV1107 A108 Return fan Brake mode Auto reset Stop unit Al_BrakeMode_EBM_2 DI1108 BV1108 A109 Return fan Cable break Auto reset Stop unit Al_Cable...

Страница 48: ...m the release 2 1 0 there is the possibility to setup a different PID values for each devices in base of the working mode set The enabling is manage under the menu Settings parameter H028 8 4 HEPA fil...

Страница 49: ...ed the unit of measure from s to min on the time setting for the pump on the heating coils during the off time Fixed the DEV configuration changed FloatValve management now at the startup of the unit...

Страница 50: ...ant value added all the masks to set up the PID parameters for each coils in base of the working mode added the fresh modulating damper Condensing Unit Management Add the RU language Add the CZ langua...

Страница 51: ...kVent rel 3 1 22 06 2018 51...

Страница 52: ...changes or modifications to its products without prior notice All trademarks hereby referenced are the property of their respective owners CAREL is a registered trademark of CAREL INDUSTRIES Hqs in It...

Страница 53: ...kVent rel 3 1 22 06 2018 53 CAREL INDUSTRIES S p a Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com...

Отзывы: