kVent – rel 3.1 – 22/06/2018
26
6. PARAMETERS TABLE
The following tables show the parameters and values displayed by the terminal and the variables sent to supervisor.
kVent can be connected to various systems of supervision, in particular can be used the following communication protocols BMS on the
Ethernet port: Modbus® and BacNet™.
The Modbus® address is the address specified in the Modbus® frame.
BMS index meaning
BacNet index meaning
IR
Input Register
AV
Analog Value
HR
Holding Register
IV
Integer Value
C
Coil
BV
Binary Value
DI
Discrete Input
PIV
Positive Integer Value
6.1 INFO menu in main mask
Mask
code
Description
Type
Default
UoM
Range
R/W
Variable Name
BMS
BacNet
Y00a
Supply temperature probe - Probe value
Real
°C
R
SupplyTemp.ReadVal
IR18
AV18
Y00a
Temperature setpoint
Real
°C
R
TempRegSetP
IR1
AV1
Y00a
Modulating heating output - Hardware value
Real
%
R
HeatVlv.HW_Val
IR19
AV19
Y00a
Modulating reverse output - Hardware value
Real
%
R
RevOutVlv.HW_Val
IR20
AV20
Y00a
Modulating cooling output - Hardware value
Real
%
R
CoolVlv.HW_Val
IR21
AV21
Y00a
Modulating cooling/heating signal - Hardware value
Real
%
R
Modul_CoolHeat_NoRev.HW_V
al
IR22
AV22
Y00a
Modulating heat recovery output - Hardware value
Real
%
R
HeatRecovery.HW_Val
IR23
AV23
Y00a
MixDampReq
Real
%
R
MixDampReq
IR24
AV24
Y00a
Modulating reheating output - Hardware value
Real
%
R
ReHeatVlv.HW_Val
IR25
AV25
Y00h
Supply air pressure probe - Probe value
Real
Pa
R
SupplyAirP.ReadVal
IR74
AV74
Y00h
Supply air flow
Real
m3h
R
SupplyAirFlow
IR75
AV75
Y00h
Modulating supply fan - Hardware value
Real
%
R
ModulSupplyFan.HW_Val
IR76
AV76
Y00h
Supply fan - Value
Bool
R
SupplyFan.Ctrl
DI5
BV172
Y00i
Exhaust air pressure probe - Probe value
Real
Pa
R
ExhAirP.ReadVal
IR77
AV77
Y00i
Return air flow
Real
m3h
R
ExhAirFlow
IR78
AV78
Y00i
Modulating return fan - Hardware value
Real
%
R
ModulExhFan.HW_Val
IR79
AV79
Y00i
Return fan - Value
Bool
R
ExhFan.Ctrl
DI6
BV176
Y00j
Supply temperature probe - Probe value
Real
°C
R
SupplyTemp.ReadVal
IR18
AV18
Y00j
Return temperature probe - Probe value
Real
°C
R
RetTemp.ReadVal
IR80
AV80
Y00j
External temperature probe - Probe value
Real
°C
R
ExtTemp.ReadVal
IR81
AV81
Y00j
Exhaust temperature probe - Probe value
Real
°C
R
ExhTemp.ReadVal
IR82
AV82
Y00j
Heating water temperature probe - Probe value
Real
°C
R
W_HeatCoilTemp.ReadVal
IR83
AV83
Y00k
Preheater water temperature probe - Probe value
Real
°C
R
W_PreHeatCoilTemp.ReadVal
IR84
AV84
Y00k
After preheating temperature probe - Probe value
Real
°C
R
AfterPreHeatCoilTemp.ReadVal
IR85
AV85
Y00k
thTune temperature value
Real
°C
R
Temp_THTN_1
IR86
AV86
Y00l
thTune humidity value
Real
%rh
R
Hum_THTN_1
IR87
AV87
Y00l
Supply humidity probe - Probe value
Real
%rh
R
SupplyHum.ReadVal
IR88
AV88
Y00l
Suction temperature probe - Probe value
Real
%rh
R
FreshAirHum.ReadVal
IR89
AV89
Y00l
Return CO2 sensor - Probe value
Real
ppm
R
RetAirCO2.ReadVal
IR90
AV90
Y00l
Return VOC sensor - Probe value
Real
%
R
RetAirVOC.ReadVal
IR91
AV91
Y00p
Digital input remote ON - Hardware value
Bool
R
RemoteOn.HW_Val
DI13
BV198
Y00p
Digital input remote ON - Input value
Bool
R
RemoteOn.ReadVal
DI14
BV199
Y00p
Digital input supply filter alarm - Hardware value
Bool
R
SupplyAlrmFilter.HW_Val
DI15
BV200
Y00p
Digital input supply filter alarm - Input value
Bool
R
SupplyAlrmFilter.ReadVal
DI16
BV201
Y00p
Digital input supply filter 2 alarm - Hardware value
Bool
R
SupplyAlrmFilter_2.HW_Val
DI17
BV202
Y00p
Digital input supply filter 2 alarm - Input value
Bool
R
SupplyAlrmFilter_2.ReadVal
DI18
BV203
Y00p
Digital input return filter alarm - Hardware value
Bool
R
ReturnAlrmFilter.HW_Val
DI19
BV204
Y00p
Digital input return filter alarm - Input value
Bool
R
ReturnAlrmFilter.ReadVal
DI20
BV205
Y00p
Digital Input door switch- Hardware value
Bool
R
Door_Switch.HW_Val
DI1435
BV1457
Y00p
Digital Input door switch-Input value
Bool
R
Door_Switch.ReadVal
DI1436
BV1458
Y00p
Digital Input recovery clogeed- Hardware value
Bool
R
Recovery_clogeed.HW_Val
DI1433
BV1455
Y00p
Digital Input recovery clogeed -Input value
Bool
R
Recovery_clogeed.ReadVal
DI1434
BV1456
Y00q
Digital input freeze alarm - Hardware value
Bool
R
FreezeHeat_Alrm.HW_Val
DI21
BV206
Y00q
Digital input freeze alarm - Input value
Bool
R
FreezeHeat_Alrm.ReadVal
DI22
BV207
Y00q
Digital input heating overload - Hardware value
Bool
R
DIN_AlHeat.HW_Val
DI23
BV208
Y00q
Digital input heating overload - Input value
Bool
R
DIN_AlHeat.ReadVal
DI24
BV209
Y00q
Digital input cooling alarm - Hardware value
Bool
R
CoolAlrm.HW_Val
DI25
BV210
Y00q
Digital input cooling alarm - Input value
Bool
R
CoolAlrm.ReadVal
DI26
BV211
Y00q
Digital input humidifier alarm - Hardware value
Bool
R
HumAlrm.HW_Val
DI27
BV212
Y00q
Digital input humidifier alarm - Input value
Bool
R
HumAlrm.ReadVal
DI28
BV213
Y00q
Digital input fire alarm - Hardware value
Bool
R
DIN_Fire.HW_Val
DI29
BV214
Y00q
Digital input fire alarm - Input value
Bool
R
DIN_Fire.ReadVal
DI30
BV215
Y00q
Digital input fan overload alarm - Hardware value
Bool
R
DIN_FanOvld.HW_Val
DI31
BV216
Y00q
Digital input fan overload alarm - Input value
Bool
R
DIN_FanOvld.ReadVal
DI32
BV217
Y00r
Digital input economy mode - Hardware value
Bool
R
DIN_Eco.HW_Val
DI33
BV218
Y00r
Digital input economy mode - Input value
Bool
R
DIN_Eco.ReadVal
DI34
BV219
Y00r
Digital input precomfort mode - Hardware value
Bool
R
DIN_PreComf.HW_Val
DI35
BV220
Y00r
Digital input precomfort mode - Input value
Bool
R
DIN_PreComf.ReadVal
DI36
BV221
Y00r
Digital input comfort mode - Hardware value
Bool
R
DIN_Comf.HW_Val
DI37
BV222