Carel kVent Скачать руководство пользователя страница 34

 

kVent – rel 3.1 – 22/06/2018 

34

6.7  FANS menu in main menu  

 

Mask 

code 

Description 

Type 

Default 

UoM 

Range 

R/W 

Variable Name 

BMS 

BacNet 

Supply fan - Hardware value 

Bool 

  

 

 

SupplyFan.HW_Val 

DI49 

BV234 

Supply fan - Value 

Bool 

  

 

 

SupplyFan.Ctrl 

DI5 

BV172 

Hours counter supply fan 

UDInt 

  

 

 

HC_SupplyFan_1.Hrs 

IR220 

PIV220 

D001 

Hours counter supply fan 

UDInt 

 

0...999999 

R/W 

HC_SupplyFan_1.MaintThrsh 

HR128 

PIV128 

D002 

Hours counter supply fan 

Bool 

  

 

0...1 

R/W 

HC_SupplyFan_1.Res 

C22 

BV578 

D003 

Supply fan - Manual value 

USInt 

  

 

0...2 

R/W 

SupplyFan.Man 

HR130 

PIV130 

D004 

Modulating supply fan - Manual mode analog 
output 

USInt 

  

 

0...101 

R/W 

ModulSupplyFan.Man 

HR131 

PIV131 

Return fan - Hardware value 

Bool 

  

 

 

ExhFan.HW_Val 

DI50 

BV235 

Return fan - Value 

Bool 

  

 

 

ExhFan.Ctrl 

DI6 

BV176 

Hours counter return fan 

UDInt 

  

 

 

HC_ExhFan_1.Hrs 

IR222 

PIV222 

D005 

Hours counter return fan 

UDInt 

 

0...999999 

R/W 

HC_ExhFan_1.MaintThrsh 

HR132 

PIV132 

D006 

Hours counter return fan 

Bool 

  

 

0...1 

R/W 

HC_ExhFan_1.Res 

C23 

BV583 

D007 

Return fan - Manual value 

USInt 

  

 

0...2 

R/W 

ExhFan.Man 

HR134 

PIV134 

D008 

Modulating return fan - Manual mode analog 
output 

USInt 

  

 

0...101 

R/W 

ModulExhFan.Man 

HR135 

PIV135 

D009 

Minimum fan power 

Real 

30.0 

0.0...100.0 

R/W 

MinFanPwr 

HR136 

AV136 

D010 

Supply k factor 

Real 

140.0 

 

0.0...999.9 

R/W 

K_FactorSupply 

HR137 

AV137 

D011 

Supply air flow setpoint 

Real 

4000.0 

m3h 

0.0...99999.0 

R/W 

SupplyAirFlowSet 

HR138 

AV138 

D012 

Return k factor 

Real 

140.0 

 

0.0...999.9 

R/W 

K_FactorExh 

HR139 

AV139 

D013 

Return air flow setpoint 

Real 

4000.0 

m3h 

0.0...99999.0 

R/W 

ExhAirFlowSet 

HR140 

AV140 

Unit of measure for user interface 

DInt 

 

 

Uom_Msk 

 

 

D014 

Supply air pressure setpoint 

Real 

200.0 

Pa 

0.0...9999.99 

R/W 

SupplyAirPSet 

HR141 

AV141 

D015 

Return air pressure setpoint 

Real 

200.0 

Pa 

0.0...9999.99 

R/W 

ExhAirPSet 

HR142 

AV142 

Supply fan - Value 

Bool 

  

 

 

SupplyFan.Ctrl 

DI5 

BV172 

Modulating supply fan - Hardware value 

Real 

  

 

ModulSupplyFan.HW_Val 

IR76 

AV76 

D016 

Supply fan PID - Proportional (Kp) 

Real 

0.02 

 

0.1...999.9 

R/W 

PID_Supply.Kp 

HR143 

AV143 

D017 

Supply fan PID - Integral (Ti) 

UInt 

0...30000 

R/W 

PID_Supply.Ti 

HR144 

PIV144 

D018 

Supply fan PID - Derivative (Td) 

UInt 

0...30000 

R/W 

PID_Supply.Td 

HR145 

PIV145 

Return fan - Value 

Bool 

  

 

 

ExhFan.Ctrl 

DI6 

BV176 

Modulating return fan - Hardware value 

Real 

  

 

ModulExhFan.HW_Val 

IR79 

AV79 

D019 

Exhaust fan PID - Proportional (Kp) 

Real 

0.02 

 

0.1...999.9 

R/W 

PID_Exh.Kp 

HR146 

AV146 

D020 

Exhaust fan PID - Integral (Ti) 

UInt 

0...30000 

R/W 

PID_Exh.Ti 

HR147 

PIV147 

D021 

Exhaust fan PID - Derivative (Td) 

UInt 

0...30000 

R/W 

PID_Exh.Td 

HR148 

PIV148 

D022 

Delay between damper and supply fan 

UInt 

0...65535 

R/W 

DT_SupplyFan 

HR149 

PIV149 

D023 

Supply fan idle time 

UInt 

40 

20...65535 

R/W 

IdleT_SupplyFan 

HR150 

PIV150 

D024 

Supply fan speed in idle mode 

Real 

50.0 

0.0...999.9 

R/W 

ManSupplyFanIdle 

HR151 

AV151 

D025 

Delay to switch OFF supply fan 

UInt 

70 

0...65535 

R/W 

DOff_SupplyFan 

HR152 

PIV152 

D026 

Delay between fan and damper 

UInt 

15 

0...65535 

R/W 

DT_Dmp 

HR153 

PIV153 

D027 

Delay between damper and return fan 

UInt 

10 

0...65535 

R/W 

DT_ExhFan 

HR154 

PIV154 

D028 

Return fan idle time 

UInt 

30 

0...65535 

R/W 

IdleT_ExhFan 

HR155 

PIV155 

D029 

Return fan speed in idle mode 

Real 

40.0 

0.0...999.9 

R/W 

ManExhFanIdle 

HR156 

AV156 

D030 

Delay to switch OFF return fan 

UInt 

60 

0...65535 

R/W 

DOff_ExhFan 

HR157 

PIV157 

D031 

Supply fan speed in fire alarm 

Real 

0.0 

0.0...100.0 

R/W 

FireSupplySpeed 

HR158 

AV158 

D032 

Return fan speed in fire alarm 

Real 

0.0 

0.0...100.0 

R/W 

FireExhSpeed 

HR159 

AV159 

D033 

Fire alarm threshold 

Real 

85.0 

°C 

-999.9...999.9 

R/W 

FireThrsh 

HR160 

AV160 

Air quality request for fan 

Real 

  

 

AirQualFan 

IR224 

AV224 

D034 

PID CO2 regulation - Proportional gain 

Real 

0.1 

 

-999.99...999.99 

R/W 

DevCfg_PID_Seq_CO2[1].Kp 

HR161 

AV161 

D035 

PID CO2 regulation - Integral time 

UInt 

300 

 

0...65535 

R/W 

DevCfg_PID_Seq_CO2[1].Ti 

HR162 

PIV162 

D036 

Supply fan maximum 

Real 

30.0 

 

0.0...100.0 

R/W 

SupplyFanMax 

HR163 

AV163 

D037 

Supply air flow alarm threshold 

Real 

50.0 

m3h 

0.0...9999.9 

R/W 

WarnThrshSupplyFlw 

HR164 

AV164 

D038 

Return air flow alarm threshold 

Real 

50.0 

m3h 

0.0...9999.9 

R/W 

WarnThrshExhFlw 

HR165 

AV165 

D039 

Supply air pressure alarm threshold 

Real 

50.0 

Pa 

0.0...9999.9 

R/W 

AlrmSupplyAirP 

HR166 

AV166 

D040 

Return air pressure alarm threshold 

Real 

50.0 

Pa 

0.0...9999.9 

R/W 

AlrmExhAirP 

HR167 

AV167 

D041 

Fan speed increase in case of filter warning 

Real 

10.0 

-999.9...999.9 

R/W 

FilterWarnFanIncr 

HR168 

AV168 

D042 

Supply fan set in Boost mode 

Real 

50.0 

0.0…100.0 

R/W 

MinFanPwr_Supply 

HR1084 

AV1450 

D043 

Return fan set in Boost mode 

Real 

50.0 

0.0…100.0 

R/W 

MinFanPwr_Return 

HR1085 

AV1451 

D044 

Pressure set HEPA filter 

Real 

 

Pa 

0.0...9999.9 

R/W 

HepaAirPSet 

HR1105 

AV1512 

D045 

Maximum Pressure set HEPA filter 

Real 

 

Pa 

0.0...9999.9 

R/W 

HepaAirPSet_Max 

HR1106 

AV1513 

D046 

Max Fan Speed  

Real 

 

0.0…100.0 

R/W 

HepaFansReqMax 

HR1107 

AV1514 

 

6.8  RECOVERY menu in main menu  

Mask 

code 

Description 

Type 

Default 

UoM 

Range 

R/W 

Variable Name 

BMS 

BacNet 

Recovery device - Hardware value 

Bool 

 

 

 

RecoveryPump.HW_Val 

DI57 

BV242 

Recovery device - Value 

Bool 

 

 

 

RecoveryPump.Ctrl 

DI58 

BV243 

Hours counter recovery 

UDInt 

 

 

 

HC_RecoveryPump.Hrs 

IR237 

PIV237 

E001 

Hours counter recovery 

UDInt 

 

0...999999 

R/W 

HC_RecoveryPump.MaintThrsh 

HR241 

PIV241 

E002 

Hours counter recovery 

Bool 

 

 

0...1 

R/W 

HC_RecoveryPump.Res 

C28 

BV699 

E003 

 

USInt 

 

0...2 

R/W 

RecoveryManINT 

HR243 

PIV243 

E004 

Modulating heat recovery output - Manual mode 
analog output 

USInt 

 

 

0...101 

R/W 

HeatRecovery.Man 

HR244 

PIV244 

E005 

Modulating mixing damper output - Manual mode 
analog output 

USInt 

 

 

0...101 

R/W 

ModulMixDamp.Man 

HR245 

PIV245 

Heating request 

Real 

 

 

 

Heating_PID_Seq[2] 

IR239 

AV239 

E006 

PID Heating regulation - Proportional gain 

Real 

5.0 

 

0.0...999.9 

R/W 

DevCfg_PID_Seq_Heat[2].Kp 

HR246 

AV246 

Содержание kVent

Страница 1: ...kVent rel 3 1 22 06 2018 1 kVent Controller for ventilation units Manual H i g h E f f i c i e n c y S o l u t i o n s...

Страница 2: ...kVent rel 3 1 22 06 2018 2...

Страница 3: ...ontrollers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and...

Страница 4: ...kVent rel 3 1 22 06 2018 4...

Страница 5: ...CO2 Regulation 25 5 12 Boost function 25 5 13 Minor functions 25 5 14 Import Export parameters 25 6 PARAMETERS TABLE 26 6 1 INFO menu in main mask 26 6 2 SET menu in main mask 29 6 3 MODE menu in mai...

Страница 6: ...e control Air flow control Protection Filters Fire Smoke alarm Frost protection Door switch Interface Browser interface based on WebKit pGDE for advanced function and service thTune for end user 3 dif...

Страница 7: ...cables be laid parallel to the power cables Keep the paths of the probe cables as short as possible and avoid making spiral paths that enclose power devices In case of malfunctions do not attempt to r...

Страница 8: ...ame FieldBus port for ModbusMaster 19200 8N2 With the following parameters is possible to define a different Frame Ha91 Stop bits Ha92 Parity Display protocol on port DISP ModBus master protocol on po...

Страница 9: ...alog outputs Out Y PWM output not optically isolated 2 Analog outputs Out Y Output for single pole stepper motor 1 TOTAL ANALOG OUTPUTS 2 Digital outputs Out NO NC relay output 1 Out NO relay output 5...

Страница 10: ...kVent rel 3 1 22 06 2018 10 Connections example 2 4 3...

Страница 11: ...ure AI4 Fresh temperature AI3 Recovery ON OFF DO10 Recovery 3point valve DO23 DO24 Modulating recovery AO6 Recovery 2 steps DO36 DO37 3 Glycol Supply temperature AI1 Exhaust temperature AI4 Fresh temp...

Страница 12: ...ve control Back water temperature AI6 Fresh temperature AI3 Heat 1 DO4 Modulating heat AO3 Heat 2 DO6 Heat 3 point valve DO17 DO18 Cool Heat common AO12 3 0 10V valve in common with cool Back water te...

Страница 13: ...3 point valve DO27 DO28 Modulating preheater AO7 4 1 modulating After preheater temperature AI11 Modulating preheater AO7 Preheater back water temperature AI10 Preheater 3 point valve DO27 DO28 Prehea...

Страница 14: ...ulating exhaust fan AO2 1 VAV Supply air pressure AI13 Exhaust air pressure AI14 Modulating supply fan AO1 Modulating exhaust fan AO2 2 CAV Supply air pressure AI13 Exhaust air pressure AI14 Modulatin...

Страница 15: ...r 14 Ga66 Exhaust air pressure 12 Gb23 Comfort 11 Gc21 Preheater 11 Gd11 IEC 15 Ga 71 Supply humidity 13 Gb25 Supply filter alarm 12 Gc23 Humidifier 12 Gd12 Cool Heat signal 24 GaB6 VOC sensor 14 Gb27...

Страница 16: ...update the application software of the controllers family with the following methods 1 Update from computer by USB cable 2 Update via USB flash drive 3 Update with file transfer via FTP Attention only...

Страница 17: ...directory on the computer to the UPGRADE directory on the kVent controller 3 Access the system menu on the kVent and select UPGRADE Note when having loaded the update file to the UPGRADE directory vi...

Страница 18: ...and probes are available in a menu connected to the synoptics The individual screens of the synoptics are shown below Set In this menu is possible to see the current setpoint and the working mode def...

Страница 19: ...ck Enable scheduler Clock 2s thTune scheduler settings Fan Change working setpoint 1 ECO 2 PRECOMFORT 3 COMFORT 4 STOP On Off Switch ON OFF th Tune display Exit from settings Clock Mode for 3s Run boo...

Страница 20: ...e comfort zones are ECO PRECOMFORT and COMFORT This working mode can change the following sets if the functions are activated 1 Supply temperature a Economy Z001 b Precomfort Z002 c Comfort Z003 2 Roo...

Страница 21: ...ured by Service I003 No serious alarm On by digital input On by the OR of the following conditions o On by pGD X00a o On by BMS o On by thTune if present o On by scheduler if enabled Variable mode is...

Страница 22: ...reshold The bypass damper can be modulated to reach the desired temperature for the supply air temperature because the freecooling can be considered as the first step of sequential PID regulation In c...

Страница 23: ...e below an example with devices with the same power Min inverter power 20 Max heaters power 33 3kW In this case the second heater will start when the request reach the threshold calculated in the foll...

Страница 24: ...decrease the efficiency of the unit kVent provides a control on external temperature and after preheater device If the unit has a preheater the after preheater temperature is considered for recovery...

Страница 25: ...mode menu X00b or by TH Tune pressing thogheter the buttons Clock Mode for 3s The maximum Boost time is settable on the Setting menu through the parameter H023 5 13 Minor functions Antistack procedure...

Страница 26: ...0l Supply humidity probe Probe value Real rh R SupplyHum ReadVal IR88 AV88 Y00l Suction temperature probe Probe value Real rh R FreshAirHum ReadVal IR89 AV89 Y00l Return CO2 sensor Probe value Real pp...

Страница 27: ...nt valve close Value Bool R CoolVlv_Cl Ctrl DI84 BV269 Y00y Reverse 3point valve open Hardware value Bool R CoolHeatVlv_Op HW_Val DI85 BV270 Y00y Reverse 3point valve open Value Bool R CoolHeatVlv_Op...

Страница 28: ...8 Y0ag Ziehl Abegg return fan electrical info Motr temperature C Real R MB_Devices FanElectricalInfo_Z A_2 MotTemp IR119 AV119 Y0ah Supply fan Value Bool R SupplyFan Ctrl DI5 BV172 Y0ah Modulating sup...

Страница 29: ...dity setpoint Economy Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP Economy HR7 AV7 Z008 Humidity setpoint PreComfort Real 50 0 rh 0 0 100 0 R W UnitSetP HumSetP PreComfort HR8 AV8 Z009 Humidity setpoin...

Страница 30: ...ed 0 StartMont h HR48 PIV48 Z00e Last day of period USInt 2 1 31 R W Scheduler_OnOffUnit Scheduler _1 VacationsSched 0 EndDay HR49 PIV49 Z00e Last month of period USInt 1 1 12 R W Scheduler_OnOffUnit...

Страница 31: ...PIV77 Z00f Special month USInt 1 1 12 R W Scheduler_OnOffUnit Scheduler _1 SpecDaysSched 5 SpecialM onth HR78 PIV78 Z00f Unit status of the special day 0 OFF 1 ECONOMY 2 PRE COMFORT 3 COMFORT 4 AUTO...

Страница 32: ...R210 PIV210 A042 Time minimum ON ON reheater device UInt 60 s 0 65535 R W ReHeatMinOnOnSameT HR211 PIV211 A043 Minimum reheater hot water valve Real 20 0 0 0 100 0 R W ReHW_MinPID HR212 AV212 A044 Min...

Страница 33: ...Hours counter reverse 2nd step UDInt 0 0 999999 R W HC_Rev_2 MaintThrsh HR326 PIV326 C006 Hours counter reverse 2nd step Bool 0 1 R W HC_Rev_2 Res C38 BV814 C007 Reverse device 2nd step Manual value U...

Страница 34: ...999 9 R W ManSupplyFanIdle HR151 AV151 D025 Delay to switch OFF supply fan UInt 70 s 0 65535 R W DOff_SupplyFan HR152 PIV152 D026 Delay between fan and damper UInt 15 s 0 65535 R W DT_Dmp HR153 PIV15...

Страница 35: ...ating running Bool 0 1 R W FastHeatTrig C30 BV734 E032 Fast heating stop Bool 0 1 R W FastHeatStop C31 BV735 E033 Fast heating time UInt 1500 s 0 65535 R W FastHeatT HR272 PIV272 E034 Fast cooling thr...

Страница 36: ...999 9 999 9 R W AI_ReadFnt 4 Param Min_Val HR781 AV781 Ga19 Analog input functions Maximum value Real 105 0 C 999 9 999 9 R W AI_ReadFnt 4 Param Max_Val HR782 AV782 Ga20 Analog input functions Offset...

Страница 37: ...nt 0 0 70 R W AI_ReadFnt 15 Ch HR844 IV844 Ga72 Analog input functions Type USInt 43 0 50 R W AI_ReadFnt 15 Param Typ HR846 PIV846 Ga73 Analog input functions Minimum value Real 0 0 rh 999 9 999 9 R W...

Страница 38: ...5 Analog input functions Offset Real 0 0 rh 99 9 99 9 R W AI_ReadFnt 25 Param Offset HR909 AV909 DIGITAL IN SET menu 6 10 2 Mask code Description Type Default UoM Range R W Variable Name BMS BacNet Di...

Страница 39: ...s Priority USInt R DI_ReadFnt 20 Prio IR405 PIV405 Digital input functions Status Bool R DI_ReadFnt 20 Hw_Val DI270 BV1797 Gb39 Digital input functions Channel DInt 0 0 70 R W DI_ReadFnt 20 Ch HR948 I...

Страница 40: ...ctions Channel DInt 0 0 50 R W DO_ReadFnt 15 Ch HR984 IV984 Gc30 Digital output functions Logic Bool FALSE 0 1 R W DO_ReadFnt 15 Logic C311 BV1870 Digital output functions Priority USInt R DO_ReadFnt...

Страница 41: ...igital output functions Status Bool R DO_ReadFnt 35 Hw_Val DI308 BV1948 Gc69 Digital output functions Channel DInt 0 0 70 R W DO_ReadFnt 35 Ch HR1024 IV1024 Gc70 Digital output functions Logic Bool FA...

Страница 42: ...72 PIV472 Analog output functions Request Real R AO_ReadFnt 10 Hw_Val IR473 AV473 Gd10 Analog output functions Channel DInt 0 0 60 R W AO_ReadFnt 10 Ch HR1066 IV1066 Analog output functions Priority U...

Страница 43: ...s_PreHeat Economy_Ti HR1113 IV1520 H033 Modes set PID regulations PreHeat Real 5 0 999 9 999 9 R W PIDs_PreHeat Precomfort_Kp HR1132 AV1539 H034 Modes set PID regulations PreHeat Int 120 s 0 65535 R W...

Страница 44: ...uration not allowed Alarm status Bool R Al_UnitCfgError Active DI1037 BV2068 I001 Recovery application code USInt 0 0 4 R W AppCode_Rec HR83 PIV83 I001 Application heating code USInt 0 0 4 R W AppCode...

Страница 45: ...wing alarms log display screen The alarms log memorizes the kVent operation status when the alarms are triggered Each log entry is an even that can be displayed from among all of the events available...

Страница 46: ...eset Stop humidifier Al_SupplyAirHum_Prb DI1036 BV1036 A037 Unit configuration not allowed Auto reset Stop unit Al_UnitCfgError DI1037 BV1037 A038 Supply fan Offline Auto reset Stop unit Al_Offline_ZA...

Страница 47: ...current Auto reset Stop unit Al_LimMainsA_EBM_2 DI1107 BV1107 A108 Return fan Brake mode Auto reset Stop unit Al_BrakeMode_EBM_2 DI1108 BV1108 A109 Return fan Cable break Auto reset Stop unit Al_Cable...

Страница 48: ...m the release 2 1 0 there is the possibility to setup a different PID values for each devices in base of the working mode set The enabling is manage under the menu Settings parameter H028 8 4 HEPA fil...

Страница 49: ...ed the unit of measure from s to min on the time setting for the pump on the heating coils during the off time Fixed the DEV configuration changed FloatValve management now at the startup of the unit...

Страница 50: ...ant value added all the masks to set up the PID parameters for each coils in base of the working mode added the fresh modulating damper Condensing Unit Management Add the RU language Add the CZ langua...

Страница 51: ...kVent rel 3 1 22 06 2018 51...

Страница 52: ...changes or modifications to its products without prior notice All trademarks hereby referenced are the property of their respective owners CAREL is a registered trademark of CAREL INDUSTRIES Hqs in It...

Страница 53: ...kVent rel 3 1 22 06 2018 53 CAREL INDUSTRIES S p a Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com...

Отзывы: